b.
Using wire strippers, strip the rubber jacket
from both ends of the signal cable to reveal
approximately 15cm (5.9”) of wire.
c.
Strip the insulation from the ends.
d.
Using a wire crimper, crimp u-lugs on the
ends.
NOTE:
When connecting the wires, strictly
follow the wiring diagram found inside the
electrical box cover.
2. Remove the electric cover of the outdoor unit.
If there is no cover on the outdoor unit, take
off the bolts from the maintenance board and
remove the protection board.
(See Fig. 8.1)
Cover
Screw
Fig. 8.1
3. Connect the u-lugs to the terminals
Match the wire colors/labels with the labels
on the terminal block, Firmly screw the u-lug
of each wire to its corresponding terminal.
4. Clamp down the cable with the cable clamp.
5. Insulate unused wires with electrical tape.
Keep them away from any electrical or metal
parts.
6. Reinstall the cover of the electric control box.
Indoor Unit Wiring
1.
Prepare the cable for connection
a. Using wire strippers, strip the rubber jacket
from both ends of the signal cable to reveal
about 15cm (5.9”) of the wire.
b.
Strip the insulation from the ends of the wires.
c.
Using a wire crimper, crimp the u-lugs to
the ends of the wires.
2.
Rotate the sensor device’s installation bearer to
the other side. Then remove the cover of the
electrical box. (Also, remove the electrical box
also if its capacity is 18000btu/h and has
networking functionality.)
3.
Connect the u-lugs to the terminals.
Match the wire colors/labels with the labels on
the terminal block, Firmly screw the u-lug of
each wire to its corresponding terminal. Refer
to the Serial Number and Wiring Diagram
located on the cover of the electric control box.
Connective wiring diagram
Wiring diagram
Control box
CAUTION
•
While connecting the wires, please strictly
follow the wiring diagram.
•
The refrigerant circuit can become very
hot. Keep the interconnection cable away
from the copper tube.
4. Clamp down the cable with the cable clamp.
The cable must not be loose or pull on the
u-lugs.
5.
Reattach the electric box cover.
Fig. 8.2
Table 8.2: Other World Regions
Absorbed
maximum (A)
Area (mm²)
Nominal Cross-Sectional
d
6
0.75
6 - 10
1
10 - 16
1.5
16 - 25
2.5
25- 32
4
32 - 45
6
Installation bearer
of sensor device
21