System manager operating instructions

31

42

32

12

13

12

13

Boiler n°2 primary ring system pump  switch

This switch connects and disconnects power to the +
system pump of the primary ring of boiler n°2:
-  With the switch at 

, the pump is not powered 

  electrically.

-  With  the  switch  at 

II

,  the  system  pump  is  powered 

electrically and is ready to run. 

IMPORTANT: 

the system pump must 

always

 be ready 

to run before switching the burner on to allow heat to be 
dispersed.
Otherwise, the safety thermostat in the boiler will trigger 
when the maximum temperature is reached with the 
consequent need to be rearmed.

Heating temperature control

Temperature is adjusted between a minimum of 0°C and 
a maximum of 90°C.

For the heating controller to work properly, the knob of 
the working thermostat MUST be at the MAX full-scale 
(to the “right”).
As far as the working temperature setting is concerned, 
see  the  paragraph  “PROGRAMMING THE  HEATING 
CONTROLLER”.

The value set will appear on the heating controller display. 

The temperature will also be visible on the thermometer 
indicated at the side, as long as the bulb has been 
positioned correctly in the sump on the upper part of the 
body of boiler n°2.
N.B. There could be a difference of a few degrees between 
the temperature displayed on the analogue thermometer 
and the heating control digital display.

Resetting safety thermostat

IMPORTANT: The safety thermostat is located below 
the cap indicated in the figure to the side. To access it 
when the boiler blocks, unscrew the plastic cap with 
a screwdriver; after having reset the boiler, put the 
plastic cap back on. 

The safety thermostat can be triggered when the boiler 
overheats.
This can be solved first of all by lowering the working 
temperature of the boiler.

V

I

V

I

Содержание PANEL BOARD DUAL-STAGE CASCADE

Страница 1: ...NG CASCADE DUAL STAGE CASCADE C OK 1 2 1 2 1s C C C BUS ID 1 2 11 Mod Run 2 1 31 42 11 41 12 13 32 14 15 16 17 35 33 34 18 19 20 21 22 23 21 0 20 Servizio Data Ora Vacanze Visual Inf Utente Progr Tempo Tecnico Impianto Acqua Calda Circuito risc I Solare MF Circuito risc II C OK 1 2 1 2 1s C C C BUS ID 1 2 11 Mod Run 2 1 ...

Страница 2: ... TREATMENT The hardness of the supplied water conditions the frequency at which the domestic hot water exchanger must be cleaned If the water has a hardness greater than 15 f we recommend using water softeners chosen according to the characteristics of the water We recommend checking and cleaning the domestic hot water exchanger at the end of the first year of use and every two years thereafter on...

Страница 3: ...YSTEM MANAGER by installer maintenance technician 5 SAFETY WARNINGS Attention The appliance must be installed adjusted and maintained by professionally qualified personnel in compliance with standards and provisions in force Incorrect installation can cause damage to persons animals and objects for which the manufacturer cannot be held responsible DANGER NEVER attempt performing maintenance or rep...

Страница 4: ... is powered electrically green indicator light on and is set up for the production of hot water for heating Burner switch This switch connects and disconnects power to the burner With the switch at 0 the burner is not powered electrically With the switch at I the burner is powered electrically and is set up to run at request of the heating controller 6 OPERATING INSTRUCTIONS 6 1 MODULATING MASTER ...

Страница 5: ...safety thermostat in the boiler will trigger when the maximum temperature is reached with the consequent need to be rearmed Mixed zone system pump switch This switch connects and disconnects power to the mixed zone system pump With the switch at 0 the pump is not powered electrically With the switch at II the system pump is powered electrically and is ready to run IMPORTANT the system pump must al...

Страница 6: ...pear on the heating controller display Resetting safety thermostat IMPORTANT The safety thermostat is located below the cap indicated in the figure to the side To access it when the boiler blocks unscrew the plastic cap with a screwdriver after having reset the boiler put the plastic cap back on The safety thermostat can be triggered when the boiler overheats This can be solved first of all by low...

Страница 7: ... green indicator light on and is set up for the production of hot water for heating Burner switch This switch connects and disconnects power to the burner of the boiler n 1 With the switch at 0 the burner of the boiler n 1 is not powered electrically With the switch at I the burner of the boiler n 1 is powered electrically and is set up to run at request of the heating controller 6 2 MODULATING MA...

Страница 8: ...powered electrically With the switch at II the system pump is powered electrically and is ready to run IMPORTANT the system pump must always be ready to run before switching the burner on to allow heat to be dispersed Otherwise the safety thermostat in the boiler will trigger when the maximum temperature is reached with the consequent need to be rearmed Boiler n 1 primary ring system pump switch T...

Страница 9: ... the heating controller display Resetting safety thermostat of boiler n 1 IMPORTANT The safety thermostat is located below the cap indicated in the figure to the side To access it when the boiler blocks unscrew the plastic cap with a screwdriver after having reset the boiler put the plastic cap back on The safety thermostat can be triggered when the boiler overheats This can be solved first of all...

Страница 10: ...r the production of hot water for heating Burner switch This switch connects and disconnects power to the burner of the boiler n 2 With the switch at 0 the burner of the boiler n 2 is not powered electrically With the switch at I the burner of the boiler n 2 is powered electrically and is set up to run at request of the heating controller C OK 1 2 1 2 1s C C C BUS ID 1 2 11 Mod Run 2 1 31 42 11 41...

Страница 11: ...rmostat MUST be at the MAX full scale to the right As far as the working temperature setting is concerned see the paragraph PROGRAMMING THE HEATING CONTROLLER The value set will appear on the heating controller display The temperature will also be visible on the thermometer indicated at the side as long as the bulb has been positioned correctly in the sump on the upper part of the body of boiler n...

Страница 12: ...lue save the value and activate next value open level change the value save the value Depending on implementation ITALIAN ITALIAN 20 20 CONTRAST 0 Sensor day CHOICE OF READING HS 01 HS 02 SELECTION PROGRAMMING Default Individual values Value range Description DOMESTIC HOT WATER PROGRAMMING 00 01 OFF ON 1X DHW 00 OFF 10 C 70 C DHW TEMPERATURE 1 NOMINAL 60 C 10 C 70 C DHW TEMPERATURE 2 NOMINAL 60 C ...

Страница 13: ...ION 00 0 00 3 00 h MINIMUM OPENING TIME 2 00 h 0 00 3 00 h REDUCTION OPTIMISATION 00 00 00 h 0000 9999 PC ENABLE 0000 Default Individual values Value range Description PROGRAMMING HEATING CIRCUIT 2 SERVICE OPTIONS 5 C 40 C NOMINAL ROOM TEMPERATURE 1 20 C 5 C 40 C NOMINAL ROOM TEMPERATURE 2 20 C Exit level using RETURN 5 C 40 C NOMINAL ROOM TEMPERATURE 3 20 C 5 C 40 C REDUCED TEMPERATURE 10 C 5 C 4...

Страница 14: ...nd Sunday from 07 00 to 23 00 Value range Description PROGRAMMING TIMER HEATING CIRCUIT 2 HEATING CIRCUIT 1 PROGRAM DEFAULT SETTINGS Monday Tuesday Wednesday Thursday Friday from 06 00 to 08 00 from 16 00 to 22 00 Saturday and Sunday from 07 00 to 23 00 HEATING CIRCUIT 2 PROGRAM DEFAULT SETTINGS Monday Tuesday Wednesday Thursday Friday from 05 00 to 21 00 Saturday and Sunday from 06 00 to 22 00 Va...

Страница 15: ...t I the boiler is powered electrically green indicator light on and is set up for the production of hot water for heating Burner switch This switch connects and disconnects power to the burner With the switch at 0 the burner is not powered electrically With the switch at I the burner is powered electrically and is set up to run at request of the heating controller 6 4 DUAL STAGE MASTER PANEL BOARD...

Страница 16: ...safety thermostat in the boiler will trigger when the maximum temperature is reached with the consequent need to be rearmed Mixed zone system pump switch This switch connects and disconnects power to the mixed zone system pump With the switch at 0 the pump is not powered electrically With the switch at II the system pump is powered electrically and is ready to run IMPORTANT the system pump must al...

Страница 17: ...ppear on the heating controller display Resetting safety thermostat IMPORTANT The safety thermostat is located below the cap indicated in the figure to the side To access it when the boiler blocks unscrew the plastic cap with a screwdriver after having reset the boiler put the plastic cap back on The safety thermostat can be triggered when the boiler overheats This can be solved first of all by lo...

