Wiring to a Furnace/ AC Air Handler
For this purpose, never use a device that cycles the main power to the
UltimateAir 200DX. Cycling main power ON/OFF is detrimental to the
system electronics and will void the warranty.
Wiring to a Furnace/AC Air Handler Continued…
When integrating the UltimateAir ERV with existing forced air systems, it
may need to operate in conjunction with the furnace/AC air handler.
1.
On the Furnace, locate the 24 VAC (low voltage) which activates when
the Furnace blower is ON. Furnace outputs are generally marked G for
“Go/Run” and C for Common; refer to the particular furnace manual for
details.