www.InWallDehumidifier.com | (800) 533-7533

Ultra-Aire MD33 Installation Instructions

DEHUMIDIFIER INSTALLATION

Inside of Wall

Drain

Hose

Electrical

Wiring

14 1/2"

30 1/4

14"

14"

Steps 5 - 8

Step 4.

 The drain hose can exit through the back, 

side, or bottom of the unit. Once the location is  

determined, remove the appropriate knock out. 
If exiting through the bottom, remove the access  

cover to facilitate routing of the drain line.
Save access cover for reinstallation after drain  

line is routed.

Step 5.

 After installation location has been determined, 

use a stud finder, locate and mark stud walls.

Step 6.

 Using measuring tape and pencil, measure  

14 1/2" across and 30 1/4" down and draw a line.

Step 7.

 Using a square or ruler, score the lines 

and cut with drywall saw.
Depending on installation, both walls may need to 

be cut through.

4.

Step 3.

 There are three electrical knock outs, one on  

the back and two on the bottom of the unit. Remove  

appropriate knock out and install non-metallic cable 

clamp with clamp screws inside of unit oriented so  

they are accessible for tightening later.
If using included power cord, insert cord through non-

metallic cable clamp so that a minimum of ½” insulation 

jacket is inside of cabinet before tightening non-metallic 

cable clamp screws. Make electrical connections using 

included wire nuts.

3.

Step 8.

 If not using included power cord, route the  

electrical wire from the circuit breaker or disconnect 

switch through the wall cavity and extend out of the 

opening by 14" to 20". 
Use the 10

'

 drain hose provided or the appropriate  

length of hose to come through the wall cavity  

or back of the unit and extend out of the opening  

by 14

"

 inches. 

If cutting through both walls, electrical wiring  

and drain hose may be routed differently. Use  

appropriate routing for your installation.

 

WARNING!

SHUT OFF BREAKER / POWER  
BEFORE BEGINNING INSTALLATION.

Содержание MD33

Страница 1: ...l framing The Ultra Aire MD33 provides the ultimate in comfort health and property protection TS 927 6 18 Rev E P N 4035900 Serial No Install Date Sold by HVAC Installer Please Leave Manual for Homeow...

Страница 2: ...rements 7 Dehumidifier Installation 8 Maintenance 12 Air Flow 12 Controls 13 Service 15 Warranty 17 TABLE OF CONTENTS Therma Stor is committed to manufacturing quality products To maintain our standar...

Страница 3: ...TRICAL AND PLUMBING CODES MUST BE ADHERED TO FOR PROPER UNIT OPERATION AND WARRANTY COMPLIANCE IMPROPER INSTALLATION MAY CAUSE PROPERTY DAMAGE OR INJURY INSTALLATION SERVICE AND MAINTENANCE MUST BE PE...

Страница 4: ...DOIVENT TRE RESPECT S POUR UNE UTILISATION AD QUATE DE CETTE UNIT ET UNE VALIDIT DE LA GARANTIE UNE INSTALLATION NON CONFORME PEUT CAUSER DES DOMMAGES MAT RIELS OU DES BLESSURES TOUTE INSTALLATION TO...

Страница 5: ...ted behind tamper proof cover Air Filter 1 2 Washable mounted behind diffuser Dehumidistat Digital tamper proof float switch input Cabinet Galvanized Steel Decibels 46 dBA Drain Connection 3 4 O D Dra...

Страница 6: ...ing members or unwanted noise may result Unit is designed to be suspended by side mounting flanges only Drain hose must be routed with downward slope from unit drain connection to appropriate location...

Страница 7: ...z AC only 15 amp fused and grounded electrical supply A visible circuit breaker or disconnect switch near the unit is required for maintenance and service A dedicated circuit is recommended Use of a U...

Страница 8: ...ER POWER BEFORE BEGINNING INSTALLATION 1 2 Electrical Box Shipping Bracket AVERTISSEMENT FERMEZ LE DISJONCTEUR ALIMENTATION AVANT DE COMMENCER L INSTALLATION Items Included in Box Ultra Aire MD33 Dehu...

Страница 9: ...p 3 There are three electrical knock outs one on the back and two on the bottom of the unit Remove appropriate knock out and install non metallic cable clamp with clamp screws inside of unit oriented...

Страница 10: ...ng on both sides Additional insulation or sound dampening material not provided may be required if the dehumidifier cabinet contacts the studs especially in applications involving metal studs Fasten t...

Страница 11: ...e of the electrical wires are pinched Step 15 Turn breaker power back on Step 16 Set the digital controller to desired RH See Controls Section on page 13 Step 17 Install diffuser cover by aligning the...

Страница 12: ...ORD IS DAMAGED IT MUST BE REPLACED BY THE MANUFACTURER ITS SERVICE AGENT OR SIMILARLY QUALIFIED PERSONS IN ORDER TO AVOID A HAZARD AVERTISSEMENT ASSUREZ VOUS QUE L UNIT EST FERM E OU D BRANCH E OU QUE...

Страница 13: ...will show 00 for a couple of seconds and then it will display the RH level of the room and the dehumidifier blower will turn on to start sampling the air for one minute Indicator LED located above di...

Страница 14: ...after an hour Evaporator Temperature Mode To enter evaporator temperature mode press and hold both arrow buttons for 5 seconds and the LED will change to Blue The display will flash at twice the rate...

Страница 15: ...TO PERFORM SOME TESTS THESE TESTS SHOULD BE PERFORMED BY A QUALIFIED SERVICE PERSON MISE EN GARDE LES TRAVAUX DE D PANNAGE NE DEVRAIENT TRE EFFECTU S QUE PAR UN TECHNICIEN CVCA QUALIFI AVERTISSEMENT...

Страница 16: ...ning 1 Wiring or connectors loose 2 Blower relay failure 3 Blower capacitor failure 4 Blower failure Check wiring and connectors for damage or loose connections Check power to blower circuit replace p...

Страница 17: ...y costs related to changes to a Product or Component that may be required by any codes laws or regulations that may become effective after initial purchase of the Product by Customer Customer Responsi...

Страница 18: ...18 Ultra Aire MD33 Installation Instructions www InWallDehumidifier com 800 533 7533...

Страница 19: ...19 www InWallDehumidifier com 800 533 7533 Ultra Aire MD33 Installation Instructions...

Страница 20: ......

Отзывы: