13
Tec
hnical Features
ENGLISH
ALKON 50 c (reg. 34,8)
ALKON 50 c
ALKON 70 c
Appliance category
II
2H3P
II
2H3P
II
2H3P
Modulation Ratio
1 : 3,6
1 : 5
1 : 7
Nominal Heat Input on P.C.I. Qn
kW
34,8
48,5
67,5
Minimum Heat Input on P.C.I. Qmin
kW
9,6
9,6
9,6
Nominal Output (Tr 60 / Tm 80 °C) Pn
kW
33,9
47,2
65,5
Minimum Output (Tr 60 / Tm 80 °C) Pn min
kW
9,1
9,1
9,1
Nominal Output (Tr 30 / Tm 50 °C) Pcond
kW
35,4
49,3
68,5
Minimum Output (Tr 30 / Tm 50 °C) Pcond min
kW
10,3
10,3
10,3
Efficiency at max. output (Tr 60 / Tm 80°C)
%
97,29
97,29
97,29
Efficiency at min. output (Tr 60 / Tm 80°C)
%
94,8
94,9
94,9
Efficiency at max. output (Tr 30 / Tm 50°C))
%
101,62
101,62
101,51
Efficiency at min. output (Tr 30 / Tm 50°C)
%
104,3
104,3
104,3
Rendimento al 30% del carico (Tr 30°C)
%
107,33
107,33
107,33
Combustion efficiency with nominal load
%
97,80
97,80
97,41
Combustion efficiency with minimum load
%
98,42
98,42
98,42
Heat loss at casing with burner in operation (Qmin)
%
3,62
3,61
3,61
Heat loss at casing with burner in operation (Qn)
%
0,51
0,51
0,12
Flue gas temperature tf-ta (min)(*)
°C
33
33
33
Flue gas temperature tf-ta (max)(*)
°C
43,6
43,6
51,3
Maximum allowable temperature
°C
100
100
100
Maximum operating temperature
°C
85
85
85
Flue gas mass flow rate (min)
kg/h
15,9
15,9
15,9
Flue gas mass flow rate (max)
kg/h
57,4
80,0
111,4
Excess λ air
%
26,84
26,84
20,57
Flue losses with burner in operation (min)
%
1,58
1,58
1,58
Flue losses with burner in operation (max)
%
2,20
2,20
2,59
Minimum heating circuit pressure
bar
0,5
0,5
0,5
Maximum heating circuit pressure
bar
6
6
6
Water content
l
3,9
3,9
3,9
Gas Consumption Natural (20 mbar) gas G 20 a Qn
m
3
/h
3,68
5,13
7,14
Gas Consumption Natural gas (20 mbar) G 20 a Qmin
m
3
/h
1,02
1,02
1,02
Gas Consumption G25 (supply pressure 25 mbar) Qn
m
3
/h
4,28
5,96
8,30
Gas Consumption G25 (supply pressure 25 mbar) Qmin
m
3
/h
1,18
1,18
1,18
Gas Consumption G31 (supply pressure 37/50 mbar) Qn
kg/h
2,70
3,76
5,24
Gas Consumption G31 (supply pressure 37/50 mbar) Qmin
kg/h
0,75
0,75
0,75
Max. available pressure at the chimney base
Pa
40
40
40
Condensate production max
kg/h
5,6
7,8
10,87
Emissioni
CO at Minimum Heat Input with 0% of O2
mg/kWh 71,3
71,3
82
NOx at Nominal Heat Input with 0% of O2
mg/kWh 48
56
59
NOx Class
5
5
5
Electrical Data
Voltage/Frequency electric power supply
V/Hz
230/50
230/50
230/50
Fuse on main supply
A (R)
6
6
6
Insulation degree
IP
X4D
X4D
X4D
Room Temperature = 20°C
(*) Temperatures detected with the unit in operation (Tr 60 / Tm 80°C)
CO
2
(min/max) See table INJECTORS PRESSURES
Seasonal space heating energy 2009/125 CEE (<=400Kw)
η
s
- see ErP table
Stand-by heat loss
∆T 30°C
- Pstb - see ErP table
Consumption in stand-by - Psb - see ErP table
2.5 - OPERATING DATA ACCORDING TO UNI 10348 and GENERAL FEATUREs
For the adjustment data: NOZZLES - PRESSURE - DIAGRAMS - FLOW RATES - CONSUMPTION refer to the paragraph ADAP
-