Enilit RTU 

 

 

User manual 

 

 

 

 

 

Содержание Enilit RTU

Страница 1: ...Copyright UAB Enilit All rights reserved 2010 2018 Enilit RTU User manual ...

Страница 2: ... 2 3 1 Decommissioning 10 2 3 2 Disposal 10 2 4 Declaration of conformity 10 2 5 Handling of electronic equipment 12 2 6 Warnings regarding use of UAB Enilit products 12 2 7 Guarantees 13 2 8 Copyright 14 3 Enilit RTU Hardware 15 3 1 System Conception 15 3 2 Rack mounting and Frame 16 3 3 Short hardware review 18 3 3 1 Power Supply Module 19 3 3 2 Central Processor Modules 19 3 3 3 I O Modules 19 ...

Страница 3: ... 39 3 10 Transducer less Measurements module AC 31 40 3 10 1 Wiring diagram 41 3 10 2 Technical Data 42 3 11 Glass fiber optic module ST 61 43 3 12 Plastic fiber optic module PL 61 45 3 13 Communication module CD 61 CK 61 47 3 14 Ethernet communication module LAN 21 49 3 15 Installation of System Housing 50 3 16 Order book 51 3 16 1 Basic frame 51 3 16 2 Second frame 54 4 Enilit RTU software 55 4 ...

Страница 4: ...on 116 4 10 3 IEC 60870 5 104 configuration 128 4 10 4 IEC 61850 client 136 4 10 5 Modbus RTU ASCII 149 4 10 6 Modbus TCP client 156 4 10 7 DNP3 serial master configuration 159 4 10 8 DNP3 UDP TCP IP client configuration 171 4 10 9 Simulator master configuration 173 4 10 10 RP 570 configuration 176 4 10 11 SPA Bus configuration 182 4 10 12 System monitor 192 4 11 Slave protocols 197 4 11 1 IEC 608...

Страница 5: ... 285 4 16 4 Events log 286 4 17 Redundancy 289 4 17 1 Redundancy support 289 4 17 2 Redundancy types 289 4 17 3 Connection diagram 289 4 17 4 Enilit RTU redundancy principles 290 4 17 5 Monitored fault locations 291 4 17 6 Redundancy configuration 291 4 17 7 Communication channel configuration 293 4 17 8 Status signals commands and measurements 298 4 18 Cyber security capabilities 302 4 18 1 Intro...

Страница 6: ...ver all conceivable circumstances or include detailed information on all topics In the event of questions or specific problems do not take any action without proper authorization Contact UAB Enilit office and request the necessary information 1 2 Enilit RTU The automation technology is rapidly advancing New communication techniques and devices and standard protocol interfaces combined with the imm...

Страница 7: ...king 1 millisecond Secure process inputs outputs with high isolation voltage 2 5 kV Pre processing and compressing of acquired process data e g metered value formation threshold value processing initiation delay debouncing signal damping Optimized flow of remote data transmission spontaneous cyclic or on demand transmission differentiated interrogation lists priority improvement general interrogat...

Страница 8: ...tation must never be exceeded 2 Always disconnect the device before changing the system or signaling wiring 3 The housing does not contain any operation relevant elements The device must never be opened 4 Do not operate the device in inflammable or explosive environments 5 Do not expose the device to rain or humidity 6 With regard to the installation location take care that the ventilation is suff...

Страница 9: ... using the protective earth terminal or the appropriate termination of the supply plug in the case of plug connected equipment Omitting or disconnecting the equipment earth may cause a safety hazard Recommended minimum earth wire size is 2 5mm 2 2 4 Power Supply Connection This device does not have its own mains switch and starts operation immediately after the application of system voltage Hence ...

Страница 10: ...n the Enilit RTU may include capacitors across the supply or to earth To avoid electric shock or energy hazards after completely isolating the supplies to the Enilit RTU both poles of any dc supply the capacitors should be safely discharged via the external terminals prior to decommissioning 2 3 2 Disposal It is recommended that incineration and disposal to watercourses be avoided The product shou...

Страница 11: ...09 EN 61000 3 2 2006 A2 2009 Harmonic current emission Electromagnetic immunity EN 61000 4 3 2006 EN 61000 4 3 2006 A1 2008 EN 61000 4 3 2006 A2 2010 Radiated RF electromagnetic field immunity test EN 55024 2010 EN 61000 4 2 2009 Electrostatic discharge immunity tęst EN 55024 2010 EN 61000 4 4 2012 Electrical fast transients burst immunity tęst power port EN 55024 2010 EN 61000 4 4 2012 Electrical...

Страница 12: ...rcuit board Avoid touching the electronic components printed circuit track or connectors 3 Do not pass the module to any person without first ensuring that you are both at the same electrostatic potential Shaking hands achieves equipotential 4 Place the module on an antistatic surface or on a conducting surface which is at the same potential as you 5 Store or transport the module in a conductive b...

Страница 13: ...n designer is ultimately responsible for verifying and validating the suitability of UAB Enilit products whenever they are incorporated in a system or application even without limitation of the appropriate design process and safety levels of such system or application 2 7 Guarantees UAB Enilit guarantees that the information in this document is accurate The document has been carefully reviewed for...

Страница 14: ...liable for any delay in performance due to causes beyond its reasonable control The warranty provided herein does not cover damages defects malfunctions or service failures caused by owner s failure to follow the UAB Enilit installation operation or maintenance instructions Owner s modification of the product owner s abuse misuse or negligent acts and power failure or surges fire flood accident ac...

Страница 15: ...different media for instance dedicated lines private or leased lines based on copper cables or glass FO cables dial up connections via analogue telephone network digital ISDN network and GSM networks 900 MHz e g D1 or D2 serial interfaces V 24 V 28 in combination with transmission systems like PCM30 PDH or SDH systems or with private radio networks LAN WAN connections via 10 100 1000 MB s Ethernet...

Страница 16: ...ly module and a central processor module Maximum number of 12 slots for I O and communication modules is available More I O modules can be achieved by connecting two basic frames Second frame should have Power Supply and can have 16 I O or communication modules of any type Frames are connected with external cable for communication between CPU and modules of the second frame Expanding Enilit RTU wi...

Страница 17: ...Enilit RTU User Manual 16 09 Enilit RTU Hardware Rack mounting and Frame Page 17 of 309 Standard or extended frame front view Standard or extended frame top view ...

Страница 18: ...in one basic 6U frame system protection class IP 20 One frame can include two power supply modules central processor module second frame not necessary 12 slots for I O and communication modules at maximum 12 boards inside one rack could be installed Place of the boards according type in the rack it isn t necessary No difference for RTU what type DI DO AI or ST board is installed in the slot ...

Страница 19: ...sor module is in charge of communication interface operation control of I O modules acquisition and archiving of process information and execution of PLC programs The following central Processor Modules are available in the standard versions Module Communication interfaces CPU 4x 4 Ethernet RJ45 12 Serial links RJ45 3 3 3 I O Modules Depending on the scope of process data it is possible to fit the...

Страница 20: ...t AI 31 12 20 mA to 20 mA or 10V to 10 V Glass fiber optic module ST 61 6 x FO ST type Plastic fiber optic module PL 61 6 x FO PL type RS 232 Com port module CD 6xRS 232 RS 485 Com port module CK 6xRS 485 3 4 Additional features External VGA compatible monitor keyboard and mouse for RTU monitoring management and configuration External Touch Screen monitor for one or several feeders visualization a...

Страница 21: ...r types of central processor unit modules available Module Communication interfaces CPU 41 4 x Ethernet RJ45 12 x RS485 Serial links RJ45 CPU 42 4x Ethernet RJ45 4 x RS232 Serial links RJ45 8 x RS485 Serial links RJ45 CPU 43 4x Ethernet RJ45 8 x RS232 Serial links RJ45 4 x RS485 Serial links RJ45 CPU 44 4x Ethernet RJ45 12 x RS232 Serial links RJ45 ...

Страница 22: ...e acquisition and archiving of process information and for the execution of PLC programs Central processor unit front and side view No Explanation Note Function LED indication 1 LED indicator Error1 Hardware configuration status LED is BLINKING mistake in hardware configuration Error2 User defined 2 LED indicator Run CPU status LED is BLINKING device is OK running 3 Push button Reset Manually rese...

Страница 23: ...tor 6 USB socket USB1 USB4 Socket to connect keyboard mouse USB stick and etc 7 Serial communication interface socket RJ 45 COM1 COM12 Connect others RTUs or protection devices 8 Ethernet communication interface socket RJ 45 ETH1 ETH4 Connect control centers or protection devices Note If Error1 and Error2 LEDs lights up and RUN LED is OFF that means CPU error or system is starting ...

Страница 24: ... 485 2 wire 1 Not used Not used Not used Not used 2 RX RX RB DB 2 3 pins should be linked together 3 TX TX TB DB 4 Not used GND GND GND 5 GND RX RA DA 5 6 pins should be linked together 6 Not used TX TA DA 7 Not used Not used Not used Not used 8 Not used Not used Not used Not used RJ45 connector The status of each communication interface is shown via the two software controlled LEDs that are insta...

Страница 25: ...rface is shown via the two software controlled LEDs that are installed in the connectors The green LED lights up if there is a physical connection to a device i e if the connection layer is in operation The yellow LED is activated during transmission of data in the transmission or the receive direction 3 5 3 Parallel Redundancy Protocol PRP Parallel Redundancy Protocol PRP is supported by Enilit R...

Страница 26: ...0 Base TX RJ45 socket 8 pin socket Twisted pair cable CAT5 speed 10 100 1000 Mbps Working temperature 25 85 C on request range can be extended Working humidity 0 95 RH non condensing 3 5 5 WatchDog WatchDog State Description Normal Device is turned on Enilit CMS is working RTU hardware configuration state has no abnormal card states Normal Device is starting Watchdog relay time out timer didn t en...

Страница 27: ...ltage 110V DC PS 31 Input voltage 220V DC PS 41 Input voltage 48V DC PS 51 Each type off power supply has 12V DC output which can be used to connect power supply for external monitor or some other device Max power for this output is 3 Amps In one Enilit RTU can be installed two power supply units whose one can work from different voltages one from AC and another from DC supply voltage at the same ...

Страница 28: ...s ON voltage is OK 2 LED indicator 12V PS output voltage status LED is ON voltage is OK 3 LED indicator 110V AC 230V AC 48V DC 110V DC 220V DC PS input voltage status LED is ON voltage is OK 4 Input voltage connection terminals 5 12V DC output connection terminals 3 6 1 Wiring diagram Terminal Function AC Voltage DC Voltage L L1 N N PE Ground Ground Power supply wiring diagram ...

Страница 29: ...s 115V at full load Hold up time Typ 25ms 230V 30ms 115V at full load Input voltage range Input voltage range PS 11 Input voltage range PS 21 Input voltage range PS 31 Input voltage range PS 41 Input voltage range PS 51 88 132VAC 176 264VAC 88 132VDC 176 264VDC 36 84VDC Frequency range 47 63Hz Current Typ 3A 115V 2A 230V Inrush current Typ COLD START 40A 230V Leakage current 2mA 240VAC Working tem...

Страница 30: ... processing of up to 24 digital input signals Digital input board front and side view No Explanation Function LED indication 1 LED indicators for each digital input Digital input status LED is ON input is active LED is OFF input is inactive ALL LEDS are blinking together no connection with CPU or digital input board error 2 Connection terminals 2 1 ...

