STEP 4 Vertical Pull Test
Lift up vertically on the UbiCell to
confirm that the hooks are fully
engaged.
STEP 5 Dimming Test
When correctly installed, the UbiCell
should follow the following flash
patterns based on expected
functionality:
If the luminaire supports dimming
functionality
, there will be 3 flashes
(on/off) for one second each.
If
dimming is not available
, there will
be no flashes.
If the expected results are not
achieved, check the line power. If
power is confirmed, perform a second
vertical pull test to validate that the
pins were properly rotated into the
sockets in Step 3. If proper
installation is confirmed, then mark
the UbiCell for return and install a
new UbiCell.
STEP 6 Glove Test
Cover the UbiCell or ALS entirely
with a glove or other blacked-out
material to trigger photocell and turn
on the lamp.
If the glove test fails, check the line
power. If power is confirmed,
perform a second vertical pull test to
validate that the pins were properly
rotated into the sockets in Step 3. If
proper installation is confirmed, then
mark the failed UbiCell for return and
install a new UbiCell.