Installation, use and maintenance instructions

Gas Burners

RS 45/M LN

Low-High-Low or Modulating Operation

C6505071 - 2915847 (2)

Содержание RS 45/M LN

Страница 1: ...Installation use and maintenance instructions Gas Burners RS 45 M LN Low High Low or Modulating Operation C6505071 2915847 2...

Страница 2: ...d layout 16 Burner firing rates according to air density 19 Start up report 23 N B Figures mentioned in the text are identified as follows 1 A part 1 of figure A same page as text 1 A p 4 part 1 of fi...

Страница 3: ...ANDARDS see page 9 MODEL RS 45 M LN Output 1 MAX MBtu hr 717 2037 1969 _ 210 597 577 _ kW MIN MBtu hr kW 341 100 Fuel Natural gas Max delivery SCFH 2037 Pressure at maximum delivery 2 natural gas WC 5...

Страница 4: ...or 24 Burner terminal strip 25 Air damper 26 Bracket for mounting the PID modulating controller RWF40 optional 27 Pilot burner attachment Note If the flame relay 22 A pushbutton lights up it indicates...

Страница 5: ...ratures and or altitudes MINIMUM FURNACE DIMENSIONS B The firing rates were set in relation to certified test boil ers Figure B indicates the diameter and length of the test combustion chamber Example...

Страница 6: ...Find the nearest pressure value to your result in col umn 1 of the table A Read off the corresponding output on the left Example RS 45 M LN Maximum output operation Natural gas Gas ring 2 B p 8 adjust...

Страница 7: ...from the graduated sector 5 Remove the screws 2 from the slide bars 3 Remove screw 1 and pull the burner back on slide bars 3 by about 4 Disconnect the wires from the probe and the electrode and then...

Страница 8: ...until the notch identified is aligned with screw 4 Tighten the screws 1 and 4 fully down Example Burner output 1515 MBtu hr If we consult diagram C we find that for this output the adjustments are ou...

Страница 9: ...he pilot gas train must be connected to the gas attachment 5 A and can enter the burner from the right or left side GAS TRAIN B It must be type approved according to required local standards and is su...

Страница 10: ...he cams simply check that they are set as indicated below Red cam 90 Limits rotation toward maximum position When the burner is at max output the gas butterfly valve must be fully open 90 Blue cam 0 L...

Страница 11: ...wn on page 5 In the above instructions we left the burner running in MIN output operation Now press switch 2 A increase output and keep it pressed until the servomotor has opened the air damper and th...

Страница 12: ...asure the gas delivery Note The servomotor follows the adjustment of cam only when the cam angle is reduced If it is necessary to increase the cam angle first increase the servomotor angle with the sw...

Страница 13: ...etween the air pres sure switch and the suction inlet of the fan In this way the air pressure switch operates as differential pressure switch 6 LOW GAS PRESSURE SWITCH B Adjust the low gas pressure sw...

Страница 14: ...the outside of the burner taking special care with the linkages joints and cam Combustion Adjust the burner if the combustion values found at the beginning of the operation do not comply with the reg...

Страница 15: ...ided for auto matically by the boiler load control system If this is not the case a time switch should be fitted in series to IN to provide for burner shut down at least once every 24 hours RS 45 M LN...

Страница 16: ...16...

Страница 17: ...17...

Страница 18: ...18...

Страница 19: ...delivery must be reduced A reduction in delivery is accompanied by a reduction of the pressure in the combustion chamber Qr reduced delivery H1r reduced pressure Example a 5 delivery reduction Qr Q x...

Страница 20: ...mited by contact with orange cam The air damper closes completely to reduce thermal disper sion to a minimum Every time output is changed the servomotor automati cally modifies gas delivery gas butter...

Страница 21: ...inning of air pressure control Every air pressure failure after this moment in time leads to lock out too Lock out due to a fault in the flame supervision circuit Interruption of startup sequence beca...

Страница 22: ...ignal LT3 Fire signal LT5 Power on signal LT6 Limit satisfied MC Motor contactor MTR Fan motor MTRA Servomotor OC Operating control OCR High low control PS Remote lock out reset PSA Air pressure switc...

Страница 23: ...Fire High Fire High Fire High Fire High Fire High Fire OIL OPERATION Oil supply pressure Oil suction pressure Control Power Supply Burner Firing Rate Low Fire Flame Signal High Fire Flame Signal Low F...