Страница 31: ... 309 3 7 1 Wiring diagram Terminal Function 1 DI 1 2 DI 2 3 DI 3 4 DI 4 5 DI 5 6 DI 6 7 DI 7 8 DI 8 G1 COM 9 DI9 10 DI10 11 DI11 12 DI12 13 DI13 14 DI14 15 DI15 16 DI16 G2 COM 17 DI17 18 DI18 19 DI19 20 DI20 21 DI21 22 DI22 23 DI23 24 DI24 G3 COM Digital input board wiring diagram ...

Страница 32: ... No groups of 8 channels share a common ground Signaling circuit voltage Input voltage range DI 11 Input voltage range DI 21 Input voltage range DI 31 Input voltage range DI 41 16 30 V DC 34 72 V DC 80 150 V DC 150 264 V DC Increased insulation resistance acc to IEC 60255 5 Power frequency withstand voltage Surge voltage 2 5 kV 50 Hz 1 min 4 4 kV 1 2 50 μs 0 5 J Power consumption for binary input ...

Страница 33: ...he processing of up to 24 digital outputs Digital output board front and side view No Explanation Function LED indication 1 LED indicators for each digital output Digital output status LED is ON output is active LED is OFF output is inactive ALL LEDS are blinking together no connection with CPU or digital output board error 2 Connection terminals 2 1 ...

Страница 34: ...4 of 309 3 8 1 Wiring diagram Digital output board wiring diagram Function Function 1 DO1 2 DO2 3 DO3 4 DO4 5 DO5 6 DO6 7 DO7 8 DO8 G1 COM 9 DO9 10 DO10 11 DO11 12 DO12 13 DO13 14 DO14 15 DO15 16 DO16 G2 COM 17 DO17 18 DO18 19 DO19 20 DO20 21 DO21 22 DO22 23 DO23 24 DO24 G3 COM ...

Страница 35: ...nother Yes optocoupler Yes Switching capacity AC1 AC15 AC3 DC1 DC13 16 A 250 V AC 3 A 120 V 1 5 A 240 V B300 750 W single phase motor 16 A 24 V DC see Fig 3 0 22 A 120 V 0 1 A 250 V R300 Voltage control circuit of the relay rated value operating range 12 V DC 3 220 V Increased insulation resistance acc to IEC 60255 5 Power frequency withstand voltage Surge voltage 2 5 kV 50 Hz 1 min 4 4 kV 1 2 50 ...

Страница 36: ...Analogue Input Module AI 31 The AI 31 analogue input module serves for the processing of up to twelve analogues current or voltage input signals Note Measuring current or voltage can be selected for each input separately by the internal jumper position Analogue input board front and side view 2 1 ...

Страница 37: ...V to 10 V measuring Analogue input switch position No Explanation Function LED indication 1 LED indicators for each analogue input Analogue input status LED is OFF normal measured value LED is ON measured value is under or over range ALL LEDS are blinking together no connection with CPU or analog input board error 2 Connection terminals ...

Страница 38: ...3 Analogue input 3 4 Analogue input 4 4 Analogue input 4 5 Analogue input 5 5 Analogue input 5 6 Analogue input 6 6 Analogue input 6 7 Analogue input 7 7 Analogue input 7 8 Analogue input 8 8 Analogue input 8 9 Analogue input 9 9 Analogue input 9 10 Analogue input 10 10 Analogue input 10 11 Analogue input 11 11 Analogue input 11 12 Analogue input 12 12 Analogue input 12 G1 Ground G2 Ground Analogu...

Страница 39: ...nic isolation from system electronics of the channels from one another Yes optocoupler Yes Measuring ranges standard fitting Configurable via switch Resolution in all ranges 16 bit Acquisition cycle max 100 ms Increased insulation resistance acc to IEC 60255 5 Power frequency withstand voltage Surge voltage 2 5 kV 50 Hz 1 min 4 4 kV 1 2 50 μs 0 5 J ...

Страница 40: ...ocessing of up to 6 current transformers inputs and up to 6 voltage transformers inputs Measurement input board front and side view No Explanation Function LED indication 1 LED indicators for each input Measurement input status LED is OFF normal measured value LED is ON measured value is under or over range ALL LEDS are blinking together no connection with CPU or analog input board error 2 Connect...

Страница 41: ... input N3 4 V1 voltage input V1 4 V1 voltage input 01 5 V2 voltage input V2 5 V2 voltage input 02 6 V3 voltage input V3 6 V3 voltage input 03 7 I4 Current input L4 7 I4 Current input N4 8 I5 Current input L5 8 I5 Current input N5 9 I6 Current input L6 9 I6 Current input N6 10 V4 voltage input V4 10 V4 voltage input 04 11 V5 voltage input V5 11 V5 voltage input 05 12 V6 voltage input V6 12 V6 volta...

Страница 42: ... of inputs 12 Galvanic isolation from system electronics of the channels from one another Yes optocoupler Yes Measuring ranges standard fitting Resolution in all ranges 16 bit Acquisition cycle max 100 ms Increased insulation resistance acc to IEC 60255 5 Power frequency withstand voltage Surge voltage 2 5 kV 50 Hz 1 min 4 4 kV 1 2 50 μs 0 5 J ...

Страница 43: ... ports to one RS 422 RS 485 serial port The ST 61 uses a separate LED emitter and photo detector operating at an 820 nm wavelength Connections to the emitter and detector are done with ST type connectors Almost any multimode glass fiber size can be used including 50 125 µm 62 5 125 µm 100 140 µm and 200 µm Two fibers are required between the two devices one each direction of data Glass fiber optic...

Страница 44: ... assignment for RS422 485 Pin Designation RS 422 RS 485 4 wire RS 485 2 wire 1 Not used Not used Not used 2 RX RB DB 2 3 pins should be linked together 3 TX TB DB 4 GND GND GND 5 RX RA DA 5 6 pins should be linked together 6 TX TA DA 7 Not used Not used Not used 8 Not used Not used Not used RJ45 connector a ST 61 side b Cable side ...

Страница 45: ...d to provide communication from six plastic fiber optic ports to one RS 422 RS 485 serial port The PL 61 uses a separate LED emitter and photo detector operating at an 660 nm wavelength Connections to the emitter and detector are done with PL type connectors Two fibers are required between the two devices one each direction of data Glass fiber optic board ...

Страница 46: ...n assignment for RS422 485 Pin Designation RS 422 RS 485 4 wire RS 485 2 wire 1 Not used Not used Not used 2 RX RB DB 2 3 pins should be linked together 3 TX TB DB 4 GND GND GND 5 RX RA DA 5 6 pins should be linked together 6 TX TA DA 7 Not used Not used Not used 8 Not used Not used Not used RJ45 connector b PL 61 side b Cable side ...

Страница 47: ... 61 CK 61 The CD 61 module is for RS 232 communication The CK 61 module is for RS 485 communication The CD 61 CK 61 is designed to provide communication from six RS 232 485 ports to one RS 232 485 serial port The serial communication interfaces RS 232 or RS 485 are designed as 8 pole RJ45 connector Com port boards CK 61 CD 61 ...

Страница 48: ...B 3 TX TB 4 Not used GND 5 GND RA 6 Not used TA 7 Not used Not used 8 Not used Not used RJ45 connector The status of each communication interface is shown via the six software controlled LEDs that are installed on the top of the card The yellow LED is activated during transmission of data in the transmission direction The green LED is activated during transmission of data in the receive direction ...

Страница 49: ...le LAN 21 Page 49 of 309 3 14 Ethernet communication module LAN 21 The Ethernet communication module LAN 21 is designed to provide 2 Ethernet type ports The ethernet 10 100 base TX communication interface is designed as 8 pole RJ45 connector Ethernet communication module LAN 21 ...

Страница 50: ...rection Pin Designation 1 TX 2 TX 3 RX 4 BI_DC 5 BI_DC 6 RX 7 BI_DD 8 BI_DD RJ45 connector 3 15 Installation of System Housing Multi frame systems RTUs are usually installed in a cabinet horizontal installation A station s height is 6 height units U i e 266 mm It is important to leave one U free between two stations in order to allow for sufficient ventilation Another possibility is to install the...

Страница 51: ...41 auxiliary voltage 220V DC 4 4 PS 51 auxiliary voltage 48V DC 5 5 Without redundant power supply 0 0 CPU module CPU 41 with 4 Ethernet RJ45 12 RS485 Serial links 5 CPU 42 with 4 Ethernet RJ45 4 RS232 Serial links 8 RS485 Serial links 6 CPU 43 with 4 Ethernet RJ45 8 RS232 Serial links 4 RS485 Serial links 7 CPU 44 with 4 Ethernet RJ45 12 RS232 Serial links 8 Inputs outputs boards DI 11 24 x DI op...

Страница 52: ...board 0 0 0 0 0 0 0 0 0 0 0 0 Communications IEC 60870 5 101 serial communication protocol to upper or lower levels 1 IEC 60870 5 104 ethernet based communication protocol to upper or lower levels 1 IEC 61850 ethernet based communication protocol to upper or lower levels 1 IEC 60870 5 103 legacy IED communication protocol to lower levels 1 DNP3 Modbus SPA Bus RP 570 1 Without communication protoco...

Страница 53: ...3 points Connectors 9 points Connectors 12 points Enilit RTU configuration tool always included in order ISaGRAF software PLC Editor Manuals Technical and Operation guides in English Technical and Operation guides in German Technical and Operation guides in Russian Technical and Operation guides in Lithuanian ...

Страница 54: ... 1 1 DI 21 24 x DI operating voltage 48 VDC 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 DI 31 24 x DI operating voltage 110 VDC 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 DI 41 24 x DI operating voltage 220 VDC 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 DO 31 24 x DO 5 5 5 5 5 5 5 5 5 5 5 5 5 5 5 5 AI 31 12 x AI 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 AC 31 12 x AC A A A A A A A A A A A A A A A A CD 61 6 x RS232 7 7 7 7 7 7 7 7 7 7 7 7 7 ...

Страница 55: ... relationships between master and slave protocols Also you can define relationships between hardware connections and slave protocols Supported protocols are control direction o IEC 60870 5 101 o IEC 60870 5 103 o IEC 60870 5 104 o DNP3 serial o DNP3 TCP o IEC 61850 o Modbus RTU ASCII o Modbus TCP o SPA BUS o RP 570 o ICP DCON monitor direction o IEC 60870 5 101 o IEC 60870 5 104 o DNP3 serial o DN...

Страница 56: ...s database Not less than 1000 events second Up to 96 serial slave devices 4 3 Licensing Enilit RTU CMS software is included by default Linux or Windows 7 Embedded operating system license is included in the Enilit RTU price IsaGRAF license can be added by the request Enilit RTU Substation and SCADA system concept ...

Страница 57: ...er protocols points Then you create points in Slave protocols and connect it to the tags which you have created before And now you will have some points from controlled device going to the SCADA or some other controlling device One of the main features of Enilit CMS is that the adding or making changes in protocols like adding points or tag manager can be done on line so you don t need to upload c...

Страница 58: ...s window Click to open Redundancy management window button is visible only if Redundancy is used Click to open Time management window Click to open Console window Click to save configuration Click to close Enilit RTU software The following figure shows the standard perspective of the program window of Enilit RTU CMS The display and work area is subdivided into several views As is usual with all Wi...

Страница 59: ...s window in the right application side When clicking on tree item with the right mouse button a corresponding popup menu enables access to further functions available for this tree item Right side Settings table When clicking on tree item in left side of window the corresponding Settings table is opened enabling the user to view and edit the settings Help section Help section is located in the bot...

Страница 60: ...menu If you use menu item Create New Communication Port you will see following figure Then you can select protocol The new tree item will appear in the communications tree Popup menu is fast and simple way for creating RTU communications The following window shows Select New Master protocol window Select New Master protocol window The following window shows Select New Slave protocol window ...

Страница 61: ...Enilit RTU User Manual 16 09 Enilit RTU software User interface Page 61 of 309 Select New Slave protocol window TAG Manager window ...

Страница 62: ...rator you can change some initial system parameters regarding with CPU Serial ports Ethernet ports OPC Isagraf Redundancy Service Graphics Logs Debug and other Configurator window File menu Menu item Description Log On Log on as a user Log Off Log off currently logged user Save Ctrl S Save configuration Exit Exit Configurator ...

Страница 63: ...Description Enilit Users Users must belong to this group if they want to work with Enilit CMS Enilit Allow Control Allows users to simulate controls in Enilit CMS Enilit Allow Edit Allows users to edit Enilit CMS configuration 4 5 2 Create user groups First step to start working with Enilit CMS software is to Create Enilit user groups from Enilit Configurator To create Enilit user groups in Window...

Страница 64: ...econd step open Computer Management tool from Control Panel Administrative Tools Go to Local Users and Groups Create new user in Users folder like shown in following figure Computer management window In the General tab of Enilit User properties uncheck User must change password at next logon checkbox and check Password never expires checkbox ...

Страница 65: ...Enilit RTU User Manual 16 09 Enilit RTU software Configurator Page 65 of 309 Enilit user password options After that open created user properties window and click Member Of tab then Add new Groups ...

Страница 66: ...Enilit RTU User Manual 16 09 Enilit RTU software Configurator Page 66 of 309 User properties window Click Advanced Select group window Select all Enilit user groups and click OK ...

Страница 67: ... Member Of tab in the last step Click OK and you will have user with the rights to log in configure and control Enilit Configurator Enilit Project Manager and Enilit CMS User with all three groups will have full access to the Enilit CMS software but if you need users with different access level you can add only Enilit Users or Enilit Allow Edit ...

Страница 68: ...uthenticate himself with own user name and password Log on window Without user registration you can only review configuration but not be able to do anything else Even without user log on you can t manually start stop RTU with current configuration After user log on you will see in the Main window user name which have logged on The following figure shows that logged on user Enilit Logged on user ...

Страница 69: ...w Menu item Description Name Project name Description Additional project description Startup If yes then project is startup project Directory Projects directory read only Change possible only in Projects xml file in Enilit CMS directory Configuration version Version of project configuration Created on RTU of computer name on which project is created Created user User who created the project Creati...

Страница 70: ...escription Additional description Additional description IP IP address to connect to RTU 127 0 0 1 IP2 Second IP address to connect to RTU Empty Enabled Enables Redundancy No Redundant RTU Name Redundant RTU name Empty Redundant RTU IP IP address of redundant RTU Empty Redundant RTU IP2 Second IP address of redundant RTU Empty File menu Menu item Description Log On Log on as a user ...

Страница 71: ...he selected branch Add RTU Add RTU to the selected project Delete Delete branch project or RTU Project menu Menu item Description Start project Start Enilit RTU CMS with the selected project Edit RTU configuration Edit Enilit RTU configuration with CMS Show Project directory Opens project directory Go to startup project Selects startup RTU in the projects tree Check projects Validates projects Imp...

Страница 72: ...ation directory Directory where to save imported project Project file Ezip file of importing project New project name New imported project name 4 7 3 Export project With the Export project feature you can export project to external network or other storage for RTU configuration backup Export project window Menu item Description Destination directory Where to save exported project Project name File...

Страница 73: ...ses Enilit RTU by default has four Network adapters Network adapters are independent and each has own MAC address In that case all Network adapters can have different IP address with a different gateway You can choose also Static IP address or obtain it by DHCP To configure a Static IP address for one of four Enilit RTU network adapters work through the following steps 1 Launch Control Panel 2 Cli...

Страница 74: ...click on the targeted network adapter icon and select Properties 6 Select Internet Protocol Version 4 TCP IPv4 and click on Properties 7 Select Use the following IP address and enter the following IP address and subnet mask IP address 172 17 217 130 Subnet mask 255 255 255 0 Gateway 172 17 217 254 ...

Страница 75: ...it RTU is installed UltraVNC server or similar software Remotely you can do everything what you can do locally Enilit RTU Self control and Diagnosis change configuration import export project configure Windows OS Remote Desktop is not enabled by default You must specifically enable it to allow remote access to the Enilit RTU When it is enabled configured member of the Administrators group can conn...

Страница 76: ...ctions only from Windows 7 or later computers and computers with secure network authentication 5 Click Select Users This displays the Remote Desktop Users dialog box 6 To grant Remote Desktop access to a user click Add This opens the Select Users dialog box In the Select Users dialog box click Locations to select the computer or domain in which the users you want to work with are located Type the ...

Страница 77: ...ain configuration Page 77 of 309 7 Click OK twice when you have finished 4 8 2 2 To connect to Enilit RTU 1 Go to Start All Programs Accessories Remote Desktop Connection 2 Enter the Computer Name or IP address of the Enilit RTU you wish to connect to ...

Страница 78: ...ions Here you can save the connection profile adjust display properties run specified programs upon connection adjust connection bandwidth etc For more information on specific tabs click on Help 4 Click on Connect 5 Enter your log in credentials of a user account on the Enilit RTU that is allowed to do a remote desktop connection ...

Страница 79: ...Enilit RTU User Manual 16 09 Enilit RTU software Main configuration Page 79 of 309 Default username EnilitRemote Default password Enilit123 ...

Страница 80: ...ual If chose automatic the RTU will check it s slots and configure the slot according the founded board After that RTU creates Hardware points with default names Hardware Auto configuration Another possibility is to create hardware configuration manually In the Card Slots you can configure which module is mounted on the particular slot Hardware Tags enables you to configure signal measurement comm...

Страница 81: ...tation 1 RTU Extended Does RTU contain extension rack No DI Slot Default DI slot name created in Hardware Points branch Slot DI DO Slot Default DO slot name created in Hardware Points branch Slot DO AI Slot Default AI slot name created in Hardware Points branch Slot AI SPS Name Default SPS name created in Hardware Points branch DI MES Name Default MES name created in Hardware Points branch AI SPC ...

Страница 82: ... Current 20 20 mA Voltage 10 10 V Voltage 5 5 V Voltage 2 5 2 5 V Voltage 1 25 1 25 V Current 4 20 mA Event count Number of event to keep in one file Range of Values 100 100000 1000 History days Number of days to keep files in history Range of Values 1 1000 100 Max files size Maximum log files size Range of Values 1 100 Mb 10 UTC time stamp Allows to choose the time stamp used in log files Values ...

Страница 83: ...nge of Values Not used PS 11 110 V AC PS 21 230 V AC PS 31 110 V DC PS 41 220 V DC PS 51 48 V DC Not used Description Free user description or comment 4 9 2 CPU CPU parameters Field name Description Default value Type Configuration allows you to set the CPU type Range of Values CPU 31 CPU 32 CPU 33 CPU 34 CPU 41 CPU 42 CPU 43 CPU 44 CPU 31 CPU enabled CPU enabled on system startup Yes ...

Страница 84: ...link rate no CPU Led Error2 blink rate in 100 ms when there is no communication with CPU Range of Values 0 255 0 means always OFF 255 Led Run Blink rate no CPU Led Run blink rate in 100 ms when there is no communication with CPU Range of Values 0 255 0 means always OFF 0 Time out with CPU Communication time out with CPU in 100 ms Time when no activity got from Main CPU Range of Values 10 255 10 Wa...

Страница 85: ...slot The type of the module is written on the top of the module front panel RTU Slots tree Slot parameters pane Field name Description Default value Slot number Number of RTU slot Only for internal use For example 10 21 Depends on slot number Card enabled Card is enabled Yes Card Type Choose type of module Values DI 31 Digital Input DO 31 Digital Output AI 31 Analog Input ST 61 Fiber optics Empty ...

Страница 86: ...iption Default value Digital input number Number of digital input Only for internal use For example 1 24 Depends on digital input Debouncing check time Debouncing checking time in milliseconds If the value is 0 then debouncing filter is not used Range of Values 0 255 ms 5 Filtering time Filter checking time in milliseconds If value is 0 then filtering is not used Range of Values 0 255 ms 1 Togglin...

Страница 87: ...cription Default value Digital output number Number of digital output Only for internal use For example 1 24 Depends on digital output 4 9 4 3 Analog input Analog input parameters Field name Description Default value Analog input number Number of analog input Only for internal use For example 1 12 Depends on analog input Analog input type Configuration allows you to set the analog input type to th...

Страница 88: ...10 10 V Voltage 5 5 V Voltage 2 5 2 5 V Voltage 1 25 1 25 V Maximum value Here the maximum raw value of analog input for the conversation to normalized measured value Range of Values 99999999999999 99999999999999 100 Minimum value Here the minimum raw value of analog input for the conversation to normalized measured value Range of Values 99999999999999 99999999999999 0 4 9 4 4 Fiber optics Fiber o...

Страница 89: ...or off fiber optic port Values No Yes No In the following window Baud rate of COM Parameters for one CHIP cards should be the same like communication port you connect from CPU to ST 61 board COM Parameters for one CHIP cards Field name Description Default value Baud rate Serial port baud rate Range of values 110 921600 19200 Data bits Serial port data bits Values 7 8 bits 8 Stop bits Serial port s...

Страница 90: ...igital inputs analog inputs and command outputs The following figure shows popup menu of Hardware points With it you can create Hardware Points tree After that you can create tags like single point status double point status multi point status single commands double commands multi point commands measurements and counter single counter doubles Popup menu of Hardware points ...

Страница 91: ...pends on tag Name Hardware tag name For example IED fault Length 1 255 Item SPS1 DI input Allows connecting hardware tag to binary input For example Slot 13 DI 01 Not set OFF delay Delay on stable state after which the hardware tag is set to OFF 100 ms Range of Values 0 1000 0 ON delay Delay on stable state after which the hardware tag is set to ON 100 ms Range of Values 0 1000 0 Time tagging star...

Страница 92: ...Hardware Points tree and double point parameters Field name Description Default value ID Identification number of hardware tag Only for internal use Range of Values 1 65535 Depends on tag Name Hardware tag name For example Item DPS1 Length 1 255 Item DPS1 DI input OFF Allows connecting hardware tag to binary input For example Slot 13 DI 04 Not set DI input ON Allows connecting hardware tag to bina...

Страница 93: ...Delay on stable state after which the hardware tag is set to ON 100 ms Range of Values 0 1000 0 Indeterminate 11 delay Delay on stable state after which the hardware tag is set to Undefined both inputs are active 100 ms Range of Values 0 1000 0 Time tagging start Type of tag timestamp Event can be with start or end of filtering timestamp Range of Values Yes No Yes Inverse Invert of hardware tag Ra...

Страница 94: ...tree and multipoint status parameters Field name Description Default value ID Identification number of hardware tag Only for internal use Range of Values 1 65535 Depends on tag Name Hardware tag name For example Item MPS1 Length 1 255 Item MPS1 Type Select type of multipoint status Range of Values Binary BCD 1 from N bits Binary ...

Страница 95: ...ot 13 DI 04 Not set Stable delay Delay on stable state before changing tags value in 100 ms Range of Values 0 1000 0 Time tagging start Type of tag timestamp Event can be with start or end of filtering timestamp Range of Values Yes No Yes Offset Offset value for conversion Range of Values 0 100 0 Scale Scale value for conversion Range of Values 0 100 1 Tag Name Hardware tag connection to TAG Manag...

Страница 96: ...fined type it will be overridden with this type of pulse Range of Values Pulse short Pulse long Persistent Pulse short ID Identification number of hardware tag Only for internal use Range of Values 1 65535 Depends on tag Name Hardware tag name For example Item SPC1 Length 1 255 Item SPC1 DO output Allows connecting hardware tag to digital output For example Slot 11 DO 01 Not set Inverse Invert of ...

Страница 97: ...ort pulse length in 10 milliseconds Range of Values 10 6000 10 Type If command got with unknown or undefined type it will be overridden with this type of pulse Range of Values Pulse short Pulse long Persistent Pulse short ID Identification number of hardware tag Only for internal use Range of Values 1 65535 Depends on tag Name Hardware tag name For example Item DPC1 Length 1 255 Item DPC1 DO outpu...

Страница 98: ...put For example Slot 11 DO 05 Not set Inverse Invert of hardware tag Range of Values Yes No No Tag Name Hardware tag connection to TAG Manager TAG Manager tag name 4 9 5 6 Multipoint command Hardware Points tree and multipoint command parameters Field name Description Default value Long pulse Long pulse length in seconds Range of Values 1 600 1 ...

Страница 99: ...l use Range of Values 1 65535 Depends on tag Name Hardware tag name For example Item MPC1 Length 1 255 Item MPC1 Type Select type of multipoint command Range of Values Binary BCD 1 from N bits Gray Binary DO Output bit01 DO Output bit16 Allows connecting one of multipoint command item to binary output For example Slot 13 DO 04 Not set Offset1 Offset value for conversion Range of Values 0 100 0 Off...

Страница 100: ... tag Name Hardware tag name For example Voltage U1 Length 1 255 Item MV1 AI input Allows connecting hardware tag to analog input For example Slot 15 AI 01 Not set Deadband type Type of measurement dead band Range of Values Simple Integrated Type 1 Integrated Type 2 Simple Deadband value Change of measurement is sent if the change is more than this deadband value If the value is 0 then all changes ...

Страница 101: ...adratic Linear Tag Name Hardware tag connection to TAG Manager TAG Manager tag name 4 9 5 8 Single counter parameters Hardware Tags tree and single counter parameters Field name Description Default value Auto reset Automatically reset counter value after accumulation period Values Yes No Yes Period Period for which accumulation should be proceeded Range of values 1 minute 12 hours 1 hour Send type...

Страница 102: ...tag Name Hardware tag name For example Counter C1 Length 1 255 Item SCT1 DI input Allows connecting hardware tag to digital input For example Slot 12DI 01 Not set Tag Name Hardware tag connection to TAG Manager TAG Manager tag name 4 9 5 9 Double counter parameters Hardware Tags tree and double counter parameters Field name Description Default value Auto reset Automatically reset counter value aft...

Страница 103: ... Yes Valid delay Stable ON delay before increasing tags value Range of Values 0 1000 ms 10 ID Identification number of hardware tag Only for internal use Range of Values 1 65535 Depends on tag Name Hardware tag name For example Counter C1 Length 1 255 Item DCT1 DI input OFF Allows connecting hardware tag to digital input DI input used for OFF counting For example Slot 12DI 01 Not set DI input ON A...

Страница 104: ... protocol New IEC 103 master protocol Enabled on start Port enabled on system startup Values No Yes No Com port Communication port number Not assigned Baud rate Serial port baud rate Range of values 110 921600 9600 Data bits Serial port data bits Values 7 8 bits 8 Stop bits Serial port stop bits Values 1 1 5 2 bits 1 Parity Serial port parity Values None Odd Even Mark Space None RS 485 Mode If use...

Страница 105: ...ange of values 1 600 seconds 10 Next request Wait time before sending next request Range of values 0 1000 ms 50 Port Monitor Show port monitor on system startup Values No Yes No Log raw data Log raw communication data Values No Yes Yes 4 10 1 2 Data link layer parameters Field name Description Default value ID For internal use Data link name Data link layer name For example Feeder 1 New Data Link ...

Страница 106: ...vents 0 request until no Class1 events or Class1 timer expires Range of values 0 255 1 Class1 Time How long request the same data link layer if there is Class1 events 0 time is not checked Range of values 0 255000 ms 0 Reconnect How often try to reconnect to communication port if there was error Range of values 1 600 seconds 10 Answer timeout Wait timeout of response from controlled device Range o...

Страница 107: ...DFC bit Values No Yes No Log header Log data link header Values No Yes Yes Log Answer Timeout Log data link answer timeouts to system log Values Never First time Always First Time 4 10 1 3 Application layer parameters Field name Description Default value ID For internal use Application layer name Application layer name For example Feeder 1 New Application Enabled on start Enables or disables appli...

Страница 108: ...ynchronization Cycle time of clock synchronization to the controlled device Range of values 1 86400 seconds 600 Day of Week In request with timestamp use Day of Week bit Values No Yes No Summer time In request with timestamp use Summer time bit Values No Yes No Allow synchronization Yes synchronize always No synchronize only if RTU internal clock is synchronized Yes UTC time In requests and respon...

Страница 109: ...doesn t include in General Interrogation Following figure shows points popup menu which you can run with right mouse button You can Add Status point Edit Status point Delete Status point Select All status points or commands Also you can Connect to Tag or Remove connection to the Tag Remove connection to source is possible from TAG Manager All menu items have keyboard shortcuts They will simplify a...

Страница 110: ...rement Type 3 and Type 9 Measurement Type 4 Time Tagged Message Type 1 and Type 2 Double Generic Command Time Tagged Message Type 1 and Type 2 Function Here the function type of the employed protection equipment can be defined The following paragraph lists the meaning of some of the function types 128 Distance protection 160 Overcurrent time protection 176 Transformer differential protection 192 L...

Страница 111: ...System functions 16 31 Status 32 47 Monitoring 48 63 Earth faults 64 127 Short circuits 128 143 Automatic reclosing 144 159 Measured values 240 255 Generic functions Ranges for information numbers in control direction 0 15 System functions 16 31 General commands 240 255 Generic functions For a complete list of all information numbers please refer to the IEC 60870 5 103 norm Range of values 0 255 1...

Страница 112: ...timer is set to not zero it will be delayed for set time and if some data change occurs it will be ignored Range of values 0 3600 seconds 0 not used 0 Timer ON This parameter is relevant only if IEC Type is Time Tagged Message Type 1 and Type 2 Double If received value is ON and timer is set to not zero it will be delayed for set time and if some data change occurs it will be ignored Range of valu...

Страница 113: ...ox Values Checked Unchecked Unchecked Invert Inversion of signals Type 1 and Type 2 Values Checked Unchecked Unchecked Offset 1 New value Old value Offset1 Scale Offset2 0 Scale 1 Offset 2 0 Following figure shows the list of status points and commands You can use double click to edit data or command point You can select many points as well and then edit it with keyboard shortcut Ctrl E List of st...

Страница 114: ...e employed protection equipment can be defined The following paragraph lists the meaning of some of the function types For a complete list of all function types please refer to the IEC 60870 5 103 norm Range of values 0 255 1 Function Increment Used only for configuration After adding new command function will be automatically incremented by set value 0 Information Here the information number can ...

Страница 115: ...onse from controlled device 4 10 1 5 Measured information coefficient calculation Sometimes it is hard to understand how Scale parameter is calculated to get real value of measurement Most of relays for measurement transmission use coefficients 1 2 or 2 4 It is according to IEC 60870 103 standard We will name it COF According IEC 60870 103 standard measurements are transmitted in range from 4096 t...

Страница 116: ...l New IEC 101 master protocol Enabled on start Port enabled on system startup Values No Yes No Listen Mode Communication port will only receive data but will not make any transmits Use only for testing proposes Values No Yes No Com port Communication port number Not assigned Baud rate Serial port baud rate Range of values 110 921600 9600 Data bits Serial port data bits Values 7 8 8 Stop bits Seria...

Страница 117: ...wire Reconnect How often try to connect to communication port if there was error Range of values 1 600 seconds 10 Next request Wait time before sending next request Range of values 0 1000 ms 50 Data link address size Data link layer address size in bytes Range of values 0 2 bytes 1 Port monitor Show port monitor on system startup Values No Yes No Log raw data Log raw communication data Values No Y...

Страница 118: ...f values 1 2 bytes 1 CAA size Common address size Range of values 1 2 bytes 2 Frame size Maximum frame length Range of values 50 255 bytes 255 Broken link Number of retries to determine if the connection is broken Range of values 1 10 3 Priority Request data every cycle Only relevant if more than one data link layer exists Range of values 1 255 1 Class1 Count How many times request the same data l...

Страница 119: ...r disables E5 response from controlled device Values No Yes Yes Use Status link Enables or disables use Status of link frame before Reset Link is sent Values No Yes Yes User Data with confirm Sends User Data with confirmation request Values No Yes Yes Log header Log data link header Values No Yes Yes Log Answer Timeout Log data link answer timeouts to system log Values Never First time Always Firs...

Страница 120: ...f 309 4 10 2 3 Application layer parameters Field name Description Default value ID For internal use Application name Application link layer name For example Measurements data controller New Application Enabled on start Enables or disables application on start Values No Yes No ...

Страница 121: ...ed Auto add Automatically adds all data points received after General Interrogation to the controlled device Values No Yes Yes Allow same IOA Allow to have same information object address for status and command points Values No Yes No Cyclic start Yes next cyclic operation time is calculated at the end of operation No next cyclic operation time is calculated at the start of operation Values No Yes...

Страница 122: ...lues 1 3600 seconds 60 Reconnect If application layer is not connected how often to send station interrogation command Range of values 1 3600 seconds 10 Interrogation general Cycle time of General Interrogation to the controlled device Range of values 1 86400 seconds 3600 Interrogation group 1 16 Cycle time of Group Interrogation to the controlled device Range of values 0 86400 seconds 0 disabled ...

Страница 123: ...s 60 Counter Interrogation general Cycle time of Counter Interrogation to the controlled device Range of values 0 86400 seconds 0 disabled Counter Interrogation Counter Interrogation group 1 4 Cycle time of Counter Interrogation group to the controlled device Range of values 0 86400 seconds 0 disabled Counter Interrogation Timeout CS Timeout for clock synchronization Range of values 1 3600 seconds...

Страница 124: ...uisition delay before sending clock synchronization C_CD_NA_1 Values No Yes No Timeout CD Timeout for delay acquisition Range of values 1 3600 seconds 10 Use for test C_TS_TA_1 Use test frame format C_TS_TA_1 Values No Yes Yes Test Cycle time of test frame This parameter is not used when Is test frame used are set to No Range of values 1 86400 seconds 0 disabled FBP Fixed test bit pattern Range of...

Страница 125: ...5 bytes 0 Log header Log application layer header Values No Yes Yes Log IO Log information objects Values No Yes Yes Log IO not configured Log not configured information objects Values No Yes Yes 4 10 2 4 Points Following figure shows Status points of IEC 60870 5 101 protocol IEC 60870 5 101 Status points table IEC 60870 5 101 Command points table Following figure shows how to add new data points ...

Страница 126: ...EC 60870 5 101 Field name Description Default value IEC Type IEC 60870 5 101 data type Values Single point Double point Step position Bit string of 32 bits Measured value normalized value Measured value scaled value Measured value short floating point value Single Point IOA Here the information address can be specified Range of information address depends from Application layer parameter Informati...

Страница 127: ...and Double command Regulating step command Setpoint normalized command Setpoint scaled command Setpoint short float command Bitstring command Single Command IOA Here the information address can be specified Range of information address depends from Application layer parameter Information object address length Range of values 0 16777215 1 IOA Increment After adding new point IOA will be automatical...

Страница 128: ...EC 104 master 172 29 37 113 New IEC 104 master protocol Enabled on start Enables or disables communication port on start Values No Yes No Ethernet port Which Ethernet port to use for connection to server Values All ETH ETH1 ETH2 ETH3 ETH4 All ETH Server name or IP Name or IPv4 address of the host 127 0 0 1 TCP port TCP port Range of values 1 65535 2404 Redundancy enabled Enables or disables redund...

Страница 129: ...cation Range of values 0 2147483647 milliseconds 0 disabled 10000 TCP No delay TCP No delay disables the Nagle Algorithm Values No Yes No Connect Timeout How long to wait for connection establishment Range of value 1 255 seconds 30 Reconnect If the connection is broken cycle time of reconnection Range of values 1 600 seconds 10 Next request Wait time before sending next request Range of values 0 2...

Страница 130: ... No Yes No T1 Acknowledgement time out 1 Range of values 1 600 seconds 15 T2 Acknowledgement time out 2 Range of values 1 600 seconds 10 T3 Connection test timeout Range of values 1 600 seconds 20 k Maximum number of unacknowledgments ADPUs Range of values 1 32 767 12 w Maximum number of received ADPUs for acknowledgments Range of values 1 32 767 8 No frame I Change behavior of I frame Values Not ...

Страница 131: ...of values 1 2 bytes 2 Cause of transmission size Cause of transmission size Range of values 1 2 bytes 2 Frame size Maximum frame size All start stop checksum and other bytes are included Range of values 50 255 bytes 255 Log APCI Log Application Protocol Control Information Values No Yes Yes 4 10 3 3 Application layer parameters ...

Страница 132: ...cture Object address structure shows in what format information object address is entered in configuration Range of values Unstructured Structured 8 8 8 Structured 8 16 Structured 16 8 Structured 8 8 Unstructured Auto add Automatically adds all data points received after General Interrogation to the controlled device Values No Yes Yes Allow same IOA Allow to have same information object address fo...

Страница 133: ...ct If application layer is not connected how often to send station interrogation command Range of values 1 3600 seconds 10 Status Point not topical Point will be set to not topical state if it was not found in general interrogation response list Values No Yes No Interrogation general Cycle time of General Interrogation to the controlled device Range of values 1 86400 seconds 3600 Interrogation gro...

Страница 134: ...ange of values 0 86400 seconds 0 disabled Counter Interrogation Counter Interrogation group 1 4 Cycle time of Counter Interrogation group to the controlled device Range of values 0 86400 seconds 0 disabled Counter Interrogation Timeout CS Timeout for clock synchronization Range of values 1 3600 seconds 10 Allow synchronization Yes synchronize always No synchronize only if RTU internal clock is syn...

Страница 135: ...ame format C_TS_TA_1 Values No Yes Yes Test Cycle time of test frame This parameter is not used when Is test frame used are set to No Range of values 1 86400 seconds 0 disabled FBP Fixed test bit pattern Range of values 0 32768 21930 Timeout TC Timeout for test command Range of values 1 3600 seconds 10 Timeout RP Timeout for reset process Range of values 1 3600 seconds 10 Enabled Enables file tran...

Страница 136: ...objects Values No Yes Yes 4 10 3 4 Points Status points Command points Configuration of IEC 60870 5 104 protocol data and command points are the same like in IEC 60870 5 101 protocol Refer to the paragraph above 4 10 4 IEC 61850 client Enilit RTU supports also IEC 61850 client protocol You can connect IED devices via 61850 protocol standard The main requirement is that you will need SCD Substation...

Страница 137: ... Values No Yes No Client Name Name to use for this client in IEC61850 communication Ethernet port Which Ethernet port to use for connection to server Values All ETH ETH1 ETH2 ETH3 ETH4 All ETH SCD file SCD file of substation You can browse the file with Open file dialog button Values File name and path SCD Enilit CMS saves the file in Projects SCD folder When you select SCD file the main parameter...

Страница 138: ... from IED Name and AP Name Enabled on start IED is enabled on system startup Values No Yes No IED Name IED name in SCD file AP Name Access point name in SCD file ACSE requirements ACSE requirements are used some IEDs do not support disable when necessary Yes Authentication mechanism Authentication mechanism used for connection to IED None Password Password used for connection to IED Release used f...

Страница 139: ...function will be executed at set interval 0 3600 seconds 0 Function not used 1 GetDataSetValues Period If DataSet does not belong to any ReportControl GetDataSetValues function will be executed at set interval 0 3600 seconds 0 function not used 0 Only needed data Start only buffered and unbuffered reports which contain needed data No RPT Reconnect If it was not possible to find or connect to any r...

Страница 140: ...t override this setting with TRUE value General Interrogation is needed for normal communication Yes TrgOps Data Change If SCL file does not set Data Change Bit override this setting with TRUE value Data Change is needed for normal communication Yes TrgOps Quality Change If SCL file does not set Quality Change Bit override this setting with TRUE value Quality Change is needed for normal communicat...

Страница 141: ...uld be used for Buffered Reports Yes BRCB OptFlds EntryID If SCL file does not specify BRCB EntryID try to override this setting with TRUE value It is not mandatory but EntryID should be used for Buffered Reports Yes Select Positive not NULL Yes if received normal security select response is not NULL value it be consider successful for backward compatibility No only received CO_CtrlObjectRef is co...

Страница 142: ...te on connect for GOOSE control blocks No Wildcard Use Wildcard in GetServerDirectory FILE request No Separator Used separator in directory and file names IP in SCL IP Address of IED in SCL configuration file TCP port in SCL TCP port of IED in SCL configuration file IP override If you want to override IP address of IED from SCL file In other cases leave it empty SCL value will be used TCP port ove...

Страница 143: ...og MMS Partially logs MMS communication No Log SCSM Logs SCSM communication Yes ICD not found DA Disable this error if it does not really matters to you No ICD not found DA CtlModel Disable this error if it does not really matters to you No ICD not found DA sboTimeuot Disable this error if it does not really matters to you No ICD not found DA sboClass Disable this error if it does not really matte...

Страница 144: ...sable this error if it does not really matters to you No IEC INT8U overflow Disable this error if it does not really matters to you No IEC sqNum Value overflow Disable this error if it does not really matters to you No IEC Report not started Disable this error if it does not really matters to you No IEC Report TrgOps QualitChange not set Disable this error if it does not really matters to you No O...

Страница 145: ...a point Delete data point Select All data points and Remove connection to Tag Import and Export points Data points popup menu IEC 61850 If you select from the above menu Browse IED file following IED file window will open There you can choose which data point to add to the data points list This is an automated way to create data points IEC 61850 Browse data point you needed and double click to add...

Страница 146: ... manually you will see following dialog box You must enter information like Logical device Logical node Data object Functional constraint Data attribute Time attribute Quality attribute Invert and Value variables Add new data points manually IEC 61850 Field name Description Default value LDevice Logical device name of IEC 61850 structure For example System ...

Страница 147: ...name These Data Names are determined by the standard and are functionally related to the power system purpose For example DPC FC Functional constraints for status ST attributes substituted value SV attributes description DC attributes measurement attributes MX and extended definition EX attributes Values MX ST DA Value Data attribute for Value For example stVal DA Time Data attribute for Time For ...

Страница 148: ... logical node is a named grouping of data and associated services that is logically related to some power system function For example LLN0 DATA Data object name of IEC 61850 structure Each logical node contains one or more elements of Data Each element of data has a unique name These Data Names are determined by the standard and are functionally related to the power system purpose For example DPC ...

Страница 149: ...Interlock check Default Offset 1 New value Old value Offset1 Scale Offset2 0 Scale 1 Offset 2 0 Invert Inversion of command Values No Yes No 4 10 5 Modbus RTU ASCII 4 10 5 1 Communication port parameters Modbus RTU ASCII communication port parameters Field name Description Default value Port name Name of the port and protocol For example COM1 Modbus master New Modbus RTU ASCII master protocol Enab...

Страница 150: ... 1 5 2 1 Parity Serial port parity Values None Odd Even Mark Space None RS 485 mode If used two wires mirrored data check should be used If serial port is RS 232 parameter is not important Values Two wires Four wires Four wires Reconnect How often to try to connect to communication port Range of values 1 600 seconds 10 Next request Wait time before sending next request Range of values 0 1000 ms 10...

Страница 151: ...ess Device link address Range of values 0 255 0 Max PDU Size Maximum PDU size in bytes Range of values 20 260 255 Pooling time The time to pool the data Range of values 0 65535 ms 1000 Answer timeout Time to wait response after request Range of values 10 65535 ms 1000 Broken link Determine the connection as broken after so many retries Range of values 1 255 3 Priority Request data every cycle Only...

Страница 152: ...es Log IO Not configured Log not configured information objects Values No Yes Yes Log Answer Time Out Log application link answer timeouts to system log Values Never First Time Always First Time 4 10 5 3 Points To create new data or command point to the points list you must call popup menu in the Points window With the following menu items you can Add Edit or Delete data points Select all or Remov...

Страница 153: ...Modbus type Modbus data type Values 1 Read coil 2 Read discrete input 3 Read holding register 4 Read input register Read coil Data subtype Available only if Modbus type is Read holding register or Read input register Available data subtypes 16 bits unsigned B1B2 16 bits unsigned B2B1 16 bits signed B1B2 16 bits signed B2B1 32 bits unsigned in one register B1B2B3B4 32 bits unsigned in one register ...

Страница 154: ...1 32 bits float in two register B1B2B3B4 32 bits float in two register B4B3B2B1 Offset 1 New value Old value Offset1 Scale Offset2 0 Scale 1 Offset 2 0 Invert Inversion of status Values No Yes No Data points window Columns between Function and Offset 2 are data point configuration parameters Value Time Quality will show real time data from controlled device Add new command points window Field name...

Страница 155: ...ite multiple register Write single coil Data subtype Available only if Modbus type is Write single register or Write multiple register Available data subtypes 16 bits unsigned B1B2 16 bits unsigned B2B1 16 bits signed B1B2 16 bits signed B2B1 Offset 1 New value Old value Offset1 Scale Offset2 0 Scale 1 Offset 2 0 Invert Inversion of command Values No Yes No Commands window In the Command points wi...

Страница 156: ...Enabled on start Port enabled on system startup Values No Yes No Max transactions Maximum transactions running on the same time 1 16 16 Ethernet port Which Ethernet port to use for connection to server Values All ETH ETH1 ETH2 ETH3 ETH4 All ETH Server Name or IP Server name or IP address Values xxx zzz yyy nnn 127 0 0 1 TCP Port TCP port for TCP IP connection Must be the same port on the server si...

Страница 157: ... wait before new request is transmitted Range of values 1 2000 ms 0 Port Monitor Show port monitor on system startup No Log raw data Enables to log raw data in Port Monitor Values No Yes Yes Log MBAP header Enables to log Modbus application headers in Port Monitor Values No Yes Yes 4 10 6 2 Application layer parameters Modbus TCP application layer parameters Field name Description Default value ID...

Страница 158: ... data every cycle Only relevant if more than one application layer exists Range of values 1 255 1 Reconnect How often try to connect to communication port if there was error 1 3600 seconds 10 Answer timeout Answer timeout when no link 50 30000 milliseconds 1000 Log header Enables to log headers in Port Monitor Values No Yes Yes Log IO Enables to log data and command points information in Port Moni...

Страница 159: ...led on start Port enabled on system startup Values No Yes No Com port Communication port number Range of values COM 1 255 Not assigned Baud rate Serial port baud rate Range of values 110 921600 9600 Data bits Serial port data bits Values 7 8 8 Stop bits Serial port stop bits Values 1 1 5 2 1 Parity Serial port parity Values None Odd Even Mark Space None RS 485 mode If used two wires mirrored data ...

Страница 160: ...s Yes 4 10 7 2 Data link layer parameters DNP3 serial data link layer parameters Field name Description Default value ID For internal use Read only Data Link Name Data link name For example Data link New Data link Enabled on start Port enabled on system startup Values No Yes No Data Link address RTU s master address Range of values 0 65519 1 Outstation address IED slave address Range of values 0 6...

Страница 161: ... broken Range of values 1 255 3 Reconnect If there is no link how often to check for communication Range of values 1 3600 seconds 10 Priority Request data every cycle Only relevant if more than one application layer exists Range of values 1 255 1 Link Status How often to request link status if there was no data Range of values 0 86400 seconds 0 Link status is not used 0 Link Status DFC How often t...

Страница 162: ...t Name Transport layer name For example Transport layer New Transport Enabled on start Port enabled on system startup Values No Yes No Log header Enables to log headers in Port Monitor Values No Yes Yes 4 10 7 4 Application layer parameters DNP3 serial application layer parameters Field name Description Default value ID For internal use Read only Application Name Application layer name For example...

Страница 163: ...mum allowed application layer fragment size Range of values 249 65535 bytes 2024 Class0 Cycle How often to request static objects Range of values 0 86400000 milliseconds 0 only on connect or lost events 10000 Class123 Cycle How often to request event objects Range of values 0 86400000 milliseconds 0 not used 5000 Class1 count How much of event request in Class1 Range of values 0 16777216 0 request...

Страница 164: ...change Assign Analog Input Class assignment on connection for Analog Input Should exist at least one point of such type in configuration Values No change Class0 Class1 Class2 Class3 No change Assign Frozen Analog Input Class assignment on connection for Frozen Analog Input Should exist at least one point of such type in configuration Values No change Class0 Class1 Class2 Class3 No change Assign Co...

Страница 165: ...mand Should exist at least one point of such type in configuration Values No change Class0 Class1 Class2 Class3 No change Assign Analog Output Class assignment on connection for Analog Output Should exist at least one point of such type in configuration Values No change Class0 Class1 Class2 Class3 No change Assign Analog Output Command Class assignment on connection for Analog Output Command Shoul...

Страница 166: ... is set to Yes Values No Yes Yes Class2 Class2 events enabled for unsolicited messages Is relevant only if Unsolicited on connect is set to Yes Values No Yes Yes Class3 Class3 events enabled for unsolicited messages Is relevant only if Unsolicited on connect is set to Yes Values No Yes Yes Allow synchronization Yes allow synchronize always No synchronize only if RTU internal clock is synchronized ...

Страница 167: ...t Float 32 Bit Double bit over two single If master station does not support Double Bit inputs use Binary input Double point type This parameter sets which bit should be first transferred If set No first is OFF if set Yes first is ON No Log DO Log Data Object information Value No Yes Yes Log header Enables to log headers in Port Monitor Values No Yes Yes Log IO Log status and command points inform...

Страница 168: ...int dialog window The parameters which you can specify on DNP3 protocol are proposed in the next table Create new status point window Field name Description Default value Object DNP3 object type Values Binary Input Binary Input Double Double Bit Input Binary Output Analog Input Analog Output Binary Input Index Here the Object index can be specified Range of values 0 2147483647 1 Index Increment Af...

Страница 169: ...tion Range of values 0 2147483647 0 DB Use Use Deadband value to set outstation configuration Value No Yes No Data points window Columns between Object type and Offset 2 are data point configuration parameters Value Time Quality and others will show real time data from controlled device Create new command point window Field name Description Default value Object DNP3 object type Binary Output Comma...

Страница 170: ...ndex Increment After adding new point Index will be automatically incremented by set value 1 Command Type Command Type sent to slave device Values Select Operate Direct Operate Direct Operate No Acknowledgment Write Select Operate Count How many times execute command Range of values 0 255 0 Cancel Command will be executed 1 On Timer Pulse ON timer length Range of values 0 2147483647 milliseconds 0...

Страница 171: ...tart Port enabled on system startup Values No Yes No Ethernet port Which Ethernet port to use for connection to server Values All ETH ETH1 ETH2 ETH3 ETH4 All ETH Server Name or IP Server name or IP address Values xxx zzz yyy nnn 127 0 0 1 TCP Port TCP port Range of values 1 65535 20000 TCP Keep Alive Force TCP activity when idle to long Do not set low values because it will add overhead to communi...

Страница 172: ... log raw data in Port Monitor Values No Yes Yes 4 10 8 2 Data link layer parameters Refer to the DNP3 serial paragraph Data link layer parameters The configuration is very similar 4 10 8 3 Transport layer parameters Refer to the DNP3 serial paragraph Transport layer parameters The configuration is very similar 4 10 8 4 Application layer parameters Refer to the DNP3 serial paragraph Application lay...

Страница 173: ...ameters Simulator port parameters Field name Description Default value ID For internal use only Port name Simulator port name For example Simulator New Simulator master Enabled on start Enables or disables port on start Values No Yes No Port monitor Show port monitor on system startup Values No Yes No 4 10 9 2 Points Simulators Status points window Following figure shows Add new simulation point d...

Страница 174: ...00 Max value Maximum value of simulation data point Range of values 100000 1000000 1000 Step Step size to change simulation data point between Min and Max values Range of values 100000 1000000 10 Change type Data point simulation type Range of values Increment Decrement Random Manual Increment Period Cycle time of data point change Range of values 0 10000 milliseconds 100 If you have configured ma...

Страница 175: ...transmission and Quality of data point Cause of transmission can be Not defined Initialize Periodic Background Spontaneous General Interrogation Requested Control local Control remote Disconnected source Disabled source Deleted source Test mode Calculated Quality values can be in the range Not Init Blocked Not Topical Invalid Substituted Overflow Invalid Time Substituted time Clock failure ...

Страница 176: ...master New RP 570 master protocol Enabled on start Port enabled on system startup Values No Yes No Com port Communication port number Range of values COM 1 255 Not assigned Baud rate Serial port baud rate Range of values 110 921600 9600 Data bits Serial port data bits Values 7 8 8 Stop bits Serial port stop bits Values 1 1 5 2 1 Parity Serial port parity Values None Odd Even Mark Space None RS 485...

Страница 177: ...onization type every 0 86400 s 0 synchronization is disabled 0 Time synchronization short Use short time synchronization type every 0 600000 ms 0 synchronization is disabled 0 Allow synchronization Allow time synchronization always False only if internal clock is synchronized Yes UTC time In request UTC time is used Yes Port monitor Show port monitor on system startup Values No Yes No Log raw data...

Страница 178: ...255 1 Broken link Number of retries to determine if the connection is broken Range of values 1 255 3 Reconnect How often to try to connect to remote device Range of values 1 600 seconds 10 Response timeout Wait timeout of response from controlled device Range of values 50 60000 milliseconds 500 Select Cancel With Value Some master devices do not send value with select and cancel commands In this c...

Страница 179: ... Yes 4 10 10 3 Points Application layer has Points branch You can manage there signals measurements from controlled device and commands to controlled device Following figure shows points popup menu which you can run with right mouse button You can Add data point Edit data point Delete data point Select All data points or commands Also you can Remove connection to the Tag You can Remove connection ...

Страница 180: ...ot support event transmission By default only indications are supported Yes Block No Block number Range of values 0 255 1 Block No Increment After adding new point Block No will be automatically incremented by set value 1 Bit Bit Number Range of values 0 15 0 Bit Increment After adding new point Bit Number will be automatically incremented by set value 1 Double Point Is indication double point No ...

Страница 181: ... RP 570 type of command Range of values CBX Command SPM SetPoint GOM General Output CBX Command Block No Block number Range of values 0 255 1 Block No Increment After adding new point Block No will be automatically incremented by set value 1 Invert Inversion of status Values No Yes No Offset 1 New value Old value Offset1 Scale Offset2 0 Scale 1 Offset 2 0 ...

Страница 182: ...ster New SPA Bus master protocol Port enabled Port enabled on system startup Values No Yes No Com port Communication port number Range of values COM 1 255 Not assigned Baud rate Serial port baud rate Range of values 110 921600 9600 Data bits Serial port data bits Values 7 8 bits 7 Stop bits Serial port stop bits Values 1 1 5 2 bits 1 Parity Serial port parity Values None Odd Even Mark Space Even R...

Страница 183: ...nization to the controlled device Range of values 1 86400 seconds 0 synchronization is disabled 0 Time synchronization short Broadcast Cycle short time of clock synchronization to the controlled device Range of values 1 86400 seconds 0 synchronization is disabled 0 Allow synchronization Yes synchronize always No synchronize only if RTU internal clock is synchronized Yes UTC time Use UTC time in co...

Страница 184: ...n layer name For example Application layer New Application Enabled on start Enables or disables application layer on start Values No Yes No Address Slave address Range of values 1 999 900 is broadcast 1 Frame size Maximum frame length Range of values 48 255 bytes 255 Priority Request data every cycle Only relevant if more than one application layer exists Range of values 1 255 1 Broken link Number...

Страница 185: ... 0 use only while connecting 10 Reset Reset status bit in slave device Set this parameter to No only if the slave device does not support such command Yes Request Alarms How often request alarms Range of values 0 86400 seconds 0 disabled 0 Request Events Request events from slave device Set this parameter to No only if the slave device does not support such command Yes Request Events Count Relevan...

Страница 186: ...ynchronized Yes UTC time Use UTC time in communication Values No Yes Yes Log header Log application layer header Values No Yes Yes Log IO Log information objects Values No Yes Yes Log IO not configured Log not configured information objects Values No Yes Yes 4 10 11 3 Points Application layer has Points branch You can manage there signals measurements from controlled device and commands to control...

Страница 187: ...parameters which you can specify on SPA BUS protocol are proposed in the next table Create new status point window Field name Description Default value Type SPA type of point Range of values I Input Data O Output Data S Setting Values V Variables M Memory Data I Input Data SubType SPA sub type of point Range of values Single Point Double Point Integer Single Point ...

Страница 188: ...nge of values 0 999999 1 EV0 Channel Leave empty to use same channel as data Range of values Empty 0 999 EV0 Number Leave empty to ignore events Range of values Empty 0 64 EV1 Channel Leave empty to use same channel as data Range of values Empty 0 999 EV1 Number Leave empty to ignore events Range of values Empty 0 64 EV2 Channel Leave empty to use same channel as data Range of values Empty 0 999 E...

Страница 189: ...ignore events Range of values Empty 0 64 Alarm Channel Leave empty to use same channel as data Range of values Empty 0 999 Alarm Number Leave empty to ignore alarms Range of values Empty 0 64 Invert Inversion of status Values No Yes No Offset 1 New value Old value Offset1 Scale Offset2 0 Scale 1 Offset 2 0 Data points Columns Value Time Quality Cause will show real time data from controlled device...

Страница 190: ...e SPA sub type of point Range of values Single Point Double Point Integer Float Single Point Channel Channel Range of values 0 999 0 Channel Increment After adding new point Channel will be automatically incremented by set value Range of values 0 999 0 Data Number Data Number Range of values 0 999999 1 Data Number Increment After adding new point Data Number will be automatically incremented by se...

Страница 191: ...Enilit RTU User Manual 16 09 Enilit RTU software Master protocols Page 191 of 309 Scale Offset2 1 Offset 2 0 Invert Inversion of status Values No Yes No Command points ...

Страница 192: ...art Enables or disables application layer on start Values No Yes No Port monitor Show port monitor on system startup Values No Yes No 4 10 12 2 Points Port name layer has Points branch This protocol is used for RTU Cyber security functions and Self diagnostic It gets data from RTU hardware Operating system and Enilit CMS Points are created automatically There is a possibility to change some parame...

Страница 193: ...erating system Type Status Signal activates and goes to normal Security Operating System Log On Failure Total Count of Failed user logon s to Operating system Type Integer Security Operating System Log On Failure in series Count of Failed user logon s to Operating system in series Type Status Security Operating System Logged On User is logging to Operating system Type Status Signal activates only ...

Страница 194: ...ted Operating system log Type Status Signal activates on deletion of Operating system logs and then goes to normal Security Enilit CMS Log On Failure Failed user log on to Enilit CMS Type Status Signal activates and goes to normal Security Enilit CMS Log On Failure Total Count of Failed user logon s to Enilit CMS Type Integer Security Enilit CMS Log On Failure in series Count of Failed user logon ...

Страница 195: ...stics Disks Low C Limit for used disk space in percent Limit range is configurable Range of value 0 100 Diagnostics Disks Low D Limit for used disk space in percent Limit range is configurable Range of value 0 100 Diagnostics Disks Low E Limit for used disk space in percent Limit range is configurable Range of value 0 100 Diagnostics Disks Low F Limit for used disk space in percent Limit range is ...

Страница 196: ...tion for example network interface card NIC is not present 4 NCS_HARDWARE_DISABLED The hardware for the connection is present but is not enabled 5 NCS_HARDWARE_MALFUNCTION A malfunction has occurred in the hardware for the connection 6 NCS_MEDIA_DISCONNECTED The media for example the network cable is disconnected 7 NCS_AUTHENTICATING The connection is waiting for authentication to occur 8 NCS_AUTH...

Страница 197: ...example COM3 IEC 101 slave New IEC_101 slave protocol Enabled on start Port enabled on system startup Values No Yes No COM port Communication port number Range of values COM 1 COM 255 Not assigned Baud rate Serial port baud rate Range of values 110 921600 9600 Data bits Serial port data bits Values 7 8 8 Stop bits Serial port stop bits Values 1 1 5 2 1 Parity Serial port parity Values None Odd Eve...

Страница 198: ... 600 seconds 0 Not used 0 Data Link address size Data link address size Range of values 0 2 bytes 1 Port monitor Show port monitor on system startup Values No Yes No Log raw data Log raw communication data Values No Yes Yes 4 11 1 2 Data link layer parameters IEC 60870 5 101 protocol data link layer parameters Field name Description Default value ID For internal use Data Link Name Data link layer ...

Страница 199: ...e All start stop checksum and other bytes are included Range of values 50 261 bytes 255 Disconnect No requests Disconnect data link layer if no requests received from master for specified time Range of values 0 3600 seconds 0 not used 0 Status Link If status link needed before reset link Values No Yes No Allow E5 Enables or disables E5 response to controlling device Values No Yes Yes Class1 answer...

Страница 200: ... 60870 5 101 protocol application layer parameters Field name Description Default value ID For internal use Application Name Application layer name For example SCADA 1 New application Enabled on start Enables or disables data link on start Values No Yes No Common address Common address of data unit Range of values 1 254 1 ...

Страница 201: ...ogation command request but general interrogation already is going No general interrogation is restarted Values No Yes No Interrogation over Class2 Interrogation response will have higher priority than Class2 events Values No Yes No Time difference Time difference to discard command execution Range of values 1 60000 milliseconds 10000 C SE ActTerm Activation termination is used for set point comma...

Страница 202: ...ground COT Range of values 10 10000 seconds 60 Event buffer Class1 size Spontaneous Events buffer of Class 1 size Change has only take effect after system restart Range of values 10 10000 events 1000 Event buffer Class1 overflow If the buffer of class 1 events overflows with this parameter you can select which event to remove from queue Range of values Remove first Remove all Remove first Overflow...

Страница 203: ...ice should initiate general interrogation 0 not used Not Event NotTopical Disconnected If received event from main module has only set quality to Not Topical and cause of change is Disconnected source than no event will be generated to upper system Values No Yes No SQ Use SQ bit Recommended to use only if most part of information object addresses are incremented by one Values No Yes Yes Log header...

Страница 204: ...for IEC 60870 5 101 slave Create new status point dialog for IEC 60870 5 101 slave Field name Description Default value IEC Type IEC 60870 5 101 data type Values Single point Double point Step position Bit string of 32 bits Measured value normalized value Measured value scaled value Single Point ...

Страница 205: ...hort time 3 bytes Long time 7 bytes Long Time 7 bytes Interrogation Assign data point to the specific interrogation group Range of values General Interrogation Interrogation Group1 16 General Interrogation Change You can specify data point class or cause of transmission If you choose to be Class1 Event or Class2 Event data point will be marked with Spontaneous cause of transmission Range of values...

Страница 206: ...101 slave Create new command point dialog for IEC 60870 5 101 slave Field name Description Default value IEC Type IEC 60870 5 101 command type Values Single command Double command Regulating step command Setpoint normalized command Setpoint scaled command Setpoint short float command Bitstring command Single Command IOA Here the information address can be specified 1 ...

Страница 207: ... Old value Offset1 Scale Offset2 0 Scale 1 Offset 2 0 Invert Inversion of commands Values No Yes No You can select some data points and then press Ctrl Shift N to connect all selected data points to the tags in a row If tag icon is grayed out it is not possible to connect to slave status point or command point It means if you have to choose Status point in slave protocol it is possible to connect ...

Страница 208: ... IEC 60870 5 104 protocol configuration 4 11 2 1 Communication port parameters IEC 60870 5 104 protocol communication port parameters Field name Description Default value ID For internal use Port Name Port name For example IEC 104 slave New IEC 104 slave protocol Enabled on start Enables or disables communication port on start Yes ...

Страница 209: ...on is still up and running or if it has broken Range of values 1 2147483647 milliseconds 0 disabled 10000 TCP No delay Controls TCP packet batching Values No Yes No Reconnect How often try to connect to communication port if there was error Range of values 1 600 seconds 10 Init time Protocol initialization time on startup During this time no events will be generated Range of values 1 60 0 Port Mon...

Страница 210: ... ID For internal use Data Link Name Data link layer name For example IEC 104 client New Data link Enabled on start Enables or disables client on start Values No Yes No T1 Acknowledgement time out 1 Range of values 1 255 seconds 15 T2 Acknowledgement time out 2 Range of values 1 255 seconds 10 T3 Connection test timeout Range of values 1 255 seconds 20 k Maximum number of unacknowledged I format 12...

Страница 211: ...ximum frame size All start stop checksum and other bytes are included Range of values 50 261 bytes 255 StartTD Action taken when got second StartTD from other client Values Ignore Connect new client Ignore No ACK On disconnect keep in buffer all sent but not acknowledged I frames On new client connect all not acknowledged frames will be transmitted Values No Yes No Clients Nr 1 9 IP Access list of...

Страница 212: ...lication Name Application layer name For example SCADA 1 New Application Enabled on start Enables or disables data link on start Values No Yes No Common address Common address of data unit Range of values 1 254 1 Object address size Size of information object address field Range of values 1 3 3 Object address structure Object address structure shows in what format information object address is ent...

Страница 213: ...o discard command execution Range of values 1 60000 milliseconds 10000 C SE ActTerm Activation termination is used for set point commands Values No Yes Yes C SE Cause Allow Allow to set local or remote command cause of transmission in case measurement point was changed by command Values No Yes No Allow synchronization Allows clock synchronization from controlled station Values No Yes No UTC Time s...

Страница 214: ...uffer of events overflows with this parameter you can select which event to remove from queue Range of values Remove first Remove all Remove first Overflow IOA Overflow information object address On buffer overflow this IOA will be set to 1 and when there is free places in buffer it will be set to 0 When it changes to 0 controlling device should initiate general interrogation 0 not used Not Event ...

Страница 215: ...Page 215 of 309 Log IO Log information objects Values No Yes Yes 4 11 2 4 Points IEC 60870 5 104 status points window Create new status point dialog for IEC 60870 5 104 slave Field name Description Default value IEC Type IEC 60870 5 104 data type Values Single Point ...

Страница 216: ... IOA Increment After adding new data point address will be automatically incremented by set value It is used only for configuration 1 Time type Timestamp of data point Range of values No time Short time 3 bytes Long time 7 bytes Long time 7 bytes Interrogation Assign data point to the specific interrogation group Range of values General Interrogation Interrogation Group1 6 General Interrogation On...

Страница 217: ... IEC 60870 5 104 slave Field name Description Default value IEC Type IEC 60870 5 104 command type Values Single command Double command Regulating step command Setpoint normalized command Setpoint scaled command Setpoint short float command Bitstring command Single Command IOA Here the information address can be specified Range of information address depends from Application layer parameter Informa...

Страница 218: ... 1 Offset 2 0 Invert Inversion of command Values No Yes No 4 11 3 DNP3 serial slave configuration 4 11 3 1 Communication port parameters DNP3 serial communication port parameters Field name Description Default value ID For internal use Port Name Name of the port and protocol For example COM3 DNP3 slave New DNP3 slave protocol Enabled on start Port enabled on system startup Values No Yes No COM por...

Страница 219: ... port is RS 232 parameter is not Important Values Four wire two wire Four wire Reconnect How often try to reconnect to communication port if there was an error Range of values 1 600 seconds 10 Init time Protocol initialization time on startup During this time no events will be generated Range of values 1 600 0 Not used 0 Port Monitor Show port monitor on system startup Values No Yes No Log raw dat...

Страница 220: ...isables client on start Values No Yes No Data Link address RTU s slave address Range of values 0 65519 1 Master station address Master station address Range of values 0 65519 1 Self Address Enabled Set this parameter to true only for testing purpose when master does not know outstation address Values No Yes No Fragment Size Maximum data link fragment size Range of values 14 292 bytes 292 Response ...

Страница 221: ...not used 0 Link Status DFC How often to check for DFC 0 if DFC was 1 Range of values 1 86400 seconds 1 Disconnect No requests Disconnect data link layer if no requests received from master for specified time Range of values 0 3600 seconds 0 Not used 30 Log header Log data link header Values No Yes Yes Log Answer Time Out Log data link answer timeouts to system log Values Never First Time Always Fi...

