12.  Unicla oil injector part no. OIRA803

Unicla oil injector can be used to 

add additional system oil during the 

evacuation or refrigerant charging 

process. Or alternatively any similar 

injection device can be used. 

13. Discharge line analysis - pressure and temperature

After commissioning a Unicla compressor for the first time, some basic pressure and thermal 

loading checks will determine if the operating environment for the compressor is within Unicla 

specifications, and whether compressor durability is being maximised.  The following chart should 

be used as a guide for UWX550 and UWX440 compressors to analyse normally acceptable high 

side (discharge/head) pressures and discharge line temperatures for given ambient conditions.

Discharge Line Pressure - Temperature Chart - Unicla UWX compressors

Ambient Ideal Discharge Pressure

Discharge Line Temp ˚C

Temp ˚C

Note:  Allow 20% tolerance for humidity above 60% relative humidity.

If the system high side pressure or discharge line superheat range is not within these parameters, 

reference to the Unicla Service Manual is required, or reference to additional technical information 

for specifications and faults regarding condensing to air differentials.

• NR

 = not recommended as a continuous running phase, superheat may exceed 40°C, however 

specific system design may allow for higher condensing capacity to maximise compressor 

durability and performance.

• • NR

 = not recommended in most instances, superheat may exceed 50°C, however if condensing 

capacity allows for < 50°C superheat, momentary running in this phase may be considered.

If any further assistance or information is required please go to www.unicla.hk

or contact your nearest Unicla dealer.

˚C

˚F

kPa

PSI

1800rpm

2200rpm

3500rpm

Discharge line 

Superheat range

15

60

600 - 800

90 - 115

37 - 42

42 - 47

50 - 56

7 - 26

18

65

750 - 950

110 - 135

43 - 52

47 - 58

56 - 70

9 - 34

21

70

900 - 1100

130 - 160

50 - 57

55 - 64

66 - 76

10 - 36

24

75

1050 - 1300

155 - 190

58 - 64

66 - 73

77 - 83

12 - 37

27

80

1200 - 1550

185 - 220

65 - 72

73 - 80

75 - 89

13 - 37

30

85

1400 - 1750

200 - 250

68 - 77

75 - 86

79 - 92

14 - 38

33

90

1500 - 1900

215 - 275

72 - 85

80 - 94

89 - 97

14 - 39

35

95

1700 - 2100

245 - 300

77 - 90

86 - 98

93 - 102

15 - 40

38

100 1850 - 2250

265 - 325

85 - 92

94 - 102

• NR

17 > 40

41

105

200 - 2400

290 - 350

88 - 97

97 - 108

• NR

18 > 40

44

110 2250 - 2650

325 - 385

92 - 102

• NR

• • NR

18 > 50

47

115 2500 - 2900

370 - 420

102 - 110

• NR

• •NR

20 > 50

8.

Содержание UWX440

Страница 1: ...UWX550 and UWX440 Installation Guidelines...

Страница 2: ...ining professional information using representative graphs charts and tables Manufacturers specifications must be consulted for specific guidelines and performance data Unicla published data specific...

Страница 3: ...and screen 7 12 Oil injector 8 13 Discharge line analysis pressure and temperature 8 14 Refrigerantcharging 9 15 Compressor operation analysis report 10 Note This booklet is designed to assist the ins...

Страница 4: ...solid particle and chemical contamination before compressor fitting Solid particle contamination will cause direct compressor damage and starvation due to blocked system filters and screens see sectio...

Страница 5: ...the bolt then pull out Fig A Fig B Fig C 3 Fitting of discharge hose manifold Install the gasket Install Manifold Valve this is right hand view M10 x L60 Bolt Tightening tension 34 3 Nm 355 kg cm Con...

Страница 6: ...nd this amount is excluded from the quantities recommend above Note Oil quantity calculations are contained in the Unicla Service Handbook Total system oil requirement is based on 20 and 30 of refrige...

Страница 7: ...rvation of the compressor Warranty is void if these guidelines are not followed Unicla Oil Type Alternative Unidap 6 POE 68 Unidap 7 PAG 46 Recommended alternatives for Unicla Lubricant 6 Oil type and...

Страница 8: ...point Oil Green colouration exposure to copper oxidation Operation OK Recommendation Monitor oil condition and change if necessary Sight Glass Oil level low half point Oil Normal clean and transparen...

Страница 9: ...e Unicla inline mesh screen and filter insert should be used whenever there is risk of debris and fine particles entering the compressor through the suction line In the case of older systems where the...

Страница 10: ...ual is required or reference to additional technical information for specifications and faults regarding condensing to air differentials NR not recommended as a continuous running phase superheat may...

Страница 11: ...peration b If it is not possible to access the system at the evaporator or roof level then service points in suction and discharge lines away from the compressor are the next best option c If refriger...

Страница 12: ...ut oC Discharge Temp oC Pressure Drop Temp Difference oC Liquid Line Temp oC Suct LineTemp at Comp oC Discharge Superheat oC Evap Temp oC Condensor m s Subcooling oC Suct LineTemp at Evap oC Evap Duct...

Страница 13: ...Notes...

Страница 14: ...Unicla International Limited Unit 1209 1210 12F Manhattan Centre 8 Kwai Cheong Rd Kwai Chung N T Hong Kong Phone 852 2422 0180 Fax 852 2422 0680 Email sales unicla hk Website www unicla hk...

Отзывы: