4

Mount the device using the four (4) 1/4” clearance holes in the enclosure base. Plumb sensor to the process port.  See page 20-21 for dimensions.
The device may be mounted in any position except with the sensor connection facing up. Ensure the process connection is sealed to the process 
port to prevent leakage.  Care should be taken to minimize effects of shock and vibration. The One Series should be protected from direct sunlight 
and rain in outdoor installations using a shroud (user supplied).  

NOTE

: the optimal display viewing position is 6:00.

FOR PRESSURE AND LOCAL TEMPERATURE MODELS ALWAYS HOLD A WRENCH ON THE SENSOR HOUSING HEX WHEN MOUNTING DEVICE. DO 

NOT TIGHTEN BY TURNING ENCLOSURE, THIS WILL DAMAGE THE CONNECTION BETWEEN THE SENSOR AND HOUSING.

FOR DIFFERENTIAL PRESSURE MODELS (ESPECIALLY LOW RANGE MODELS), MOUNT THE SENSOR LEVEL TO MINIMIZE ANY PRESSURE 

READING OFFSETS.  THE OFFSET COMMAND MAY BE USED TO ZERO THE DISPLAY, (SEE PAGE 13 FOR ADDITIONAL INFORMATION).

PROCESS CONNECTIONS AND SENSOR INSTALLATION

NEVER INSERT ANY OBJECT INTO THE PRESSURE SENSOR OPENING.  DAMAGE TO THE SENSOR WILL RESULT, AFFECTING ACCURACY.

Pressure and Differential Pressure Models

To pipe mount:  Thread the pressure connection onto the pressure port, with thread sealant, making sure that the mating threads are clean and 

free of debris.  Use a wrench on the pressure connection hex to tighten. Test for leaks.  On Differential Pressure models, the Low (L) side pressure 

must NOT exceed the high (H) side pressure.  Damage to the sensor may result.

Local and Remote Temperature Models

For Local Ambient Sensing (model L):  Mount using the mounting holes on the electronics housing.  Mount the device to ensure that the sensor 

housing will not be damaged and where the measured temperature is representative of the surrounding environment.

For Local Spring-Loaded (model T):  A suitable thermowell, made from corrosion-resistant material, 5 threads engaged minimum, with thread 

sealant, is required to maintain enclosure type 4X/IP66.

For Remote Sensing:  Route the extension wire to avoid contact with live components or close proximity to electrical noise sources. Avoid kinks, or 

excessive flexing. Tighten the ferrule fitting, if applicable.

For Surface Sensing:  Secure the sensor housing to the pipe or vessel using an adhesive or strapping method suitable for the application. 

For Immersion Sensing (models C, H, R & L):  Use of a thermowell is highly recommended to aid in maintenance, testing and preservation of the 

system integrity.  

For existing thermowells with 0.375” bore, an insert is available from UE as part number 62169-44 (see Figure 2).  The adapter provides a 

faster heat transfer by adapting the 0.250” diameter temperature sensor housing to a larger bore 0.375” thermowell.  Heat transfer compound is recommended 

in the bottom of the well and inside the adapter opening.

Insert the sensor housing (0.25” diameter) into the well ensuring that the sensor’s sheath bottoms out and the well is completely immersed in 

the media (2.5” min.) Screw the sensor’s nipple into the thermowell, with thread sealant, by placing a wrench on the union nut. Tighten the union 

connector.

For best temperature measurements, the sensor housing must be in full contact with the surface or media being measured.  Heat transfer compound 

may be used to aid in fully transferring the media temperature to the sensor housing. Locate where the temperature is most representative of the 

system.  Minimum insertion depth is 2-1/2”.  Sensor dimensional drawings are shown on page 21.

  0.375 REF 

0.250

REF

2.50

REF

SENSOR

THERMOWELL ADAPTER

[6.35] mm

[63.5] mm

[9.53] mm

Figure 2

Содержание 2SLP

Страница 1: ... HAZARDOUS AND THE FOLLOWING HAZARDOUS LOCATIONS AND IS ATEX AND IECEX CERTIFIED SUITABLE FOR APPROPRIATE USE IN GAS AND DUST ZONE 1 APPLICATIONS Model 2SLP N America Europe International Flameproof Cert Number UL File E226592 DEMKO 09 ATEX 0813748X IECEx UL 08 0017X Applicable Standards UL 50 UL 50E UL 61010 1 UL 1203 CSA C22 2 No 25 1966 CSA C22 2 No 30 M1986 CSA C22 2 No 94 01 07 CSA C22 2 No 9...

Страница 2: ...Series transmitter switch product line is based on an all solid state electronic module that incorporates a microprocessor The One Series Field Safety System is a loop powered all in one device connected directly to the final element and replacing a transmitter safety relay trip amplifier and logic solver It has an embedded high capacity programmable safety relay that provides extremely fast respo...

Страница 3: ...By pushing the right g button once the display will scroll as follows SP1 XX XX DB1 XX XX SP2 XX XX DB2 XX XX By pushing the left 2 button once the display will scroll the min max process values recorded in memory MAX XX XX MIN XX XX The display will automatically revert back to the Process Display mode after scrolling ALARM CONDITION When the process goes beyond the set point the display will beg...

Страница 4: ...ure that the sensor housing will not be damaged and where the measured temperature is representative of the surrounding environment For Local Spring Loaded model T A suitable thermowell made from corrosion resistant material 5 threads engaged minimum with thread sealant is required to maintain enclosure type 4X IP66 For Remote Sensing Route the extension wire to avoid contact with live components ...

Страница 5: ...oved Tools Required Small flat head screwdriver wire strippers TO PREVENT IGNITION DISCONNECT POWER BEFORE REMOVING ENCLOSURE COVER KEEP COVER TIGHT WHILE IN OPERATION DO NOT DISCONNECT EQUIPMENT UNLESS POWER HAS BEEN SWITCHED OFF OR THE AREA IS KNOWN TO BE NON HAZARDOUS DO NOT REPLACE COMPONENTS UNLESS POWER HAS BEEN SWITCHED OFF OR THE AREA IS KNOWN TO BE NON HAZARDOUS THE DEVICES SHALL BE PROPE...

Страница 6: ... diagnostics to determine the integrity of the SRO wiring and if the SRO is functioning properly NOTE As an alternative to loop power model 2SLP may be wired directly to a 24 VDC power supply and minus terminals In this wiring configuration power is provided for all switching and diagnostic functions but a 4 20 mA output is not possible This alternative method of powering the One Series Field Safe...

Страница 7: ...ut function as normal NOTE The 4 20 mA analog signal is not possible in this wiring configuration In this configuration the 4 20 mA output and IAW Output are monitored by the safety system logic solver The final element is controlled by the logic solver Total wire connections 4 The 4 20mA signal is used by the logic solver to initiate the safety function IAW provides a separate indication of devic...

Страница 8: ...s Field Safety System fully configured where the health status IAW and SRO switch status signals are being monitored by a logic solver PLC or DCS These connections are not required however UE recommends monitoring the IAW signal to maximize the safe failure fraction in an SIS application Additionally wiring the SRO to an external load final element is not required For direct control of a final ele...

Страница 9: ...000 0 39 714 3 1045 5 40 761 9 1090 9 No Fault Displayed 4 20 mA Normal Operating range Unused Fault 3 6 3 8 mA Normal Under range 4 20 20 5 mA Normal Over range 21 0 mA 21 0 mA only when the temperature sensor is subject to 103 25 to 110 of range or when the pressure sensor is subject to 103 25 to 150 of range Fault 0 FAULT CURRENT In addition to the discrete IAW and Safety Relay Output status si...

Страница 10: ...ft 2 button increments the blinking digit The right g button sets the digit and moves to the next Once a valid password is entered OK will appear on the display Press and release the right g button CLR MAX MIN or MAN RSET if Latch is set will appear on the display This is the first command prompt in the Programming Mode NOTE The Field Safety System will automatically exit the Programming Mode and ...

Страница 11: ... opens on falling process values that reach the set point OPEN WINDOW The Safety Relay Output opens when process values are within a specified range set by two points set point high and set point low Please use the Safety Relay Output Decision Logic Figure 13 page 12 for help with setting the appropriate Safety Relay Output mode Press and release the left 2 button until the desired mode appears Pr...

Страница 12: ...16 Resetting the Maximum Minimum Values The One Series Field Safety System continuously records the readings from the sensor and stores the minimum and maximum MAX MIN peak hold values in non volatile memory The max min values may be viewed at any time by removing the enclosure cover page 5 and pushing the left 2 button The display will scroll the MAX MIN values and then return to the Process Disp...

Страница 13: ... and change the offset Zero is the factory setting Press the left 2 button to increment the blink ing digit Press the right g button to enter and move to the next digit Press the right g button to enter the new offset and return to the main menu Adjusting Span SPAN provides an adjustment to shift the slope of the sensor s response curve to accommodate an offset value other than zero To adjust SPAN...

Страница 14: ...lity to detect that the process port may be plugged It does this by monitoring the sensor for changes over time The amount of change and the time period are programmable If the process variable does not change by the amount and selected time period the display will indicate PLUG and the IAW Output will open indicat ing a fault Refer to the Programming Flowchart on page 19 Enter the Programming Mod...

Страница 15: ...cations it is desirable to dampen the Safety Relay Output response and prevent intermittent false trips due to pressure spikes or other transient isolated events The Filter feature provides a software digital filter with a configuration time constant for sup pressing certain transient short duration events Refer to the Programming Flowchart on page 19 Enter the Programming Mode see page 10 and mov...

Страница 16: ... left 2 button to change to NEG Press the right g button to view and change the scale Press the left 2 button to increment the blinking digit Press the right g button to enter and move to the next digit This process value must be between 3 and 25 of the sensor s maximum range Press the right g button to enter the new scale and return to the main menu Setting the 20 mA portion of the scale see Figu...

Страница 17: ...pen check all sensor connections E 16 Diagnostic Fault Sensor SHORT A short circuit has been detected on the sensor drive pins 2 3 Diagnostic Fault Sensor Short check all sensor connections E 18 Diagnostic Fault Relay Monitor The relay output fault monitor circuit has detected that the output state of the solid state relay is incorrect This feature must be enabled in the menu Check the wiring conn...

Страница 18: ...E ORIGINAL DATE DRWN CHKD APPD DO NOT SCALE THIS DRAWING DOC DE733010102 Rev B EM ONE SERIES 1X NAMEPLATE A 6211 847 SR 5 14 15 6211 847 DESCRIPTION DATE DRWN APPD UNLESS OTHERWISE SPECIFIED DIMENSIONS ARE IN INCHES REV ECN Figure 19 Kanban number and Date Code Set Point Reached IAW Fault SRO Status IAW Output Safety Relay Output No No Closed Closed Closed No Yes Open Open Open Yes No Open Closed ...

Страница 19: ...pend on sensor range Invalid PWORD BOTH Abort NO RESET OK Flash Err Abort BDOOR PWORD Valid SAVING SAVING One Series Field Safety System LCH1 ON OFF OFST POS NEG 8888 Set Blinking Digit Increments Blinking Digit Sets Digit and moves to next SPAN POS NEG 8888 Set Blinking Digit Increments Blinking Digit Sets Digit and moves to next Offset out of Range flash Err SPAN out of Range flash Err PLUG PORT...

Страница 20: ...OR PORT 1 2 14 NPT SENSOR PORT 1 20 NPT SENSOR PORT 1 20 NPT SENSOR PORT 111 92 mm 76 2 mm 133 35 mm 12 7 mm SURFACE MOUNTING KIT 6361 704 144 78 mm 134 62 mm 137 16 mm 154 94 mm 134 62 mm 137 16 mm 264 16 mm 203 2 mm 137 16 mm 129 54 mm 134 62 mm 137 16 mm 76 2 mm 92 20 mm 129 54 mm 134 62 mm 137 16 mm 107 95 mm 61 91 mm 158 75 mm 7 11 mm 107 95 mm 76 2 mm 6 35 mm 8 73 mm DIMENSIONAL DRAWINGS GAG...

Страница 21: ...SULATED CABLE Ø0 125 3 18 mm FOR DC UNITS Ø0 250 6 35 mm 1 2 NPT COMPRESSION FITTING 300 SERIES st st 26 AWG STRANDED TEFLON INSULATION 4 50 114 3 mm FIXED DIM EPOXY SEAL 2 00 50 8 mm FIXED DIM 1 2 14 NPT PIPE NIPPLE 300 SERIES st st 0 50 12 7 mm Temperature Sensors Remote TR1 TRC TH1 THC TC1 TCC SENSOR OPTIONS Spring Loaded Local TTC Fixed Local TL1 TL3 Differential Pressure 1 4 18 NPT MALE BOTH ...

Страница 22: ...ée de fil électrique Ne pas monter l unité à des températures ambiantes dépassant les limites publiées Cela est particulièrement important pour les unités de tem pérature à montage locale L utilisation envelopper est recommandée lorsque le soleil et la pluie peuvent entrer en contact avec le boîtier 1 In order to meet the electromagnetic compatibility requirements specified in EN61000 6 2 Im munit...

Страница 23: ... retirer le couvercle du boîtier Maintenir le couvercle fermé pendant le fonctionnement Ne pas décon necter l équipement que lorsque l alimentation est coupée ou que la zone est connue pour être non explosives 5 Do not replace components unless power has been switched off or the area is known to be non hazard ous Ne remplacez pas les composants avant que le courant soit coupé ou que la zone est co...

Страница 24: ...or personnel Electrical ratings stated in literature and on nameplate must not be exceeded Overload on a switch can cause damage even on the first cycle Wire unit accord ing to local and national electrical codes using wire size recommended in installa tion sheet Do not mount unit in ambient temp exceeding published limits LIMITED WARRANTY Seller warrants that the product hereby purchased is upon ...

Отзывы: