Outdoor unit
35M
53M
70M
105M
105T
140T
160T
Electrical connections
Power supply
ODU --> IDU / Unit
singles
ODU --> IDU
ODU --> IDU
Unit singles
Unit singles
Unit singles
Unit singles
Unit singles
ODU - Voltage/
Frequency/Phases
V/Hz/n°
230 / 50 / 1
230 / 50 / 1
230 / 50 / 1
230 / 50 / 1
400 / 50 / 3 + N
400 / 50 / 3 + N
400 / 50 / 3 + N
ODU - n° cable/ section
2 x 2,5mm + T
2 x 2,5mm + T
2 x 2,5mm + T
2 x 4mm + T
4 x 2,5mm + T
4 x 2,5mm + T
4 x 2,5mm + T
IDU - Voltage/
Frequency/Phases
V/Hz/n°
-
-
230 / 50 / 1
230 / 50 / 1
230 / 50 / 1
230 / 50 / 1
230 / 50 / 1
IDU - n° cable/ section
-
-
2 x 1mm + T
2 x 1mm + T
2 x 1mm + T
2 x 1mm + T
2 x 1mm + T
Communication
type
n° cable/ section
3 x 1mm + T
3 x 1mm + T
2 x 0,2mm + T
2 x 0,2mm + T
2 x 0,2mm + T
2 x 0,2mm + T
2 x 0,2mm + T
Outdoor unit
MC2-Y
35M
53M
70M
105M
105T
140T
160T
Refrigerant lines
Liquid line
1/4”
1/4”
3/8”
3/8”
3/8”
3/8”
3/8”
mm
6,35
6,35
9,52
9,52
9,52
9,52
9,52
Gas line
3/8” 1/2” 5/8”
5/8”
5/8”
5/8”
5/8”
mm
9,52
12,7
15,9
15,9
15,9
15,9
15,9
Max. equivalent length
m
25
25
30
30
35
35
35
Max. length ODU / IDU
m
10
20
25
30
30
30
30
Refrigerant pre-charge
kg/m
0,87 / 5
1,35 / 5
1,5 / 5
2,4 / 5
2,4 / 5
2,8 / 5
2,95 / 5
GWP
tco
675
675
675
675
675
675
675
Tons of CO equivalent
t
t
0,59
0,91
1,01
1,62
1,62
1,89
1,99
Additional refrigerant charge
g/m
12
12
24
24
24
24
24
NOTE
•
at the max length of the pipes, the yield is about 90%
•
ODU: outdoor unit
IDU: indoor unit
Technical features (Light Commercial)