5. LOCATING FAULTY STEAM TRAPS

An ultrasonic test of steam traps is a positive test.  The main advantage to ultrasonic testing is that it isolates the

area being tested by eliminating confusing background noises.  A user can quickly adjust to recognizing differences

among various steam traps, of which there are three basic types:  mechanical, thermostatic and thermodynamic.

When testing steam traps ultrasonically:

1. Determine what type of trap is on the line.  Be familiar with the operation of the trap.  Is it intermittent or

continous drain?

2. Try to check whether the trap is in operation (is it hot or cold? Put your hand near, but do 

not 

touch the trap,

or, better yet, use a non-contact infrared thermometer).

3. Use the contact (stethoscope) module.

4. Try to touch the contact probe towards the discharge side of the trap.  Press the trigger and listen.

5. Listen for the intermittent or continuous flow operation of the trap.  Intermittent traps are usually the inverted

bucket, thermodynamic (disc) and thermostatic (under light loads).  Continuous flow:  include the float, float

and thermostatic and (usually) thermostatic traps. While testing intermittent traps, listen long enough to gauge

the true cycle.  In some cases, this may be longer than 30 seconds.  Bear in mind that the greater the load that

comes to it, the longer period of time it will stay open.

In checking a trap ultrasonically, a continuous rushing sound will often be the key indicator of live steam passing

through.  There are subtleties for each type of trap that can be noted.

Use the sensitivity levels of the Sensitivity Selection Dial to assist your test.  If a low pressure system is to be

checked, adjust the sensitivity UP toward 8; if a high pressure system (above 100 psi) is to be checked, reduce the

sensitivity level. (Some experimentation may be necessary to arrive at the most desirable level to be tested.)  Check

upstream and reduce the sensitivity so that the meter reads about 50% or lower, then touch the trap body down-

stream and compare readings.

GENERAL STEAM/CONDENSATE/FLASH STEAM CONFIRMATION

In instances where it may be difficult to determine the sound of steam, flash steam or condensate,

1. touch at the immediate downstream side of the trap and reduce the sensitivity to get a mid-line

reading on the meter (about 50%).

2. move 6 - 12 inches (15.2-30.5 cm) 

downstream 

 and listen.  Flashing steam will show a large drop

off in intensity while leaking steam will show little drop off in intensity.

-11-

trap shot

Содержание VOLUME 1.3

Страница 1: ...ULTRAPROBETM 100 INSTRUCTION MANUAL VOLUME 1 3...

Страница 2: ...LTRAPROBE USERS OUR STAFF HAS YEARS OF FIELD EXPERIENCE AND IS STANDING READY TO ASSIST YOU SHOULD YOU NEED US WHEREVER YOU ARE REMEMBER WE ARE AS CLOSE AS YOUR PHONE FAX OR COMPUTER CALL 914 592 1220...

Страница 3: ...of 0 to 70 Asthedialisturnedtotheright to 0 thesensitivityoftheinstrumentincreases Asthedialisturnedtotheleft to 70 thesensitivtydecreases Alowlevelultrasoundemissionproduceslowamplitude Forthisreason...

Страница 4: ...ield It is used to block out stray ultrasound and to assist in narrowing the field of reception of the Scanning Module It also increases the sensitivity To use simply slip it over the front of the sca...

Страница 5: ...r Amplifier which is a loud speaker that is compatible with the Ultraprobe headphone output jack 5 WTG 1 WARBLE TONE GENERATOR OPTION The WTG 1 Tone Generator is an ultrasonic transmitter designed to...

Страница 6: ...s specific sensor is limited to the particular gas it was designed to sense e g helium The Ultraprobe can sense any type of gas leak since it detects the ultrasound produced by the turbulence of a lea...

Страница 7: ...method only in addition to the glove use a wipe rag to wrap around the rubber focusing probe tip Hold the rag in the gloved hand so that it actsasa curtain i e there is enough material to cover the te...

Страница 8: ...en but they will be heard This method is capable of obtaining successful leak checks in systems with leaks as low as 1x10 6 ml sec NOTE The low surface tension of the LLA is the reason small bubbles f...

Страница 9: ...e leak to be tested the thickness of the test wall and the type of material tested i e is it sound absorbant or sound reflective Remember you are dealing with a high frequency short wave signal If the...

Страница 10: ...ng tracking and corona without taking the switchgear off line to perform an infrared scan However it is recommended that both tests be used with enclosed switchgear NOTE When testing electrical equipm...

Страница 11: ...ty whereas conventional methods are incapable of detecting very slight faults As a ball passes over a pit or fault in the race surface it produces an impact A structural resonance of one of the bearin...

Страница 12: ...gy These normal microscopic disuniformities will begin to produce wear and the possibilities of small fissures may develop which contributes to the Pre Failure condition Therefore aside from normal we...

Страница 13: ...ttent traps listen long enough to gauge the true cycle In some cases this may be longer than 30 seconds Bear in mind that the greater the load that comes to it the longer period of time it will stay o...

Страница 14: ...orcesthediscagainstthe valve seat The static pressure over a large area overcomes the high inlet pressure of the steam As the steam starts to condense the pressure against the disc lessens and the tra...

Страница 15: ...s or parts of the system and make it difficult to diagnose valve leakage In this case it is still possible to diagnose valve blow through by comparing sonic intensity differences by reducing the sensi...

Страница 16: ...sound amplification is a very important feature Although there are obvious audible sounds emitted by most operating equipment it is the ultrasonic elements of the acoustic emissions that are generally...

Страница 17: ...orexceedsANSIspecificationsandOSHAstandards Transmitter Patentedwarbletonetransmission Responsetime 300m sec Ambient Operating Temperature Range 32o 120o F 0o 50o C Relative Humidity 10 95 noncondensi...

Страница 18: ...equipment with your hands or fingers Be sure to use appropriate lockout procedures when attempting repairs Be careful with loose hanging parts such as the wrist strap or headphone cord when inspectin...

Отзывы: