ROUTINE SERVICE
Warning!
Before doing any work on the boiler, make
sure that it and its components have cooled
Disconnect the boiler from the mains supply
and turn the gas supply at the appliance.
Warning!
Before cleaning the boiler, to protect the
control panel against splashing water.
Once a year, at the end of each heating season, it is
necessary make a general cleaning of the boiler.
Before carrying out any maintenance work, check that all the
precautions referred to in the previous paragraph have been
taken.
To do the maintenance, is necessary to:
- Remove tension using the main switch;
- Remove the burner, that in this case could be revised;
- Open the firebox door so is possible to accede to the room
combustion;
- Remove the access door to the smoking room;
- Check the integrity of internal components.
Checking seals and insulating fibers
The fiber insulation of the door, after a short
period of operation, may submit cracks; this,
however, does not reduce the insulating and
does not affect the duration.
Check the status of the seal which must not
show signs of deterioration; otherwise need to
be replaced, using Only original spare parts.
Check the status of the inspection cover gasket smoke
chamber.
In case of deterioration should be replaced, using Only
original spare parts
Burner Maintenance
The burner maintenance of the must be carried out by
central assistance authorized by Unical (punishment void the
warranty).
Check electrode ignition
The maintenance of the burner must be carried out by Central
assistance authorized by Unical (punishment void the
warranty).
Component:
Safety Thermostat
Expansion vessel
Door seal
Smoke chamber seal
Checking:
Does the thermostat make the boiler safe
in case of overheating?
Does the vessel contain the right amount
of air?
Is there smoke from the door seal?
Is there smoke from the chamber seal?
Intervention/ control method:
Bring the temperature of the boiler with
the pump stopped
Check the pressure of nitrogen.Replace
the boiler pressure(open the venting
pump). Open the closing taps of the
heating circuit.
Further tighten the screws of the door.
Replace the gasket seal and the seal
inside the door.
Tighten the nuts further closing of the
smoke chamber.Replace the seals
Components to be checked during the annual review