Model 200DX 

:: 

 Ultimateair.com 

:: 

Athens, Ohio 45701 :: 740.594.2277

 

 

 

 

Three-Motor Main Control Board Description 

 

A.

 

F2

: Wiring input from auxiliary air handler.  24 VAC common. In some cases “C” 

post from thermostat wiring on the furnace.  When using this input, REMOVE 
jumper at L – JP4. 

B.

 

F1

: Wiring input from auxiliary air handler.  24 VAC line. In some cases “G” post 

from thermostat wiring on the furnace.  When using this input, REMOVE jumper 
at L – JP4. 

C.

 

Boost input

:  When this post receives a 24 VAC from I, J, or K, the unit will be 

turned on, and to high speed (max air flow). 

D.

 

EconoCool input

: When this post receives a 24 VAC signal from I, J, or K, the 

EconoCool function will be enabled.  

E.

 

Temperature input A

: Temperature thermistor located at the incoming air 

stream (duct 1) connects through this input. 

F.

 

RET 3:  24 VAC return post. Common from the internal transformer. 

G.

 

RET 2:  24 VAC return post. Common from the internal transformer. 

H.

 

RET 1:  24 VAC return post. Common from the internal transformer. 

I.

 

LINE 3: 24 VAC line post.  Line voltage from the internal transformer. 

J.

 

LINE 2: 24 VAC line post.  Line voltage from the internal transformer. 

K.

 

LINE 1: 24 VAC line post.  Line voltage from the internal transformer. 

L.

 

JP4

:  Used to enable or disable on/off control from outside source via F1 and F2.  

REMOVE this jumper when controlling the ERV via F1 and F2 outside 24VAC 
signal. 

M.

 

RED LED

:  Main 24VAC power LED.  This should be lit anytime main power switch 

is on.  Indicates there is 24VAC power to this control board. 

N.

 

JMP3

: Offset / DP Set point jumper. See Air Flow Offsets 

O.

 

JMP2

: Offset / DP Set point jumper. See Air Flow Offsets 

P.

 

J3

: When J3 is in the 0-10V position, Z - JMP1 MUST be in the EU position. J3 

Selects control input from either the Wall Dial Control, or a 0-10V DC input 
voltage (at T and V).  

Q.

 

Programming jumper

. Must be in place for RecoupAerator to operate.  Remove 

for programming. 

R.

 

J6

:  When supply air is ducted to a forced air system-  this setting used to set 

minimum airflow to 70CFM. ‘1’ position.  ‘0’ position is normal flow range. 

S.

 

J7

: Relay selection. Jumper selects whether the normally open relay (X) closes 

when the unit turns on (position I/O), or as controlled by TempA input when in 
the temp position.  Default is position I/O.  

T.

 

0-10V DC input

:  When J3(P) is in the 0-10V position, a positive line voltage 0-

10V DC may be used to control the RecoupAerator operation. When J3 is in 0-
10V position, JMP1 MUST be in EU position for the 0-10V input to work. 

U.

 

Not connected.  Empty socket. 

V.

 

0-10V DC input:

  When J3 is in the 0-10V position, this post connects to the 

negative side of the 0-10V DC control. 

Содержание 200DX

Страница 1: ...Model 200DX Ultimateair com Athens Ohio 45701 740 594 2277...

Страница 2: ...ASE the UltimateAir 200DX moderates indoor humidity in the winter and turns away outdoor humidity in the summer Filtration 95 at 1 8 microns MERV 12 Exceeds ASHRAE 62 2 Variable Airflow with Quiet ope...

Страница 3: ...ndom matrix polymer Filtration Filtration material 95 effective at 1 8 microns MERV 12 replaceable with separate washable aluminum pre filter Frost Control Programmed to automatically prevent frosting...

Страница 4: ...701 740 594 2277 Performance Data Fan Power The power curve was generated using the average airflow rate over all four ducts Note Curves are generated from actual test data and should only be used as...

Страница 5: ...rature package with this manual and warranty registration card When Installing 1 Test Run the RecoupAerator by plugging into a power outlet turn switch on and adjust the blower speed with the included...

Страница 6: ...6 tapered reducer for running 8 trunk ducts 4 Use the included tek screws to attach the collar to the ERV metal tabs through the pre drilled pilot holes for rigid attachment 5 NOTE All ducts from the...

Страница 7: ...rotection against shock hazards and should be plugged directly into a properly grounded 120V three pronged wall receptacle If only a two pronged outlet is available it must be replaced with a properly...

Страница 8: ...effective the system will be Dedicated ductwork is installed for the stale air exhaust and the fresh air delivery The kitchen laundry room and other areas with high contamination should contain regis...

Страница 9: ...to the cold air return side or supply side of the furnace Stale Air Out thru the RecoupAerator is ducted separately to points throughout the house from which you would like to remove stale air e g the...

Страница 10: ...rator and your air handler to run simultaneously i e they will be interlocked to prevent recirculation shorting thru back past the furnace air handler Option 4 Shared Forced Air Return This method use...

Страница 11: ...oid directly suspending the RecoupAerator from the mid span area of joists This can result in structural vibration Allow adequate space for maintenance and service of the RecoupAerator Vertical Floor...

Страница 12: ...l Use a Ceiling Mounting Kit to suspend the RecoupAerator from the D rings located on the four corners Allow adequate space 12 between the ceiling and the unit to allow for servicing Allow 24 below th...

Страница 13: ...nce with HVAC standards and regulations to allow required quantities of fresh air to circulate through the building Under no circumstances should the trunk duct size be less than six inches as this wi...

Страница 14: ...curs Stretch flex duct evenly to avoid air restriction Use Y connections instead of T connections wherever possible Size ductwork according to recognized industry standards such as Manuals D and J pub...

Страница 15: ...x Foil Tape Use only tapes that have been listed and labeled to Standard UL 181B and labeled 181B FX Use two wraps of 1 minimum width Draw Band Plastic Clamp Clamp Tool Use for low pressure systems up...

Страница 16: ...g Mechanically fasten the vapor barrier jacket with a draw band Secure the inner core to the fitting using a draw band or three wraps of pressure sensitive tape apply additional mastic over the connec...

Страница 17: ...ulation of the exhaust air 2 Terminate the ducts using exterior weather hoods Ensure that the exterior weather caps have wire mesh to keep out birds and debris Angle the weather caps down and away fro...

Страница 18: ...ocedure to accomplish them Factory Default Settings Airflow This unit contains two blower motors each independently controlling the airflow coming into the building Blower 1 supply and leaving the bui...

Страница 19: ...Model 200DX Ultimateair com Athens Ohio 45701 740 594 2277 Three Motor Main Control Board...

Страница 20: ...L JP4 Used to enable or disable on off control from outside source via F1 and F2 REMOVE this jumper when controlling the ERV via F1 and F2 outside 24VAC signal M RED LED Main 24VAC power LED This shou...

Страница 21: ...controller FF Vun terminal For wiring to mating terminal on NA wall controller GG Temperature input B AUX Temperature thermistor input HH J4 Blower control jumper Default is 0 position for general ful...

Страница 22: ...d at the three motor Main Control board inside the power switch cover Use the screw terminals labeled 24 Vac LINE 1 2 or 3 and 24 Vac RETURN 1 2 or 3 to power low voltage accessories Limitations Note...

Страница 23: ...ire the dial control to a more convenient location 1 Run the unit before un wiring to be sure that everything is working 2 Following all applicable electrical codes Determine the location where the Wa...

Страница 24: ...g 1 4 of insulation from each of the wire ends complete the wiring by matching each labeled between the 3 Motor Main Control and the Wall Dial Be sure all connections are secure by lightly pulling eac...

Страница 25: ...lity Boost is useful for running at maximum airflow 200CFM using a low voltage signal input such as the optional Boost Timer Typically Boost inputs include bathroom timers CO2 monitors and humidity mo...

Страница 26: ...oviding Energy Savings and added Comfort The built in temperature sensor on the incoming air stream automatically stops energy recovery when the incoming air is between 55 and 70 Fahrenheit This featu...

Страница 27: ...Model 200DX Ultimateair com Athens Ohio 45701 740 594 2277...

Страница 28: ...electronics and will void the warranty Wiring to a Furnace AC Air Handler Continued When integrating the UltimateAir ERV with existing forced air systems it may need to operate in conjunction with th...

Страница 29: ...Wall Dial will flash when the furnace blower is not running Wiring to Thermostat or Dry Contact Switches This control scenario will utilize the UltimateAir 200DX internal 24Vac transformer power for O...

Страница 30: ...Model 200DX Ultimateair com Athens Ohio 45701 740 594 2277 The factory default setting is balanced airflow into and out of the space Any boost mode input will over ride offset pressurization...

Страница 31: ...ry setting is JMP2 JMP3 1 which means no offset is in effect and the unit will provide a balanced equal supply and exhaust flow 4 Move the jumpers to their corresponding air flow offset as follows JMP...

Страница 32: ...ect all power to the unit 1 Set jumpers JMP1 to the EU position and J3 to the 0 10V INPUT position on the three motor controller as shown in the drawing below to enable the 0 10 VDC control input 2 If...

Страница 33: ...Review following table for the vDC input versus airflow relationship to help program your control Note 0 0 5 vDC OFF 0 9 vDC ON and lowest flow setting Vin 0 10V CFM POWER watt Watt CFM 0 9 36 24 0 67...

Страница 34: ...ller The relay controls any auxiliary options you may want to operate in conjunction with your ventilation unit When the UltimateAir unit is turned on by the Wall Dial Control or by other means e g fa...

Страница 35: ...The programmed controller for modulating temperature will use only the minimum energy necessary to maintain the incoming air temperature just above 12 F automatic frost prevention shut off temperatur...

Страница 36: ...100 150 200 10 0 0 WATTS 0 0 0 0 5 0 47 5 110 8 158 3 237 4 316 5 0 0 95 0 221 6 316 5 474 8 633 0 5 0 142 4 332 3 474 8 712 2 949 6 10 0 189 9 443 1 633 0 949 6 15 0 237 4 553 9 791 3 20 0 284 9 664...

Страница 37: ...the Check Filter light comes on Which ever comes first Clean or replace the filtration material at least once per year Clean pre filters every 3 to 4 months if continuously operated Check exterior wea...

Страница 38: ...or soft brush Aluminum Pre filters Clean the aluminum pre filter at least once every six months 1 Disconnect power to the RecoupAerator 2 Open the filter access cover and foam insert blocks 3 Pull pre...

Страница 39: ...2 filter 1 Disconnect Power 2 Open the Service cover by releasing the two Latches 3 Remove the Rectangular Foam Inserts 4 Remove the aluminum pre filters Clean the pre filters at least once every six...

Страница 40: ...ls have a single thumb screw The motor wiring may remain connected Carefully rock or slide the motor drive roller assembly loose to remove 5 Replace Drive Roller Belt by stretching the new belt onto t...

Страница 41: ...achine responds by running at full flow The problem may be in the Wall Dial if Boost works correctly Blown fuse Check and replace the main fuse amp Verify all connections and replace any loose wiring...

Страница 42: ...s Clear airways of any and all obstructions including termination vents and pre filters Heat recovery wheel rubbing on insulation Make sure pies are flush with heat recovery wheel edge and not rubbing...

Страница 43: ...0DX RecoupAerator is guaranteed to be free from defects in materials or workmanship for Two 2 years from the date of purchase See Warranty card included in original packaging for complete warranty inf...

Отзывы: