Ultra-Aire MD33 Installation Instructions

www.InWallDehumidifier.com | (800) 533-7533

SERVICE

Troubleshooting

  Symptom 

Possible Reason 

Troubleshooting Procedure

 

Blower is running 

and compressor is 

off while ambient 

humidity is high 

(evaporator coil is 

warm).

1.  Wiring or connectors 

loose

2. Compressor relay failure

3.  Compressor capacitor 

failure

4. Compressor failure

•  Check wiring and connectors for damage or loose 

connections.

•  Check power to compressor circuit, replace power board if 

no power is detected.

•  Replace compressor capacitor if failed.

•  Note that sealed system is not generally field serviceable.

Poor dehumidification 

performance and 

evaporator coil is 

covered in ice or frost.

1.  Defrost sensor or 

connection is defective

2. Poor airflow

3. Low refrigerant charge

•  Check circuit board connection for loose plug or wires.

•  Press and hold both arrow buttons for >5 seconds to 

display the defrost sensor temperature, replace sensor if 

reading is an error. See diagnostic - Error code “ 1”

•  Verify airflow over the coils is not blocked or restricted, 

clean filter and/or coils as required.

•  Note that sealed system is not generally field serviceable

• See diagnostic - Error code “3”

Poor dehumidification 

performance, 

compressor is  

running and  

evaporator coil is  

not cooling.

1.  Failed compressor or  

low refrigerant charge

• See diagnostic - Error code “3”

•  Note that sealed system is not generally field serviceable.

Blower is not 

spinning humidity 

is high and 

compressor is 

running.

1. Wiring or connectors loose
2. Blower relay failure
3. Blower capacitor failure
4. Blower failure

•  Check wiring and connectors for damage or loose 

connections.

•  Check power to blower circuit, replace power board if no 

power is detected.

• Replace blower capacitor if failed.

•  Replace blower (note requires unit be removed from 

installation).

Blower is running 

and compressor 

is cycling on and 

off while ambient 

humidity is high.

1.  Unit is defrosting

2.   Ambient temperature is  

too low

3.   Defrost sensor malfunction

4.  Poor airflow

5.  Failing compressor relay

6.   Compressor or sealed 

system failure 

•  Check setpoint, if setting is “00” increase setpoint to 55%.

•  Cold ambient conditions will cause unit to go in and out of 

defrost (this is normal).

•  Press and hold both arrow buttons for >5 seconds to 

display the defrost sensor temperature, replace sensor if 

reading is in error.

•  Verify airflow over the coils is not blocked or restricted, 

clean filter and/or coils as required 

Replace power board. 

•  Note that sealed system is not generally field serviceable.

Neither blower 

nor compressor is 

running and display 

is on.

1.  No call for 

dehumidification

2.  Wiring or connectors 

loose

•  Press down arrow until setpoint reads “00”, wait 1 minute, 

fan and compressor should run.

•  Check wiring and connectors for damage or loose 

connections.

• Locate circuit breaker and reset if necessary.

•  Check all circuit board connections for loose plugs 

or wires.

• Replace control board and power board.

Neither blower 

nor compressor is 

running and display 

is off.

1.  No power to unit, circuit 

breaker tripped

2.  Power board wiring or 

connector loose

3.  Control board wiring or 

connector loose

4. Circuit board failure

Содержание MD33

Страница 1: ...l framing The Ultra Aire MD33 provides the ultimate in comfort health and property protection TS 927 6 18 Rev E P N 4035900 Serial No Install Date Sold by HVAC Installer Please Leave Manual for Homeow...

Страница 2: ...rements 7 Dehumidifier Installation 8 Maintenance 12 Air Flow 12 Controls 13 Service 15 Warranty 17 TABLE OF CONTENTS Therma Stor is committed to manufacturing quality products To maintain our standar...

Страница 3: ...TRICAL AND PLUMBING CODES MUST BE ADHERED TO FOR PROPER UNIT OPERATION AND WARRANTY COMPLIANCE IMPROPER INSTALLATION MAY CAUSE PROPERTY DAMAGE OR INJURY INSTALLATION SERVICE AND MAINTENANCE MUST BE PE...

Страница 4: ...DOIVENT TRE RESPECT S POUR UNE UTILISATION AD QUATE DE CETTE UNIT ET UNE VALIDIT DE LA GARANTIE UNE INSTALLATION NON CONFORME PEUT CAUSER DES DOMMAGES MAT RIELS OU DES BLESSURES TOUTE INSTALLATION TO...

Страница 5: ...ted behind tamper proof cover Air Filter 1 2 Washable mounted behind diffuser Dehumidistat Digital tamper proof float switch input Cabinet Galvanized Steel Decibels 46 dBA Drain Connection 3 4 O D Dra...

Страница 6: ...ing members or unwanted noise may result Unit is designed to be suspended by side mounting flanges only Drain hose must be routed with downward slope from unit drain connection to appropriate location...

Страница 7: ...z AC only 15 amp fused and grounded electrical supply A visible circuit breaker or disconnect switch near the unit is required for maintenance and service A dedicated circuit is recommended Use of a U...

Страница 8: ...ER POWER BEFORE BEGINNING INSTALLATION 1 2 Electrical Box Shipping Bracket AVERTISSEMENT FERMEZ LE DISJONCTEUR ALIMENTATION AVANT DE COMMENCER L INSTALLATION Items Included in Box Ultra Aire MD33 Dehu...

Страница 9: ...p 3 There are three electrical knock outs one on the back and two on the bottom of the unit Remove appropriate knock out and install non metallic cable clamp with clamp screws inside of unit oriented...

Страница 10: ...ng on both sides Additional insulation or sound dampening material not provided may be required if the dehumidifier cabinet contacts the studs especially in applications involving metal studs Fasten t...

Страница 11: ...e of the electrical wires are pinched Step 15 Turn breaker power back on Step 16 Set the digital controller to desired RH See Controls Section on page 13 Step 17 Install diffuser cover by aligning the...

Страница 12: ...ORD IS DAMAGED IT MUST BE REPLACED BY THE MANUFACTURER ITS SERVICE AGENT OR SIMILARLY QUALIFIED PERSONS IN ORDER TO AVOID A HAZARD AVERTISSEMENT ASSUREZ VOUS QUE L UNIT EST FERM E OU D BRANCH E OU QUE...

Страница 13: ...will show 00 for a couple of seconds and then it will display the RH level of the room and the dehumidifier blower will turn on to start sampling the air for one minute Indicator LED located above di...

Страница 14: ...after an hour Evaporator Temperature Mode To enter evaporator temperature mode press and hold both arrow buttons for 5 seconds and the LED will change to Blue The display will flash at twice the rate...

Страница 15: ...TO PERFORM SOME TESTS THESE TESTS SHOULD BE PERFORMED BY A QUALIFIED SERVICE PERSON MISE EN GARDE LES TRAVAUX DE D PANNAGE NE DEVRAIENT TRE EFFECTU S QUE PAR UN TECHNICIEN CVCA QUALIFI AVERTISSEMENT...

Страница 16: ...ning 1 Wiring or connectors loose 2 Blower relay failure 3 Blower capacitor failure 4 Blower failure Check wiring and connectors for damage or loose connections Check power to blower circuit replace p...

Страница 17: ...y costs related to changes to a Product or Component that may be required by any codes laws or regulations that may become effective after initial purchase of the Product by Customer Customer Responsi...

Страница 18: ...18 Ultra Aire MD33 Installation Instructions www InWallDehumidifier com 800 533 7533...

Страница 19: ...19 www InWallDehumidifier com 800 533 7533 Ultra Aire MD33 Installation Instructions...

Страница 20: ......

Отзывы: