Technical parameters for medium temperature 55°C 

Model 

HP_OWER 90 

Air-to-water heat pump: 

Yes 

Water-to-water heat pump: 

No 

Brine-to-water heat pump: 

No 

Low-temperature heat pump: 

No 

Equipped with a supplementary heater: 

No 

Heat pump combination heater: 

No 

Parameters shall be declared for medium-temperature application. 

Parameters shall be declared for average climate condition. 

Item 

Symbol 

Value 

Unit 

 

Item 

Symbol 

Value 

Unit 

Rated heat pump 

P

rated

 

kW 

 

Seasonal space heating 
energy efficiency 

η

s

 

102 

Declared  capacity  for  heating  for  part  load  at  indoor 
temperature 20°C and outdoor temperature T

j

 

 

Declared  coefficient  of  performance  or  primary  energy  ratio 
for  part  load  at  indoor  temperature  20°C  and  outdoor 
temperature T

j

 

T

= -7°C 

Pdh 

7,1 

kW 

 

T

= -7°C 

COP

d

 

2,10 

 

T

= +2°C 

Pdh 

4,3 

kW 

 

T

= +2°C 

COP

d

 

2,63 

 

T

= +7°C 

Pdh 

4,2 

kW 

 

T

= +7°C 

COP

d

 

2,82 

 

T

= +12°C 

Pdh 

4,7 

kW 

 

T

= +12°C 

COP

d

 

3,26 

 

T

= bivalent temperature 

Pdh 

7,1 

kW 

 

T

= bivalent temperature 

COP

d

 

2,10 

 

T

= operation limit 

temperature 

Pdh 

6,8 

kW 

 

T

= operation limit 

temperature 

COP

d

 

1,99 

 

For air-to-water heat 
pumps: T

= -15°C 

(if TOL < -20°C) 

Pdh 

kW 

 

For air-to-water heat pumps: 
T

= -15°C (if TOL < -20°C) 

COP

d

 

 

Bivalent temperature 

T

biv 

-7 

°C 

 

For air-to-water heat pumps: 
Operation limit temperature 

TOL 

-15 

°C 

Cycling interval capacity for 
heating 

P

cych 

4,4 

kW 

 

Cycling interval efficiency 

COP

cyc

 

2,99 

 

Degradation co-efficient 

Cdh 

1,0 

 

Heating water operating limit 
temperature 

WTOL 

58 

°C 

Power consumption in modes other than active mode 

 

Supplementary heater 

Off mode 

P

off

 

0,000 

kW 

 

Rated heat output 

Psup 

kW 

Thermostat-off mode 

P

To

 

0,011 

kW 

 

Type of energy input 

Standby mode 

P

SB

 

0,011 

kW 

 

Crankcase heater mode 

P

CK

 

0,000 

kW 

 

Other items 

 

 

 

 

 

 

 

 

Capacity control 

variable 

 

For  air-to-water  heat  pumps: 
Rated air flow rate, outdoors 

5868 

m

3

/h 

 

Sound power level, 
indoors/outdoors 

L

WA

 

- / 64 

dB(A) 

 

For  water-  or  brine-to-water 
heat  pumps:  Rated  brine  or 
water flow rate, outdoor heat 
exchanger 

m

3

/h 

Annual energy consumption 

Q

HE

 

6320 

kWh 

 

 

Содержание HP OWER 60

Страница 1: ...User s and Installer s Manual 60 90 120 150...

Страница 2: ...L CONNECTIONS 11 5 7 1 Wiring terminal block 11 5 7 2 Removal of protective carter for models 120 and 150 12 6 START UP 13 7 SHUTDOWNS FOR LONG PERIODS 13 8 MAINTENANCE AND PERIODICAL CONTROLS 13 9 TE...

Страница 3: ...HP_OWER 3...

Страница 4: ...the manufacturer as an attachment to this manual The company is available to give any detailed information about this manual and to give information regarding the use and the maintenance of its own u...

Страница 5: ...86 CEE 2009 104 CE 86 188 CEE and 77 576 CEE directives Every employer shall implement such provisions and ensure that their workers to respect them We observe therefore that Do not tamper with or rep...

Страница 6: ...ml m for each of the two components Respiratory protection For rescue and maintenance operation in storage tanks use self contained respirator apparatus The vapors are heavier than air and can cause s...

Страница 7: ...t only by QUALIFIED PERSONNEL Before any operation on the unit make sure the power supply is disconnected WARNING MOVING PARTS RISK OF DEATH Disconnect the power supply and ensure that the fan is stop...

Страница 8: ...o not exceed the maximum head loss on the plant side please see the technical data given in the table of Paragraph 12 available pressure head WARNING Connect the pipes to the attacks by using always k...

Страница 9: ...WARNING The water on the charging topping up pipe must be suitably pre filtered from any impurities and suspended particles Make sure that you have installed a cartridge filter removable WARNING Befo...

Страница 10: ...ALVE FO INVERTING CYCLE LR LIQUID RECEIVER EEV ELECTRONIC EXPANSION VALVE FL FILTER M AXIAL FAN SE OUTDOOR AIR TEMPERATURE P CIRCULATOR ON BOARD UNIT IN WATER INLET TEMPERATURE OUT WATER OUTLET TEMPER...

Страница 11: ...witch connections altered or not properly made the guarantee will be invalidated WARNING The remote control panel is connected to the water chiller by means of no 4 wires having a 1 5 mm 2 section The...

Страница 12: ...eutral output of auxiliary electric heater for plant water 230V 50Hz 5A AEH Digital output DO3 230 Vac Phase output of auxiliary electric heater for plant water 230V 50Hz 5A SAN Analogue ST9 digital D...

Страница 13: ...terminate immediately WARNING The summer winter operating mode have to be selected at the beginning of the related season Frequent and sudden changes of this seasonal operating mode have to be avoided...

Страница 14: ...d discharge piping of the compressor are usually high Be careful when working near condensing coils The aluminum fins are very sharp and can cause serious injuries After the maintenance operations clo...

Страница 15: ...R410A R410A R410A Refrigerant quantity kg 1 55 2 10 3 65 3 90 Design pressure high low MPa 4 2 2 7 4 2 2 7 4 2 2 7 4 2 2 7 Hydraulic circuit Water flow rate 3 m3 h 0 99 0 99 1 56 1 56 2 13 2 13 2 44 2...

Страница 16: ...allation and maintenance Read precautions for installation and maintenance at specific chapters on user s and installation s manual PRODUCT FICHE HP_OWER for medium temperature application Tout 55 C S...

Страница 17: ...Tj bivalent temperature Pdh 4 2 kW Tj bivalent temperature COPd 2 73 Tj operation limit temperature Pdh 3 8 kW Tj operation limit temperature COPd 2 35 For air to water heat pumps Tj 15 C if TOL 20 C...

Страница 18: ...Tj bivalent temperature Pdh 7 2 kW Tj bivalent temperature COPd 2 73 Tj operation limit temperature Pdh 6 9 kW Tj operation limit temperature COPd 2 48 For air to water heat pumps Tj 15 C if TOL 20 C...

Страница 19: ...j bivalent temperature Pdh 9 2 kW Tj bivalent temperature COPd 2 69 Tj operation limit temperature Pdh 8 1 kW Tj operation limit temperature COPd 2 29 For air to water heat pumps Tj 15 C if TOL 20 C P...

Страница 20: ...Tj bivalent temperature Pdh 10 2 kW Tj bivalent temperature COPd 2 58 Tj operation limit temperature Pdh 9 4 kW Tj operation limit temperature COPd 2 21 For air to water heat pumps Tj 15 C if TOL 20...

Страница 21: ...Pd 3 50 Tj bivalent temperature Pdh 4 0 kW Tj bivalent temperature COPd 2 21 Tj operation limit temperature Pdh 3 6 kW Tj operation limit temperature COPd 2 00 For air to water heat pumps Tj 15 C if T...

Страница 22: ...Pd 3 26 Tj bivalent temperature Pdh 7 1 kW Tj bivalent temperature COPd 2 10 Tj operation limit temperature Pdh 6 8 kW Tj operation limit temperature COPd 1 99 For air to water heat pumps Tj 15 C if T...

Страница 23: ...OPd 3 56 Tj bivalent temperature Pdh 8 3 kW Tj bivalent temperature COPd 1 93 Tj operation limit temperature Pdh 7 4 kW Tj operation limit temperature COPd 1 69 For air to water heat pumps Tj 15 C if...

Страница 24: ...OPd 3 37 Tj bivalent temperature Pdh 9 3 kW Tj bivalent temperature COPd 1 78 Tj operation limit temperature Pdh 8 5 kW Tj operation limit temperature COPd 1 55 For air to water heat pumps Tj 15 C if...

Страница 25: ...cessary to refer always to the technical data label stuck on right side panel of the unit 12 HEAT PUMPS AVAILABLE HEAD PRESSURE Below the characteristic curves corresponding to Head pressure Water flo...

Страница 26: ...HP OWER 26 13 WATER PUMP CURVES 13 1 MODELS HP_OWER 60 90 13 2 MODELS HP_OWER 120 150...

Страница 27: ...lure in the case of insufficient water flow but it does not ensure the minimum flow rate required in order the unit can work properly Models HP_OWER 60 90 120 150 Cooling capacity for reference kW 5 3...

Страница 28: ...WFCF Water flow rate correction factor PDCF Pressure drops correction factor The water flow rate and pressure drop correction factors are to be applied directly to the values given for operation with...

Страница 29: ...HP_OWER 29 16 DIMENSIONS 16 1 MODELS HP_OWER 60 IN OUT 1 M 16 2 MODELS HP_OWER 90 IN OUT 1 M...

Страница 30: ...HP OWER 30 16 3 MODELS HP_OWER 120 150 IN OUT 1 M...

Страница 31: ...HP_OWER 31 17 WIRING DIAGRAMS 17 1 MODELS HP_OWER 60 90 Temp Sensor Heat Sink...

Страница 32: ...HP OWER 32 17 2 MODEL HP_OWER 120 Temp Sensor Heat Sink...

Страница 33: ...HP_OWER 33 17 3 MODEL HP_OWER 150 Temp Sensor Heat Sink CN604 CN607 DC DC1 DC2 DC DC1 DC2 20A 5mH Reactor...

Страница 34: ...perature sensors for the environment thermohygrometer analysis and manage the double set point for the radiant floor panel that use a dehumidification system The intuitive interface simplifies the use...

Страница 35: ......

Страница 36: ...s It also reserves the right to modify its products as deemed necessary or useful without jeopardising their essential features 46033 casteldario mantova italia tel 39 0376 57001 fax 39 0376 660556 in...

Отзывы: