INSTALLATION 

 

WARNING:  All  the  operation  described  in  next  chapters  MUST  BE  DONE  BY  TRAINED  PEOPLE  ONLY.  Before  any 
operation on the unit, be sure that the electric supply is disconnected. 

5.1

 

GENERALITY 

When  installing  or  servicing  the  unit,  it  is  necessary  to  strictly  follow  the  rules  listed  in  this  manual,  to  conform  to  all  the 
specifications of the labels on the unit, and to take any possible precautions. Not observing the rules reported on this manual can 
create dangerous situations. 

 

After receiving the unit, immediately check its integrity. The unit left the factory in perfect condition; any eventual 
damage has to be questioned to the carrier and recorded on the Delivery Note before signing it. 

The company has to be informed, within 8 days, of the extent of the damage. The Customer should prepare a written statement of 
any severe damage. 

 

WARNING: The units are designed for outdoor installation. The place of installation must be entirely far away from 
fire risk. All the necessary measures should be adopted in order to prevent the fire risk in the place of installation. The 
outdoor ambient temperature shall not exceed 46°C. Above this value, the unit is no longer covered by the directives 
in force in the area of pressure equipment. 

 

WARNING: The unit should be installed so that adequate clearance is available for maintenance and repairation. The 
warranty does not cover costs related to platforms or handling equipment necessary for any maintenance. 

 

All maintenance and testing operations should be carried out only by QUALIFIED PERSONNEL. 

 

Before any operation on the unit, make sure the power supply is disconnected. 

 

WARNING: MOVING PARTS, RISK OF DEATH. 
Disconnect the power supply and ensure that the fan is stopped before opening the front panel. 

 

The temperatures of heads and discharge piping of the compressor are usually high. 

 

Be careful when working near condensing coils. 
The aluminum fins are very sharp and can cause serious injuries. 

 

After the maintenance operations, close the panels tightly with the fastening screws. 

5.2

 

LIFTING AND HANDLING 

When unloading and installing the unit, it is highly recommended to 
avoid  any  sudden  move  in  order  to  protect  the  inner  components. 
Units can be lifted by means of a forklift or, in alternative, of belts, 
being  sure  not  to  damage  the  lateral  panels  and  the  cover.  It  is 
important to keep the unit horizontal during these operations. 

 

5.3

 

LOCATION AND MINIMUM TECHNICAL CLEARANCES 

The all HP_OWER  units are designed for outdoor installation: any cover over the unit and location near trees (even if they partially 
cover  the  unit)  has  to  be  avoided  in  order  to  prevent  air  recirculation.  It  is  advisable  to  create  a  proper  basement,  with  a  size 
similar to unit foot-print. Unit vibration level is very low: it is advisable however, to fit a rigid rubber band between basement and 
unit  base-frame.  It  is  also  possible  to  install  anti-vibration  supports  (springs  or  rubbers)  to  keep  vibrations  at  a  very  low  level. 
Absolute care has to be taken to ensure adequate air volume to the condenser. Re-circulation of discharge air has to be avoided; 
failure to observe this point will result in poor performance or activation of safety controls. For these reasons it is necessary to 
observe the following clearances: 

Содержание HP OWER 60

Страница 1: ...User s and Installer s Manual 60 90 120 150...

Страница 2: ...L CONNECTIONS 11 5 7 1 Wiring terminal block 11 5 7 2 Removal of protective carter for models 120 and 150 12 6 START UP 13 7 SHUTDOWNS FOR LONG PERIODS 13 8 MAINTENANCE AND PERIODICAL CONTROLS 13 9 TE...

Страница 3: ...HP_OWER 3...

Страница 4: ...the manufacturer as an attachment to this manual The company is available to give any detailed information about this manual and to give information regarding the use and the maintenance of its own u...

Страница 5: ...86 CEE 2009 104 CE 86 188 CEE and 77 576 CEE directives Every employer shall implement such provisions and ensure that their workers to respect them We observe therefore that Do not tamper with or rep...

Страница 6: ...ml m for each of the two components Respiratory protection For rescue and maintenance operation in storage tanks use self contained respirator apparatus The vapors are heavier than air and can cause s...

Страница 7: ...t only by QUALIFIED PERSONNEL Before any operation on the unit make sure the power supply is disconnected WARNING MOVING PARTS RISK OF DEATH Disconnect the power supply and ensure that the fan is stop...

Страница 8: ...o not exceed the maximum head loss on the plant side please see the technical data given in the table of Paragraph 12 available pressure head WARNING Connect the pipes to the attacks by using always k...

Страница 9: ...WARNING The water on the charging topping up pipe must be suitably pre filtered from any impurities and suspended particles Make sure that you have installed a cartridge filter removable WARNING Befo...

Страница 10: ...ALVE FO INVERTING CYCLE LR LIQUID RECEIVER EEV ELECTRONIC EXPANSION VALVE FL FILTER M AXIAL FAN SE OUTDOOR AIR TEMPERATURE P CIRCULATOR ON BOARD UNIT IN WATER INLET TEMPERATURE OUT WATER OUTLET TEMPER...

Страница 11: ...witch connections altered or not properly made the guarantee will be invalidated WARNING The remote control panel is connected to the water chiller by means of no 4 wires having a 1 5 mm 2 section The...

Страница 12: ...eutral output of auxiliary electric heater for plant water 230V 50Hz 5A AEH Digital output DO3 230 Vac Phase output of auxiliary electric heater for plant water 230V 50Hz 5A SAN Analogue ST9 digital D...

Страница 13: ...terminate immediately WARNING The summer winter operating mode have to be selected at the beginning of the related season Frequent and sudden changes of this seasonal operating mode have to be avoided...

Страница 14: ...d discharge piping of the compressor are usually high Be careful when working near condensing coils The aluminum fins are very sharp and can cause serious injuries After the maintenance operations clo...

Страница 15: ...R410A R410A R410A Refrigerant quantity kg 1 55 2 10 3 65 3 90 Design pressure high low MPa 4 2 2 7 4 2 2 7 4 2 2 7 4 2 2 7 Hydraulic circuit Water flow rate 3 m3 h 0 99 0 99 1 56 1 56 2 13 2 13 2 44 2...

Страница 16: ...allation and maintenance Read precautions for installation and maintenance at specific chapters on user s and installation s manual PRODUCT FICHE HP_OWER for medium temperature application Tout 55 C S...

Страница 17: ...Tj bivalent temperature Pdh 4 2 kW Tj bivalent temperature COPd 2 73 Tj operation limit temperature Pdh 3 8 kW Tj operation limit temperature COPd 2 35 For air to water heat pumps Tj 15 C if TOL 20 C...

Страница 18: ...Tj bivalent temperature Pdh 7 2 kW Tj bivalent temperature COPd 2 73 Tj operation limit temperature Pdh 6 9 kW Tj operation limit temperature COPd 2 48 For air to water heat pumps Tj 15 C if TOL 20 C...

Страница 19: ...j bivalent temperature Pdh 9 2 kW Tj bivalent temperature COPd 2 69 Tj operation limit temperature Pdh 8 1 kW Tj operation limit temperature COPd 2 29 For air to water heat pumps Tj 15 C if TOL 20 C P...

Страница 20: ...Tj bivalent temperature Pdh 10 2 kW Tj bivalent temperature COPd 2 58 Tj operation limit temperature Pdh 9 4 kW Tj operation limit temperature COPd 2 21 For air to water heat pumps Tj 15 C if TOL 20...

Страница 21: ...Pd 3 50 Tj bivalent temperature Pdh 4 0 kW Tj bivalent temperature COPd 2 21 Tj operation limit temperature Pdh 3 6 kW Tj operation limit temperature COPd 2 00 For air to water heat pumps Tj 15 C if T...

Страница 22: ...Pd 3 26 Tj bivalent temperature Pdh 7 1 kW Tj bivalent temperature COPd 2 10 Tj operation limit temperature Pdh 6 8 kW Tj operation limit temperature COPd 1 99 For air to water heat pumps Tj 15 C if T...

Страница 23: ...OPd 3 56 Tj bivalent temperature Pdh 8 3 kW Tj bivalent temperature COPd 1 93 Tj operation limit temperature Pdh 7 4 kW Tj operation limit temperature COPd 1 69 For air to water heat pumps Tj 15 C if...

Страница 24: ...OPd 3 37 Tj bivalent temperature Pdh 9 3 kW Tj bivalent temperature COPd 1 78 Tj operation limit temperature Pdh 8 5 kW Tj operation limit temperature COPd 1 55 For air to water heat pumps Tj 15 C if...

Страница 25: ...cessary to refer always to the technical data label stuck on right side panel of the unit 12 HEAT PUMPS AVAILABLE HEAD PRESSURE Below the characteristic curves corresponding to Head pressure Water flo...

Страница 26: ...HP OWER 26 13 WATER PUMP CURVES 13 1 MODELS HP_OWER 60 90 13 2 MODELS HP_OWER 120 150...

Страница 27: ...lure in the case of insufficient water flow but it does not ensure the minimum flow rate required in order the unit can work properly Models HP_OWER 60 90 120 150 Cooling capacity for reference kW 5 3...

Страница 28: ...WFCF Water flow rate correction factor PDCF Pressure drops correction factor The water flow rate and pressure drop correction factors are to be applied directly to the values given for operation with...

Страница 29: ...HP_OWER 29 16 DIMENSIONS 16 1 MODELS HP_OWER 60 IN OUT 1 M 16 2 MODELS HP_OWER 90 IN OUT 1 M...

Страница 30: ...HP OWER 30 16 3 MODELS HP_OWER 120 150 IN OUT 1 M...

Страница 31: ...HP_OWER 31 17 WIRING DIAGRAMS 17 1 MODELS HP_OWER 60 90 Temp Sensor Heat Sink...

Страница 32: ...HP OWER 32 17 2 MODEL HP_OWER 120 Temp Sensor Heat Sink...

Страница 33: ...HP_OWER 33 17 3 MODEL HP_OWER 150 Temp Sensor Heat Sink CN604 CN607 DC DC1 DC2 DC DC1 DC2 20A 5mH Reactor...

Страница 34: ...perature sensors for the environment thermohygrometer analysis and manage the double set point for the radiant floor panel that use a dehumidification system The intuitive interface simplifies the use...

Страница 35: ......

Страница 36: ...s It also reserves the right to modify its products as deemed necessary or useful without jeopardising their essential features 46033 casteldario mantova italia tel 39 0376 57001 fax 39 0376 660556 in...

Отзывы: