background image

General information

3

 

The system manager must be instructed concerning the use and operation of his heating system, in particular: 

•  Give the system manager these instructions, as well as the other appliance documents inserted in the envelope 

inside the packaging. 

The system manager must keep this documentation for future consultation

•  Inform the system manager about the importance of the air vents and the flue gas exhaust system, highlighting 

their essential features and the absolute prohibition of modifying them. 

•  Inform the system manager concerning control of the system’s water pressure as well as operations to restore it. 

•  Inform the system manager concerning correct control of temperatures, control units/thermostats and radiators 

to save energy.

•   Remember that the system must receive regular maintenance at least once a year and  

a  combustion 

analysis must be performed in the timetable foreseen by standards in force.

•  Should the appliance be sold or transferred to a new owner or if you move and leave the appliance, always make 

sure that the instruction booklet accompanies it in order to be consulted by the new owner and/or installer. 

The manufacturer will not be held liable in case of damage to persons, animals or objects resulting from 
failure to comply with the instructions contained in this manual.

4 -  INFORMATION FOR SYSTEM MANAGER
 

BY INSTALLER/MAINTENANCE TECHNICIAN

5 -  SAFETY WARNINGS

ATTENTION!
The appliance must be installed, adjusted and maintained by professionally qualified personnel, in 
compliance with standards and provisions in force. Incorrect installation can cause damage to persons, 
animals and objects for which the manufacturer cannot be held responsible.

DANGER!
NEVER attempt performing maintenance or repairs on the boiler on your own initiative. 
Any work must be done by professionally qualified personnel authorised by Unical. 
We recommend stipulating a maintenance contract.
Insufficient or irregular maintenance can jeopardise the operating safety of the appliance and cause damage 
to persons, animals and objects for which the manufacturer cannot be held responsible.

Modifying parts connected to appliance

Do not modify the following parts: 
-  the boiler 
-  the gas, air, water and electricity lines 
-  the flue gas pipe, safety valve and heating water drain pipe 
-  construction parts which affect the operating safety of the appliance

Smell of gas

Should a smell of gas be perceived, follow these safety guidelines: 
-   do not turn electric switches on or off 
-   do not smoke 
-   do not use the telephone 
-   close the gas shut-off valve 
-   air out the area where the gas leakage has occurred 
-   inform the gas supplier or a company specialised in installation and maintenance of heating systems.

Explosive and easily flammable substances

Do not use or store explosive or easily flammable materials (e.g. petrol, paints, paper) in the room where the ap

-

pliance is installed.

Содержание PANEL BOARD DUAL-STAGE CASCADE

Страница 1: ...NG CASCADE DUAL STAGE CASCADE C OK 1 2 1 2 1s C C C BUS ID 1 2 11 Mod Run 2 1 31 42 11 41 12 13 32 14 15 16 17 35 33 34 18 19 20 21 22 23 21 0 20 Servizio Data Ora Vacanze Visual Inf Utente Progr Tempo Tecnico Impianto Acqua Calda Circuito risc I Solare MF Circuito risc II C OK 1 2 1 2 1s C C C BUS ID 1 2 11 Mod Run 2 1 ...

Страница 2: ... TREATMENT The hardness of the supplied water conditions the frequency at which the domestic hot water exchanger must be cleaned If the water has a hardness greater than 15 f we recommend using water softeners chosen according to the characteristics of the water We recommend checking and cleaning the domestic hot water exchanger at the end of the first year of use and every two years thereafter on...

Страница 3: ...YSTEM MANAGER by installer maintenance technician 5 SAFETY WARNINGS Attention The appliance must be installed adjusted and maintained by professionally qualified personnel in compliance with standards and provisions in force Incorrect installation can cause damage to persons animals and objects for which the manufacturer cannot be held responsible DANGER NEVER attempt performing maintenance or rep...

Страница 4: ... is powered electrically green indicator light on and is set up for the production of hot water for heating Burner switch This switch connects and disconnects power to the burner With the switch at 0 the burner is not powered electrically With the switch at I the burner is powered electrically and is set up to run at request of the heating controller 6 OPERATING INSTRUCTIONS 6 1 MODULATING MASTER ...

Страница 5: ...safety thermostat in the boiler will trigger when the maximum temperature is reached with the consequent need to be rearmed Mixed zone system pump switch This switch connects and disconnects power to the mixed zone system pump With the switch at 0 the pump is not powered electrically With the switch at II the system pump is powered electrically and is ready to run IMPORTANT the system pump must al...

Страница 6: ...pear on the heating controller display Resetting safety thermostat IMPORTANT The safety thermostat is located below the cap indicated in the figure to the side To access it when the boiler blocks unscrew the plastic cap with a screwdriver after having reset the boiler put the plastic cap back on The safety thermostat can be triggered when the boiler overheats This can be solved first of all by low...

Страница 7: ... green indicator light on and is set up for the production of hot water for heating Burner switch This switch connects and disconnects power to the burner of the boiler n 1 With the switch at 0 the burner of the boiler n 1 is not powered electrically With the switch at I the burner of the boiler n 1 is powered electrically and is set up to run at request of the heating controller 6 2 MODULATING MA...

Страница 8: ...powered electrically With the switch at II the system pump is powered electrically and is ready to run IMPORTANT the system pump must always be ready to run before switching the burner on to allow heat to be dispersed Otherwise the safety thermostat in the boiler will trigger when the maximum temperature is reached with the consequent need to be rearmed Boiler n 1 primary ring system pump switch T...

Страница 9: ... the heating controller display Resetting safety thermostat of boiler n 1 IMPORTANT The safety thermostat is located below the cap indicated in the figure to the side To access it when the boiler blocks unscrew the plastic cap with a screwdriver after having reset the boiler put the plastic cap back on The safety thermostat can be triggered when the boiler overheats This can be solved first of all...

Страница 10: ...r the production of hot water for heating Burner switch This switch connects and disconnects power to the burner of the boiler n 2 With the switch at 0 the burner of the boiler n 2 is not powered electrically With the switch at I the burner of the boiler n 2 is powered electrically and is set up to run at request of the heating controller C OK 1 2 1 2 1s C C C BUS ID 1 2 11 Mod Run 2 1 31 42 11 41...

Страница 11: ...rmostat MUST be at the MAX full scale to the right As far as the working temperature setting is concerned see the paragraph PROGRAMMING THE HEATING CONTROLLER The value set will appear on the heating controller display The temperature will also be visible on the thermometer indicated at the side as long as the bulb has been positioned correctly in the sump on the upper part of the body of boiler n...

Страница 12: ...lue save the value and activate next value open level change the value save the value Depending on implementation ITALIAN ITALIAN 20 20 CONTRAST 0 Sensor day CHOICE OF READING HS 01 HS 02 SELECTION PROGRAMMING Default Individual values Value range Description DOMESTIC HOT WATER PROGRAMMING 00 01 OFF ON 1X DHW 00 OFF 10 C 70 C DHW TEMPERATURE 1 NOMINAL 60 C 10 C 70 C DHW TEMPERATURE 2 NOMINAL 60 C ...

Страница 13: ...ION 00 0 00 3 00 h MINIMUM OPENING TIME 2 00 h 0 00 3 00 h REDUCTION OPTIMISATION 00 00 00 h 0000 9999 PC ENABLE 0000 Default Individual values Value range Description PROGRAMMING HEATING CIRCUIT 2 SERVICE OPTIONS 5 C 40 C NOMINAL ROOM TEMPERATURE 1 20 C 5 C 40 C NOMINAL ROOM TEMPERATURE 2 20 C Exit level using RETURN 5 C 40 C NOMINAL ROOM TEMPERATURE 3 20 C 5 C 40 C REDUCED TEMPERATURE 10 C 5 C 4...

Страница 14: ...nd Sunday from 07 00 to 23 00 Value range Description PROGRAMMING TIMER HEATING CIRCUIT 2 HEATING CIRCUIT 1 PROGRAM DEFAULT SETTINGS Monday Tuesday Wednesday Thursday Friday from 06 00 to 08 00 from 16 00 to 22 00 Saturday and Sunday from 07 00 to 23 00 HEATING CIRCUIT 2 PROGRAM DEFAULT SETTINGS Monday Tuesday Wednesday Thursday Friday from 05 00 to 21 00 Saturday and Sunday from 06 00 to 22 00 Va...

Страница 15: ...t I the boiler is powered electrically green indicator light on and is set up for the production of hot water for heating Burner switch This switch connects and disconnects power to the burner With the switch at 0 the burner is not powered electrically With the switch at I the burner is powered electrically and is set up to run at request of the heating controller 6 4 DUAL STAGE MASTER PANEL BOARD...

Страница 16: ...safety thermostat in the boiler will trigger when the maximum temperature is reached with the consequent need to be rearmed Mixed zone system pump switch This switch connects and disconnects power to the mixed zone system pump With the switch at 0 the pump is not powered electrically With the switch at II the system pump is powered electrically and is ready to run IMPORTANT the system pump must al...

Страница 17: ...ppear on the heating controller display Resetting safety thermostat IMPORTANT The safety thermostat is located below the cap indicated in the figure to the side To access it when the boiler blocks unscrew the plastic cap with a screwdriver after having reset the boiler put the plastic cap back on The safety thermostat can be triggered when the boiler overheats This can be solved first of all by lo...

Страница 18: ... green indicator light on and is set up for the production of hot water for heating Burner switch This switch connects and disconnects power to the burner of the boiler n 1 With the switch at 0 the burner of the boiler n 1 is not powered electrically With the switch at I the burner of the boiler n 1 is powered electrically and is set up to run at request of the heating controller 6 5 DUAL STAGE MA...

Страница 19: ...powered electrically With the switch at II the system pump is powered electrically and is ready to run IMPORTANT the system pump must always be ready to run before switching the burner on to allow heat to be dispersed Otherwise the safety thermostat in the boiler will trigger when the maximum temperature is reached with the consequent need to be rearmed Boiler n 1 primary ring system pump switch T...

Страница 20: ...n the heating controller display Resetting safety thermostat of boiler n 1 IMPORTANT The safety thermostat is located below the cap indicated in the figure to the side To access it when the boiler blocks unscrew the plastic cap with a screwdriver after having reset the boiler put the plastic cap back on The safety thermostat can be triggered when the boiler overheats This can be solved first of al...

Страница 21: ...r the production of hot water for heating Burner switch This switch connects and disconnects power to the burner of the boiler n 2 With the switch at 0 the burner of the boiler n 2 is not powered electrically With the switch at I the burner of the boiler n 2 is powered electrically and is set up to run at request of the heating controller C OK 1 2 1 2 1s C C C BUS ID 1 2 11 Mod Run 2 1 31 42 11 41...

Страница 22: ...rmostat MUST be at the MAX full scale to the right As far as the working temperature setting is concerned see the paragraph PROGRAMMING THE HEATING CONTROLLER The value set will appear on the heating controller display The temperature will also be visible on the thermometer indicated at the side as long as the bulb has been positioned correctly in the sump on the upper part of the body of boiler n...

Страница 23: ...lue save the value and activate next value open level change the value save the value Depending on implementation ITALIAN ITALIAN 20 20 CONTRAST 0 Sensor day CHOICE OF READING HS 01 HS 02 SELECTION PROGRAMMING Default Individual values Value range Description DOMESTIC HOT WATER PROGRAMMING 00 01 OFF ON 1X DHW 00 OFF 10 C 70 C DHW TEMPERATURE 1 NOMINAL 60 C 10 C 70 C DHW TEMPERATURE 2 NOMINAL 60 C ...

Страница 24: ...ION 00 0 00 3 00 h MINIMUM OPENING TIME 2 00 h 0 00 3 00 h REDUCTION OPTIMISATION 00 00 00 h 0000 9999 PC ENABLE 0000 Default Individual values Value range Description PROGRAMMING HEATING CIRCUIT 2 SERVICE OPTIONS 5 C 40 C NOMINAL ROOM TEMPERATURE 1 20 C 5 C 40 C NOMINAL ROOM TEMPERATURE 2 20 C Exit level using RETURN 5 C 40 C NOMINAL ROOM TEMPERATURE 3 20 C 5 C 40 C REDUCED TEMPERATURE 10 C 5 C 4...

Страница 25: ...nd Sunday from 07 00 to 23 00 Value range Description PROGRAMMING TIMER HEATING CIRCUIT 2 HEATING CIRCUIT 1 PROGRAM DEFAULT SETTINGS Monday Tuesday Wednesday Thursday Friday from 06 00 to 08 00 from 16 00 to 22 00 Saturday and Sunday from 07 00 to 23 00 HEATING CIRCUIT 2 PROGRAM DEFAULT SETTINGS Monday Tuesday Wednesday Thursday Friday from 05 00 to 21 00 Saturday and Sunday from 06 00 to 22 00 Va...

Страница 26: ...verify water pressure in the boiler When the pressure drops below 1 bar it should be restored with the boiler cold until it reaches the static pressure relative to the highest point of the system by gradually opening the filling cock outside the boiler Close the filling cock when the proper pressure has been reached If water pressure must be continually restored contact an Authorised Assistance Ce...

Страница 27: ...Remarks ...

Страница 28: ...errors It also reserves the right to modify its products as deemed necessary or useful without jeopardising their essential features 46033 casteldario mantova italia tel 39 0376 57001 fax 39 0376 660556 info unical ag com export unical ag com www unical eu AG S p A 44880 1 st ed 09 16 www unical eu ...

Отзывы: