9
Technical features
ENGLISH
1.8 - BOILER ANTIFREEZE
PROTECTION
It is activated by default
This protection can intervene only if the electricity and gas
supplies are connected.
If one of the two is not available and upon reset
11 (Sm) a
temperature level between 2 and 5°C is detected, the appliance
will behave as described in the table below, pos 2.
The heating system can be protected effectively from frost by
using antifreeze products with inhibitor for heating systems
(specific for multidmetal)
Do not use car engine antifreeze products as they could damage
the water gaskets.
P
O
S
ANTIFREEZE FUNCTION
Power supplies
SR
(*)
Status
antifreeze function
Actions
Electric
Gas
1
oN
oN
< 7 °C
oN
- Burner and Pump oN until T > 15°C
2
oN
off
< 5 ÷ 5 °C
oN
fAuLT SIGNAL CoDE 16
(with Electrical power supply oN)
(see par. 4.6 - Error CoDES).
Ignition inhibited.
off
oN
off
Ignition inhibited.
off
off
off
Ignition inhibited.
(*) Heating Sensor Sr par. 2.1