The Connection Cord:
Connection cords are typically 20 to 60 feet long, with a maximum
recommended length of 60 feet for a 30-amp circuit. To determine the correct
cord length, follow these easy steps:
STEP 1.
Select a location for your generator when it is being used with
GenerLink
™
. Consult your generator manufacturers owner’s manual for
instructions on the acceptable placement of your generator.
STEP 2.
Measure the length of the cord you will need by calculating the
distance from the installed GenerLink
™
to your generator, including the
vertical distance from the electric meter to the ground.
The length of the power cord should always be as close as possible to the actual
measured distance from the electric meter in order to maximize your generator’s
power quality. Additionally, the power cord must be fully unrolled during use.
NOTE:
The GenerLok
™
power cord is the only power cord approved for use
with GenerLink
™
. The GenerLok
™
connector can only be used with
GenerLink
™
. It is not compatible for use with any other electric
appliance/device.
8
17
T
T
echnical Fact Sheet
echnical Fact Sheet
GenerLink
™
Specifications and Technical Information
Physical:
Diameter:
6
¹₂
in.
Depth:
5
¹₄
in.
Weight w/o surge:
5
¹₂
lbs
Weight with surge:
5
³₄
lbs
Socket Style:
Ring or Ring-less, 200 Amp, 4 jaw
Electrical:
Source Compatibility:
200 Ampere Service or Less
Withstand Current:
8,000 Amperes rms symmetrical at .5 pf, 240
Volts, 60 Hz 6000 Amperes for 6 cycles
at .7 - .8 pf, 240 Volts, 60 Hz
Generator Input:
8.5kW Continuous
†
, 120/240 Volt
8.5kW Continuous for MA-23
Connection:
Proprietary GenerLok™ QuickConnect
Power Cord
Operational:
Transfer Type:
Break-Before-Make
Transfer Delay:
2-3 Seconds
Life Cycle:
300,000 Operations
Temperature Range:
-30°C to 60°C External Ambient
Features:
Generator Input Protection:
Generator Input Voltage
≥
200 Volts
Supplemental Overcurrent
≤
40 A
Utility Input Protection:
Utility Input Voltage
≥
180 Volts
Over-Temperature Trip
≥
105°C
Load Protection:
Integrated Whole-House Surge Protection
Model MA 23-S Only (Optional)
Type 1 - 75kA per phase
Status Indication:
Long-life LED indicators show utility power
availability and/or fault presence
Listings:
UL 1008M - Meter socket transfer switch
†
3 hours at 25°C/ 77°F ambient
*When protected by max 200 A circuit breaker in series with 100 A branch circuit breaker