Страница 18: ... green indicator light on and is set up for the production of hot water for heating Burner switch This switch connects and disconnects power to the burner of the boiler n 1 With the switch at 0 the burner of the boiler n 1 is not powered electrically With the switch at I the burner of the boiler n 1 is powered electrically and is set up to run at request of the heating controller 6 5 DUAL STAGE MA...

Страница 19: ...powered electrically With the switch at II the system pump is powered electrically and is ready to run IMPORTANT the system pump must always be ready to run before switching the burner on to allow heat to be dispersed Otherwise the safety thermostat in the boiler will trigger when the maximum temperature is reached with the consequent need to be rearmed Boiler n 1 primary ring system pump switch T...

Страница 20: ...n the heating controller display Resetting safety thermostat of boiler n 1 IMPORTANT The safety thermostat is located below the cap indicated in the figure to the side To access it when the boiler blocks unscrew the plastic cap with a screwdriver after having reset the boiler put the plastic cap back on The safety thermostat can be triggered when the boiler overheats This can be solved first of al...

Страница 21: ...r the production of hot water for heating Burner switch This switch connects and disconnects power to the burner of the boiler n 2 With the switch at 0 the burner of the boiler n 2 is not powered electrically With the switch at I the burner of the boiler n 2 is powered electrically and is set up to run at request of the heating controller C OK 1 2 1 2 1s C C C BUS ID 1 2 11 Mod Run 2 1 31 42 11 41...

Страница 22: ...rmostat MUST be at the MAX full scale to the right As far as the working temperature setting is concerned see the paragraph PROGRAMMING THE HEATING CONTROLLER The value set will appear on the heating controller display The temperature will also be visible on the thermometer indicated at the side as long as the bulb has been positioned correctly in the sump on the upper part of the body of boiler n...

Страница 23: ...lue save the value and activate next value open level change the value save the value Depending on implementation ITALIAN ITALIAN 20 20 CONTRAST 0 Sensor day CHOICE OF READING HS 01 HS 02 SELECTION PROGRAMMING Default Individual values Value range Description DOMESTIC HOT WATER PROGRAMMING 00 01 OFF ON 1X DHW 00 OFF 10 C 70 C DHW TEMPERATURE 1 NOMINAL 60 C 10 C 70 C DHW TEMPERATURE 2 NOMINAL 60 C ...

Страница 24: ...ION 00 0 00 3 00 h MINIMUM OPENING TIME 2 00 h 0 00 3 00 h REDUCTION OPTIMISATION 00 00 00 h 0000 9999 PC ENABLE 0000 Default Individual values Value range Description PROGRAMMING HEATING CIRCUIT 2 SERVICE OPTIONS 5 C 40 C NOMINAL ROOM TEMPERATURE 1 20 C 5 C 40 C NOMINAL ROOM TEMPERATURE 2 20 C Exit level using RETURN 5 C 40 C NOMINAL ROOM TEMPERATURE 3 20 C 5 C 40 C REDUCED TEMPERATURE 10 C 5 C 4...

Страница 25: ...nd Sunday from 07 00 to 23 00 Value range Description PROGRAMMING TIMER HEATING CIRCUIT 2 HEATING CIRCUIT 1 PROGRAM DEFAULT SETTINGS Monday Tuesday Wednesday Thursday Friday from 06 00 to 08 00 from 16 00 to 22 00 Saturday and Sunday from 07 00 to 23 00 HEATING CIRCUIT 2 PROGRAM DEFAULT SETTINGS Monday Tuesday Wednesday Thursday Friday from 05 00 to 21 00 Saturday and Sunday from 06 00 to 22 00 Va...

Страница 26: ...verify water pressure in the boiler When the pressure drops below 1 bar it should be restored with the boiler cold until it reaches the static pressure relative to the highest point of the system by gradually opening the filling cock outside the boiler Close the filling cock when the proper pressure has been reached If water pressure must be continually restored contact an Authorised Assistance Ce...

Страница 27: ...Remarks ...

Страница 28: ...errors It also reserves the right to modify its products as deemed necessary or useful without jeopardising their essential features 46033 casteldario mantova italia tel 39 0376 57001 fax 39 0376 660556 info unical ag com export unical ag com www unical eu AG S p A 44880 1 st ed 09 16 www unical eu ...

Отзывы: