background image

17

18

   
A. Under insulation resistance measurement condition and without testing voltage 
     output, press     to progressively decrease at the step of corresponding range 
     (decrease by 50% at a step of 10% each).
B. When setting time or resistance,      button is used as a cursor button to adjust 
     time and resistance.    
C. After polarization index or absorption ratio measurement is completed, press   

to cyclically display polarization index or absorption ratio, insulation resistance in 
Time2 and Time1.

A. Under insulation resistance measurement condition and without testing voltage 
     output, press       to progressively increase at the step of corresponding range 
     (increase by 120% at a step of 10% each).
B. For time or resistance setting,     button is used as a cursor button to adjust time 
     and resistance.    
C. After polarization index or absorption ratio measurement is completed, press   
    to cyclically display polarization index or absorption ratio, insulation resistance in 
    Time2 and Time1.

 

   

 READ

Without high voltage output, short press “READ” to read latest group of saved data, 

and press 

 and 

 to select different data.

 

   

 SAVE

Short press “SAVE” to save current displayed data. The LCD shows the symbol “FUL” 
and the number of group “999” to indicate full storage.  To save next group of data, 
please clear the saved data.

 

     

Backlight button

Short press this button to turn on/off the backlight.

 

     

Setting confirmation button

For setting parameter in non-testing state, short press “ENTER” to confirm the setting 
and exit the current setting.

 

     

Setting cancellation/exit button

For setting parameter without high voltage output, short press “ESC” to cancel current 
setting and exit. Under “TIME” and “COMP” modes, short press “ESC” consecutively 
for twice to return to the interface of continuous insulation resistance measurement.

 

    

Data deletion button

In “READ” state, short press “CLR” and then press “ENTER” to delete current data, 
press “ESC” to exit data deletion function. In “READ” state, the symbol “CLR” and 
the storage capacity symbol “2Hz” flash when “CLR” is long pressed for 2 to 3 
seconds, press “ENTER” to confirm clearing all saved data, press “ESC” to exit data 
deletion function. Note: To delete all saved data after short pressing “CLR”, please 
long press “CLR” directly to enter after pressing exit button.

 

    

Data upload button

Short press this button to select USB data transfer mode, current transfer mode 
can be displayed on the LCD synchronously , select current mode to transfer data 
through confirmation button. 
When connected to the computer software, press and hold this button to upload all 
stored data to the PC.
USB: Active uploading for the tester.

 

    

Timer setting button

The default mode of the tester is continuous insulation resistance measurement 
mode. Under insulation resistance measurement condition and without testing voltage 
output, perform time setting for insulation resistance measurement mode. 
Short press “TIME” to cyclically select “Continuous Measurement”, “Timer 
Measurement”, “Polarization Index Measurement” and “Absorption Ratio

 

Measurement”, press “ENTER” to confirm the selection, press “ESC” to unselect 
and return to default measurement mode.

 

    

Comparison measurement button

Under insulation resistance measurement condition and without testing voltage 
output, short press “COMP” to select resistance comparison measurement as 
insulation resistance measurement mode, the default comparison value is 10M

Ω

.

 

    

Measurement button

This button is used to turn on/off insulation resistance measurement or capacitance 
measurement. Long press “TEST” for more than 2 seconds to start measurement.
 If current measurement function is enabled, the red warning light illuminates the 
background of “TEST” button. Short press “TEST” to exit measurement.

UT512D/E User Manual

UT512D/E User Manual

Содержание UT512D

Страница 1: ...UT512D UT512E 2 5kV Insulation Resistance Tester User Manual P N 110401111817X...

Страница 2: ...Trend guarantees that the product is free from any defect in material and workmanship within one year from the purchase date This warranty does not apply to damages caused by accident negligence misu...

Страница 3: ...ainly used to measure insulation resistance of cable motor power generator transformer mutual inductor high voltage switch lightning arrester and more it is an ideal measurement meter for electric pow...

Страница 4: ...T512E 8 PCS LR14 alkaline batteries UT512D Error limit a of reading b digits one year warranty Environment temperature 23 5 Environment humidity 45 75 RH In the table below The humidity must be less t...

Страница 5: ...ications UT512E Function Measurement range Accuracy Remark Low resistance measurement Open circuit voltage 5V Note If the measured resistance is 20 the buzzer alarms if 660 660 is displayed The short...

Страница 6: ...bidden to use the tester without battery cover set in place otherwise it may pose a risk of electric shock Keep fingers behind the finger guard when perform measurement do not touch exposed wire conne...

Страница 7: ...plug red lead GUARD Grounding protection outlet single plug green lead EARTH High resistance measurement outlet single plug black lead LCD segmented display screen Functional buttons USB port Carryin...

Страница 8: ...testing Bluetooth Insulation resistance measurement mode AC DC voltage measurement mode Power on off Increase select high range or previous group of data Decrease adjust time and resistance cyclically...

Страница 9: ...ress this button to switch to insulation resistance testing function V UT512E AC DC voltage testing button Without high voltage output short press V button to switch to AC DC voltage testing mode The...

Страница 10: ...measurement Data deletion button In READ state short press CLR and then press ENTER to delete current data press ESC to exit data deletion function In READ state the symbol CLR and the storage capaci...

Страница 11: ...rged if low battery occurs please replace with battery in same type 9 2 Battery Charging UT512E When charging with battery charger in power on state the battery power indicator and the charging symbol...

Страница 12: ...hange Press TEST to perform test the LCD shows basic elements including battery power high voltage warning symbol leakage current real time output voltage measured insulation resistance testing value...

Страница 13: ...tion resistance in Time1 9 3 1 4 Dielectric Absorption Ratio Measurement Dielectric Absorption Ratio DAR refers to the value of insulation resistance in 1 minute to that in 15 seconds It takes 1 minut...

Страница 14: ...s if insulation resistance is less than comparison resistance the symbol FAIL will appear on the LCD otherwise PASS appears To return to the continuous measurement interface please press COMP in COMP...

Страница 15: ...ltage input the danger symbol flashes in such case do not press the test button to measure resistance as shown in figure 9 3 4 2 Under resistance measurement function connect the black grounding lead...

Страница 16: ...rminal with the exterior conductor of inner insulation layer and the unused cable Surface leakage current is conducted to the safety terminal so as to eliminate the surface leakage current at the meas...

Страница 17: ...Red XI Maintenance Clean the casing 1 Wipe the surface using soft cloth or sponge dipped with water 2 Do not immerse the tester in water to avoid tester damage 3 Do not store the tester if it is wet 4...

Отзывы: