Yudian (H.K.) Automation Technology Co. Ltd.
Website:
http://www.yudian.us
http://www.yudian.com.hk
Email:
Tel: +852-2770 8785 Fax: +852-2770 8796
TECHNICAL SPECIFICATION
Input:
Thermocouples: (with J1 module)
K, S, R, E, J, T, B, N and WRe5-WRe26
Two-wire RTDs: (with J2 module that supports 2 inputs)
PT100, Cu50, 0~80 ohm, 0~400 ohm
Three-wire RTDs: (with J0 module that supports 1 inputs)
PT100, Cu50, 0~80 ohm, 0~400 ohm
Linear mV voltages: (with J1 module)
0~20mV, 0~60mV, 0~100mV, 0~1V
Linear voltage: (with J3 module)
0~1V, 0~3V, 0~5V, 1~5V etc.
Linear current: (with J4 module)
0~12mA, 0~20mA, 4~20mA etc.
Square root extraction calculation input: (with J3 voltage or J4 current input module)
1~5V, 4~20mA etc.
Two-wire transmitter inputs: (with J5 module that provides 24VDC power supply)
Connect to 4~20mA two wires transmitter
Maximum lead wire resistance for RTD input:
2-wire type RTDs:
2 ohm for Pt100 or 0~400 ohm input ;1 ohm for Cu50 and 0-200 ohm input
;
3-wire type RTDs:
5 ohm
Measurement range
:
K(0~1300
℃
), S(0~1700
℃
), R(0~1700
℃
), T(-200~+350
℃
), E(0~1000
℃
),
J(0~1200
℃
), B(0~1800
℃
), N(0~1300
℃
), WRe5-WRe26(0~2300
℃
),
Pt100(-200~+800
℃
), Cu50(-50~+150
℃
)
Linear input
:
-1999~+9999 set by user
Measurement accuracy:
±0.2%FS±1digit / ±0.3%FS±1digit (only for Cu50)
Note 1:
For thermocouple inputs with internal cold junction compensation, 1
℃
CJC error
should be taken into consideration. For those with Cu resistor, ice point or thermostat bath
compensation, the accuracy is as above.
Note 2:
Accuracy is not guaranteed between 0 and 600
℃
for type B thermocouple input.