Yudian (H.K.) Automation Technology Co. Ltd.
Website:
http://www.yudian.us
http://www.yudian.com.hk
Email:
Tel: +852-2770
8785 Fax: +852-2770 8796
AF
Advanced
function
selection
AF is used to select advanced function. The value of AF
is calculated as below:
AF=Ax1 + Bx2 + Cx4 + Dx8 + Ex16
A=0, Slow cyclic display;
A=1, Fast cyclic display.
Above setting only affects display and has no effect on
internal scan speed and alarm response time.
B=0, RTD input use two-wire wiring;
B=1, RTD input use three-wire wiring.
C=0, Only channel 2 is retransmitted to COMM port;
C=1, All input channels are cyclically retransmitted, and
the retransmission time interval on every channel is about
3 seconds. The output ranges of all channels are defined
by dIL2 and dIH2.
D=0, Normal;
D=1, All low limit alarms are changed to high limit alarm.
E=0, Normal;
E=1, Set M2(MIO) and M3(OUPT) support single channel
input only.
For example, to set a AI-702M with 2 inputs, fast cyclic
display, channel 1 input from three-wire RTD (J0 module
on M1 socket), channel 2 input from thermocouple (J1
module on M2 socket), current retransmission of channel
2 outputted to COMM port, the AF parameter should be
set as below:
A=1,B=1,C=0,D=0, then AF=19.
0~31
nonc
NO/NC
selection
Single channel relay module provides both normal open
and normal close output, while dual relay output module
only provides NO output.
If L5 dual relay installed, set nonc=0, all in NO status, set
nonc=127, all in NC status.
However, by parameter “nonc”, the NO output can
be
changed to NC output.
nonc = Ax1 + Bx2 + Cx4 + Dx8 + Ex16 + Fx32 + Gx64
A,B,C,D,E,F,G respectively set NO/NC output of OP1,
OP2, AL1, AL2, AU1, AU2 and MIO. 0 means the
corresponding output is NO, and 1 means NC output.
0 ~63, 127
OPn
Select the
channel to be
retransmitted
OPn=0, OUTP port is for alarm output.
OPn=1~4, OUTP port is used for retransmission of
channel OPn.
OPn=7, Re-transmit the minimum value, among all
channels (defined by Cn) to OUTP
OPn=8, Re-transmit the maximum value, among all
channels (defined by Cn) to OUTP
0~4, 7~8