Please refer
to page 22
for GenerLink™
testing,
while utility power
is present.
Audible Alarm
Audible Alarm
GenerLink
™
units equipped with optional surge protection are also equipped
with an audible alarm. The alarm will sound continuously if the surge
components require service. (Refer to the Terms and Conditions for service
instructions). Do not, under any conditions, attempt to remove or repair
GenerLink
™
yourself.
If the alarm is sounding, you
CAN CONNECT
a generator to GenerLink
™
.
The audible alarm is an indication that service may be required. An authorized
utility technician or licensed electrician must service the device. (Refer to the
Terms and Conditions for service instructions)
T
T
roubleshooting T
roubleshooting T
ips
ips
Problem
The GenerLink
™
will not transfer to the generator during testing with utility
power present.
Cause
The GenerLink
™
unit is equipped with a lockout circuit that prevents transfer
to generator power if the load on the home exceeds 30-amps. The yellow
status light will be illuminated if the load exceeds 30-amps
Solution / Testing
1. Disconnect the generator.
2. Reduce the load by turning off ALL the circuit breakers in the house
3. Confirm that the yellow status light is not illuminated
4. Reconnect and restart the generator.
5. Restore load equal to or less than the capacity of generator.
6. Operate household loads using your generator.
7. Do not, under any conditions, attempt to remove or repair GenerLink
™
yourself.
Problem
GenerLink
™
will not continuously connect the generator to the loads or it
periodically cycles the loads on and off.
Cause
GenerLink
™
is equipped with load sensing capabilities. If it detects a
connected load that exceeds the 30 amp continuous load rating, it will
automatically disconnect the generator for a short period of time.
Solution
Reconnect GenerLink
™
through the 30-amp, 4 blade connector.
Problem
The green indicator light on GenerLink
™
is not illuminated when utility power
is present.
Cause
The green status light on the bottom of the GenerLink
™
must be illuminated
when utility power is present. If it is not illuminated, this may indicate an
abnormal condition that may require service.
Solution
1. Call for service. (Refer to the Terms and Conditions for service instructions)
2. Do not attempt to test or use the GenerLink
™
with a generator until the
condition is corrected.
3. Do not, under any conditions, attempt to remove and/or repair GenerLink
™
yourself.