27
ENGLISH
Installation Instructions
ATTENTION!
Function reserved for Authorised Assistance
Centres only.
1
ACTIvATION / MAXIMUM OUTPUT
Press the key + (
PLUs
) and -
(MINUs)
for at least 3
seconds: boiler at max power, symbol light .
3
MINIMUM OUTPUT
Press key -
(MINUs)
boiler at mimum power, symbol flashing.
4
DIsABLING
After calibration, press the + (PLUS) and - (MINUS) at the
same time, the symbol off.
Flue gas
probe
To determine the combustion efficiency
one must make the following measurements:
- measurement of the combustion air temperature
- measurement of the flue gas temperature and content of
CO
2
taken in the relevant hole
2
.
Take the measurements with the generator in steady state
conditions (see par. 3.11.1).
3.11 - MEAsUREMENT OF COMBUsTION
EFFICIENCY DURING INsTALLATION
3.11.1- ACTIvATION OF THE CALIBRATION FUNCTION
3.11.2 - POsITIONING THE PROBEs