background image

7

• 

Never apply voltage to the inputs.

• 

Temperature affects readings. Allow the CLM100 to attain the ambient temperature of the wire under test.

• 

 Use a 9 Volt alkaline battery only

• 

Use the test leads that came with the unit only. Other leads will not work.

• 

Ensure that the test leads are clean and in good working order.

• 

Use an abrasive pad similar to the one provided to ensure the wire under test is clean and free of oxidation

• 

Ensure that insulation is stripped adequately from both ends of the wire under test. This will enable 

measurements to be accurate.

• 

Ensure that the alligator clips are connected across the diameter of the wire under test.

• 

When measuring wire for insertion into conduit, add extra wire to compensate for the accuracy of the 

meter. For example, 205 feet of wire is needed to run inside a piece of conduit that is 200 feet long. (This 

would allow 2.5 feet on each end to attach the wire.) At 205 feet and 70˚F, the cable length meter has an 

accuracy of ±7 feet. In this case it would be safer to measure out 212 feet of wire. This would ensure that 

enough wire is available for the application.

OPERATIONAL HINTS

Содержание CLM100

Страница 1: ...CLM100 Cable Length Meter 1 800 547 5740 www ueitest com email info ueitest com INSTRUCTION MANUAL ENGLISH ...

Страница 2: ...8 8 8 8 Introduction Features icludes Safety Tips International Symbol Instructions Calibration Procedures Measuring Length of Wire Low Battery Indication Measuring Resistance Specifications Operational Hints Warranty Disposal Cleaning Storage ...

Страница 3: ...gs Please see accuracy specifications For best results allow the CLM100 to attain the same ambient temperature as the wire under test The length of time this will take depends on the ambient temperature Typically it will take 10 to 15 minutes for the CLM100 to attain equal ambient temperature INTRODUCTION Before using this meter read all safety information carefully In this manual the word WARNING...

Страница 4: ...ks and the red test leads into the other pair of input jacks Ignore the gray marking on the banana plug This is very important to ensure that the meter works correctly If black and red test leads are mixed the unit will give a false reading Fig 1 INSTRUCTIONS Fig 1 Fig 2 NOTE Make sure clips are as close together as possible Use the tips of the Kelvin clips when performing measurements on small di...

Страница 5: ...illuminate in the top left corner of the display 7 Press the FT button if you require readings to be in feet The ft enunciator will illuminate in the display 8 Press the M button if you require readings to be in meters The m enunciator will illuminate in the display 9 Connect a Kelvin clip to one end of the wire and the other Kelvin clip to the other end of the wire 10 Read the length of wire dire...

Страница 6: ... 3 LSD LSD least significant digit Resistance 0 to 65Ω 2 of reading Operating Temperature 32 to 104 F Operating Humidity 20 to 80 RH Storage Temperature 0 to 120 F Auto power off After 5 minutes approx Battery Life Depends on use Typically 40 hours Extended measurements times can lower battery life to no less than 6 hours WARNING This meter is NOT designed to measure less than 25ft cable SPECIFICA...

Страница 7: ...dequately from both ends of the wire under test This will enable measurements to be accurate Ensure that the alligator clips are connected across the diameter of the wire under test When measuring wire for insertion into conduit add extra wire to compensate for the accuracy of the meter For example 205 feet of wire is needed to run inside a piece of conduit that is 200 feet long This would allow 2...

Страница 8: ...xpenses or economic loss A purchase receipt or other proof of original purchase date will be required before warranty repairs will be rendered Instruments out of warranty will be repaired when repairable for a service charge Return the unit postage paid and insured to 1 800 547 5740 FAX 503 643 6322 www ueitest com Email info ueitest com This warranty gives you specific legal rights You may also h...

Отзывы: