REFRIGERANT CONNECTIONS

The condenser has male rotalock connections.

The condenser is factory charged with dry nitrogen to
prevent the ingress of humidity and the connections are
sealed with plugs.

BEFORE REMOVING THE PLUGS FROM THE
CONNECTIONS, DISCHARGE THE NITROGEN BY
MEANS OF THE NEEDLE VALVE ON THE INLET
MANIFOLD.

Connection to the condenser can be achieved with one of the
following rotalock connectors:
3a)  straight connectors: see fig. 3a;
3b)  right angle connectors (supplied on request): see fig 3b;
3c)  service valves (supplied on request):  see fig. 3c:
to which the interconnecting pipework is connected.

A: ROTALOCK
CONNECTIONS
B: SEAL

Fig. 3

Take care that the connections are correctly made and in
particular do not invert the inlet and outlet connections (see fig.
4)

Fig. 4

Run the refrigeration lines taking care to ensure the following
(see also fig. 5);

  use straight line routes wherever possible;

A: discharge line
B: liquid line
C: trap

Fig. 5

  incline the discharge line with a gradient of 1/100 in the

direction of flow to facilitate oil entrainment;

  make a ‘U’ trap in the discharge line at the bottom of any

vertical risers;

  thermally insulate the refrigerant liquid line wherever it may

be exposed to sun;

  avoid any contact between the discharge line and the liquid

line.

Carry out the evacuation and charging of the complete
refrigerant circuit.

ELECTRICAL CONNECTIONS
CABLE SIZES - PROTECTION

(

see wiring diagram SECA ......... attached)

The condenser can be operated automatically and
autonomously (as a function of the refrigerant pressure ) and
therefore its power supply does not necessarily have to come
from the indoor unit to which it is connected. It can come from
the nearest convenient distribution board.
Check that the voltage and frequency of the power supply
correspond to the data shown on the nameplate of the
condenser.
Connect the power supply cable to the isolator introducing the
cable into the switch box through an IP 55 rated cable gland
and screw the terminals down tightly.
The following table lists the principal electrical data needed for
the connection.

VOLTAGE

No.

kW

FLA mm² FUS

CAL0231

230V/1ph/50

1

0,14

0,7

1,5

10 A

CAL0251

230V/1ph/50

1

0,14

0,7

1,5

10 A

CAL0331

230V/1ph/50

1

0,14

0,7

1,5

10 A

CAL0361

230V/1ph/50

2

0,28

1,4

1,5

10 A

CAL0511

230V/1ph/50

2

0,28

1,4

1,5

10 A

CAL0661

230V/1ph/50

2

0,28

1,4

1,5

10 A

CAL0801

230V/1ph/50

3

0,42

2,1

1,5

10 A

CAL1011

230V/1ph/50

3

0,42

2,1

1,5

10 A

CAL1301

230V/1ph/50

4

0,56

2,8

1,5

10 A

CAL1511

230V/1ph/50

5

0,70

3,5

1,5

10 A

CAL1801

230V/1ph/50

6

0,84

4,2

1,5

10 A

No.

: Number of fans

kW

kW : Nominal power

FLA

A

: Max. absorbed current

mm²

mm² : Recommended cable size

FUS

AT : Short circuit protection recommended

(for cable runs up to 30 m)

N.B. :  The condenser is fitted with overload protection (bi-
metallic switch in each motor) but not against short circuit; so
feed the condenser via a suitable protection device (fuse or
circuit breaker of appropriate rating ).

OK

B

A

3a

 3b

B

A

3c

B

A

B

1/100

A

max 5 m

max 30 m

1/100

A

B

max 15 m

B

A

C

1/100

Содержание CAL 0251

Страница 1: ...fore installing or servicing the unit read the instructions and the safety notes carefully BEDIENUNGSANLEITUNGEN ACHTUNG Bitte vor Installation oder jeglichem Eingriff an diesem Ger t die Bedienungs a...

Страница 2: ...to Holding Legs St tzbeine Pieds de support Patas 4 Connessioni frigorifere Connections Anschl sse Raccordements Conexiones 5 Sezionatore Mains Isolator Hauptschalter Sectionneur Interruptor 6 Regolat...

Страница 3: ...he condenser to the nearest possible point to the actual installation location by using a pallet truck or a forklift securing the unit to ensure that it does not fall off Carefully cut or remove the s...

Страница 4: ...g diagram SECA attached The condenser can be operated automatically and autonomously as a function of the refrigerant pressure and therefore its power supply does not necessarily have to come from the...

Страница 5: ...seldom fall below 0 C In cold climates it could cause excessive hunting of the system Fig 6 The values of SET and DIFF are adjusted by means of the adjusting screws which are accessed by removing the...

Страница 6: ...fore possible faults which may apparently be attributed do the condenser could actually be caused by external factors The following table lists the most likely faults FAULT POSSIBLE CAUSE CHECK CORREC...

Страница 7: ...3 Verificare che sia presente la guarnizione bianca in teflon B sull attacco rotalock A 4 Avvitare il giunto C sull attacco A GB 1 Unscrew the yellow cap E on the rotalock connection A 2 Remove the b...

Отзывы: