Pmax
3.0 BAR
CAUTION: The auxiliary I/O board is separated from the main network through a "principal" insulation type (basic insulation
according to EN 60730-1). Any circuit connected to this terminal will acquire the same level of insulation with respect to the mains
power supply. For this reason the connections must be carried out with a cable type that guarantees the additional insulation.
START-UP:
WARNING: do not allow the pump to run for long without water the first time it is switched on otherwise the inverter will
overheat! Prime the pump before switching on the system.
on the power.
On initial start-up the operator will be requested to enter the current as stated on the motor data plate on the following screen:
Set the value as stated in the technical specifications of the pump as follows:
press the central key to confirm and proceed with entry of the maximum operating pressure (Pmax). After setting the pressure, press the
central key again to exit the settings menu.
The inverter is now in stand-by; in this mode (pump stationary)
the system is started up.
-
: The inverter will exit the stand-by mode and the motor will start
turning.
If the pump does not run or if it produces anomalous vibrations, check the connection and that the direction of rotation is correct.
To facilitate pump
rce the pump up to top speed without the dry running
protection feature cutting in.
After setting all the device parameters, write the data entered in the form found at the end of this handbook for future reference and
for guarantee purposes.
PROGRAMMING
DESCRIPTION OF THE BUTTONS
Left-hand arrow: this scrolls back through the menu pages
Right-hand arrow: this scrolls forwards through the menu pages
On-Off/Reset: this switches the device from stand-by to operation mode and resets the unit in the event
of alarms and/or errors.
run at
top speed without the dry running protection feature cutting in.
-
parameter currently shown on the display.
MAIN MANU STRUCTURE
The main menu shows the operational values of the system: pressure, current frequency of the motor, input voltage, output current of the
motor and internal temperature of the inverter. It is also possible to select the language.
INSTALLED PUMP
MODEL
Imax (A)
3 2-55
5
3 2-85
8
3 3-55
6
3-80
8
Imax
0.5 Amp
1.0 BAR
150Hz
V= 230V
I= 5.0A
Ti= 35
°
C
Ta= 35
°
C
Language
EN
Содержание 3 ACUASPEED
Страница 2: ......
Страница 80: ...RUS Sirio ROHS 2002 95 EC...
Страница 82: ...IGBT...
Страница 83: ...7 I n 30mA LINE 5 A 3 2 55 1 2 1 6Hp 12 3 2 85 1 9 2 5Hp 16 3 3 55 1 2 1 6Hp 12 3 3 80 1 9 2 5Hp 16 230 50 60...
Страница 84: ...MOTOR dV dT 60730 1 Pmin...
Страница 85: ...Pmax 3 0 BAR Pmax2 Pmax Pmax Pmax Pmax2 60730 1 Imax A 3 2 55 5 3 2 85 8 3 3 55 6 3 80 8 Imax 0 5 A...
Страница 91: ...1...
Страница 92: ......
Страница 94: ......
Страница 95: ......