PART III: OPERATION
30
Now adjust the pressure switches.
If it is necessary to change the burner output in the low flame stage, move the low flame cam: the low flame position matches the
ignition position. As far as burners fitted with Dungs MBC gas valves, the low flame cam does not match the ignition cam position,
that is why it must be set at about 30° more than the ignition cam.
Turn the burner off and then start it up again. If the adjustment is not correct, repeat the previous steps.
Fully-modulating burners
.To adjust the fully-modulating burners, use the
CMF
switch on the burner control panel (see next picture), instead of the
TAB
thermo-
stat as described on the previous paragraphs about the progressive burners. Go on adjusting the burner as described before, paying
attention to use the CMF switch intead of
TAB
.
The
CMF
position sets the oprating stages: to drive the burner to the high-flame stage, set CMF=1; to drive it to the low-flame stage, set
CMF=2.
Adjusting the combustion head
The burner is factory-adjusted with the combustion head in the "MAX" position, accordingly to the maximum power. To operate the bur-
ner at a lower power, progressively shift back the combustion head, towards the "MIN" position, screwing the screw
VRT
. The ID index
shows how much the combustion head moved.
CMF = 0 stop at the current position
CMF = 1 high flame operation
CMF = 2 low flame operation
CMF = 3 automatic operation
CAUTION: perform these adjustments once the burner is turned off and cooled.
Attention! if it is necessary to change the head position, repeat the air and fuel adjustments described above.
CMF
VRT
ID