PART III: OPERATION
29
Progressive burners
Once the procedure till step 8 described is accomplished, go on as follows:
set the low flame cam matching the high flame cam;
set the
TAB
thermostat to the minimum in order that the actuator moves progressively towards the low flame position;
The manual air damper control is not provided on these actuators. The adjustments must be carried out acting manually on the
cams.
Versione LME22
Versione LGK16-SQM40
move the low flame cam to the minimum to move the actuator towards the low flame until the two bearings find the adjusting screw
that refers to the lower position: screw
V
to increase the rate, unscrew to decrease.
Move again the low flame cam towards the minimum to meet the next screw on the adjusting cam and repeat the previous step; go
on this way as to reach the desired low flame point.
Berger STA12B3.41 (progressive and fully modulating burners)
Siemens SQN72.4A4Axx (progressive and fully modulating burners)
For DUNGS MB-DLE / Siemens VGD gas valves
Actuator camsBerger
STA
Siemens SQN72
High flame position (set to 90°)
ST2
I (
red
)
Low flame and ignition position
ST1
III (
orange
)
Stand-by position (set to 0°)
ST0
II (
blue
)
Not used
MV
IV (
black
)
Siemens SQM40
Actuator cams (SQM40)
I
High flame
II
Stand-by
III
Low flame - gas
IV
Low flame - oil
V
Ignition - oil
VI
Ignition - gas
MV
ST2
ST1
ST0
IV
III
II
I
AUTO/MAN
MAN-AUTO
mensions
Dimensions in
SQM4...
I
III
II
IV
V
VI
VI
V
IV
II
III
I
SC
SV
ID
V
SV
Gas butterfly valve clo
s
ed
Gas butterfly valve open