Страница 222: ...rameters 1 Field name Description Default value ID For internal use Read only Application Name Application layer name For example Application layer New Application Enabled on start Port enabled on system startup Values No Yes No Response timeout Response timeout Range of value 50 60000 milliseconds 500 Confirmation Application layer should request confirmations Values No Yes No Confirmation Events...

Страница 223: ...yer fragment size Range of values 249 65535 bytes 2024 Binary Input Default variation for binary input Values Single Bit With Status With Status Binary Input Change Default variation for binary input change Values Without Time With Time Relative Time With Time Double Bit Input Default variation for Double Bit input Values No Flags With Status With Status Double Bit Input Change Default variation f...

Страница 224: ...t With Time 64 Bit Float With Time 32 Bit With Time Analog Input Deadband Default variation for Analog input Deadband Values 16 Bit 32 Bit 32 Bit Float 32 Bit Analog Output Default variation for Analog output Values 16 Bit 32 Bit 32 Bit Float 64 Bit Float 32 Bit Analog Output Change Default variation for Analog output change Values 32 Bit With Time 16 Bit With Time 32 Bit Without Time 16 Bit Witho...

Страница 225: ...artup Send unsolicited NULL response on startup restart or enabling Values No Yes Yes Unsolicited Class1 Unsolicited messages enabled for Class1 after startup or restart Values No Yes Yes Unsolicited Class2 Unsolicited messages enabled for Class2 after startup or restart Values No Yes Yes Unsolicited Class3 Unsolicited messages enabled for Class3 after startup or restart Values No Yes Yes Unsolici...

Страница 226: ...0 10000 1000 Cold restart Action performed on received FC13 Cold Restart request Values Ignore Discard Software restart Full Device restart Ignore Warm restart Action performed on received FC14 Warm Restart request Values Ignore Discard Restart Ignore Save configuration Action performed on received FC19 Save configuration request Values Ignore Discard Save configuration Ignore Activate configurati...

Страница 227: ... Input Double point type This parameter sets which bit should be first transferred If set No first is OFF if set Yes first is ON No Log DO Log Data Object information Value No Yes Yes Log header Enables to log headers in Port Monitor Values No Yes Yes Log IO Log data and command points information Values No Yes Yes Log Answer Time Out Log application link answer timeouts to system log Values Never...

Страница 228: ... After adding new point Index will be automatically incremented by set value 1 Event Class To which event class belongs data object Values No event Class 1 Class 2 Class 3 No Event Unsolicited Unsolicited messages enabled for this point If class is disabled this parameter has no meaning Values No Yes Yes Offset 1 New value Old value Offset1 Scale Offset2 0 Scale 1 Offset 2 0 Invert Inversion of st...

Страница 229: ...Object DNP3 object type Values Binary Output Command Analog Output Command Binary Output Command Index Here the Object index can be specified Range of values 0 2147483647 1 Index Increment After adding new point Index will be automatically incremented by set value 1 Offset 1 New value Old value Offset1 Scale Offset2 0 Scale 1 Offset 2 0 Invert Inversion of status Values No Yes No ...

Страница 230: ... LAN server protocol Enabled on start Port enabled on system startup Values No Yes No Ethernet port Which Ethernet port to use to create server Values All ETH ETH 1 ETH 2 ETH 3 ETH4 All ETH TCP Port TCP port Range of values 1 65535 20000 TCP Keep Alive Checks the connected socket and determines whether the connection is still up and running or if it has broken Range of values 1 2147483647 millisec...

Страница 231: ... port monitor on system startup Values No Yes No Log raw data Enables to log raw communication data Values No Yes Yes Log Unknown Data Link Set this parameter always to No in multiple slave systems Yes 4 11 4 2 Data link layer parameters DNP3 UDP TCP IP data link layer parameters Field name Description Default value ID For internal use Data Link Name Data link layer name For example DNP3 client Ne...

Страница 232: ... should use confirmations Values No Yes No Broken link Number of retries to determine if the connection is broken Range of values 1 255 3 Priority Request data every cycle Only relevant if more than one data link layer exists Range of values 1 255 1 Link Status How often to request link status if there was no data Range of values 0 86400 seconds 0 Link Status is not used 0 Link Status DFC How ofte...

Страница 233: ...4 11 4 4 Application layer parameters Refer to the DNP3 serial paragraph Application layer parameters The configuration is very similar 4 11 4 5 Points Refer to the DNP3 serial paragraph Points The configuration is very similar 4 11 5 SPA BUS configuration 4 11 5 1 Communication port parameters SPA BUS communication port parameters Field name Description Default value ID For internal use Port name...

Страница 234: ...Serial port parity Values None Odd Even Mark Space Even RS 485 mode If used two wires mirrored data check should be used If serial port is RS 232 parameter is not important Values Two wires Four wires Four wires Reconnect How often to try to connect to communication port Range of values 1 600 seconds 10 Init time Protocol initialization time on startup During this time no events will be generated ...

Страница 235: ...on layer on start Values No Yes No Address Slave address Range of values 1 999 900 is broadcast 1 Frame size Maximum frame length Range of values 48 255 bytes 255 Disconnect No requests Disconnect data link layer if no requests received from master for specified time Range of values 0 3600 seconds 0 not used 0 Allow synchronization Yes synchronize always No synchronize only if RTU internal clock i...

Страница 236: ...oints popup menu which you can run with right mouse button You can Add data point Edit data point Delete data point Select All data points or commands You can Connect to Tag Remove connection to the Tag Go to Tag in TAG Manager as well Remove connection to source is possible from TAG Manager All menu items have keyboard shortcuts They will simplify and quicken the work with the software Points pop...

Страница 237: ...tatus point window Field name Description Default value Type SPA type of point Range of values I Input Data O Output Data S Setting Values V Variables M Memory Data I Input Data SubType SPA sub type of point Range of values Single Point Double Point Integer Float Single Point Channel Channel 0 ...

Страница 238: ...empty to use same channel as data Range of values Empty 0 999 EV0 Number Leave empty to ignore events Range of values Empty 0 64 EV1 Channel Leave empty to use same channel as data Range of values Empty 0 999 EV1 Number Leave empty to ignore events Range of values Empty 0 64 EV2 Channel Leave empty to use same channel as data Range of values Empty 0 999 EV2 Number Leave empty to ignore events Rang...

Страница 239: ...es Empty 0 64 Alarm Channel Leave empty to use same channel as data Range of values Empty 0 999 Alarm Number Leave empty to ignore alarms Range of values Empty 0 64 Invert Inversion of status Values No Yes No Offset 1 New value Old value Offset1 Scale Offset2 0 Scale 1 Offset 2 0 SPA Bus Status points window Columns Value Time Quality Cause will show real time data ...

Страница 240: ... Data I Input Data SubType SPA sub type of point Range of values Single Point Double Point Integer Float Single Point Channel Channel Range of values 0 999 0 Channel Increment After adding new point Channel will be automatically incremented by set value Range of values 0 999 0 Data Number Data Number Range of values 0 999999 1 Data Number Increment After adding new point Data Number will be automa...

Страница 241: ...ser Manual 16 09 Enilit RTU software Slave protocols Page 241 of 309 Offset 1 New value Old value Offset1 Scale Offset2 0 Scale 1 Offset 2 0 Invert Inversion of status Values No Yes No SPA Bus Command points window ...

Страница 242: ... RP 570 slave protocol Port enabled Port enabled on system startup Values No Yes No COM port Communication port number Range of values COM 1 255 Not assigned Baud rate Serial port baud rate Range of values 110 921600 9600 Data bits Serial port data bits Values 7 8 bits 8 Stop bits Serial port stop bits Values 1 1 5 2 bits 1 Parity Serial port parity Values None Odd Even Mark Space Even RS 485 mode...

Страница 243: ...nit time Protocol initialization time on startup During this time no events will be generated Range of values 1 60 0 Port monitor Show port monitor on system startup Values No Yes No Log raw data Log raw communication data Values No Yes Yes Log Unknown Application Layer Set this parameter always to No in multiple slave system Yes 4 11 6 2 Application layer parameters RP 570 application layer param...

Страница 244: ...e Range of values 0 3600 seconds 0 not used 0 Select Cancel With Value Some master devices do not send value with select and cancel commands In this case set this parameters to No Yes Allow synchronization Yes synchronize always No synchronize only if RTU internal clock is synchronized Yes UTC Use UTC time in communication Values No Yes Yes Time difference Time difference to synchronize internal R...

Страница 245: ...ty Events with Time will be sent with the same priority as events with status in other case priority level will be lower If master supports RequestA possible it will not support this function Yes Events before SCI Event messages have higher priority than SCI responses Yes AVM Multi Allow multiple analog values with incrementing block number transmit with incrementing NCB Yes CCR with Data Allow to...

Страница 246: ...nse 0 255 0 unlimited 1 IDM Maximum count in one response 0 255 0 unlimited 1 IDS Maximum count in one response 0 255 0 unlimited 1 AVM Maximum count in one response 0 255 0 unlimited 1 AVS Maximum count in one response 0 255 0 unlimited 1 DVM Maximum count in one response 0 255 0 unlimited 1 ERMI Maximum count in one response 0 255 0 unlimited 1 ERMA Maximum count in one response 0 255 0 unlimite...

Страница 247: ...data point Delete data point Select All data points or commands You can Connect to Tag Remove connection to the Tag Go to Tag in TAG Manager as well Remove connection to source is possible from TAG Manager All menu items have keyboard shortcuts They will simplify and quicken the work with the software Points popup menu Following figure shows Create new status point dialog window The parameters whi...

Страница 248: ...Priority RP 570 priority of point 1 Block No Block Number Range of values 0 255 1 Block No Increment After adding new point Block No will be automatically incremented by set value Range of values 0 255 1 Bit Bit Number Range of values 0 15 0 Bit Increment After adding new point Bit number will be automatically incremented by set value Range of values 0 255 1 Double Point Is indication double point...

Страница 249: ...int Range of values CBX Command SPM SetPoint GOM General Output CBX Command Block No Block Number for CBX 0 2047 for SPM and GOM 0 255 0 Block No Increment After adding new point Block number will be automatically incremented by set value Range of values 0 999 0 Offset 1 New value Old value Offset1 Scale Offset2 0 Scale 1 Offset 2 0 Invert Inversion of status Values No Yes No ...

Страница 250: ...tware part which connects status and command points from master to slave protocols or connects hardware tags to slave protocols Either you can create there tags for internal logic or IsaGRAF programming With the help of tree structure you can create structure of substation for easier work with tags Main windows of TAG Manager ...

Страница 251: ...of Tags Delete Deletes selected branch Del Goto Data source If Tag is selected you can reach the data source of Tag G Remove Data source Disconnect Data source from Tag Show Change Monitor Opens Change monitor window Test event Test event with forced value and quality Test command Test command with forced value and quality Import Tags Import Tags from CSV file Export Tags Export Tags to CSV file E...

Страница 252: ...e one new with the type you want Values Status Integer 64 bits Status Float 64 bits Manual Status Integer 64 bits Manual Status Float 64 bits Name Name of the tag Status 1 Description Additional user description Comments Additional user comments State ID Tag states configuration ID Not connected State Name Tag states configuration Name Not connected State Real time state of Tag Value Real time val...

Страница 253: ...ters you have possibility to change value which you will take from the data source NewValue OldValue Offset1 Scale1 Offset2 Scale2 0 Offset 2 0 Scale 1 1 Scale 2 1 Command Tag edit window Field name Description Default value ID ID number Only for internal use Automatically increment value Type Tag data type You can t edit this value You must delete the tag and then create one new with the type you...

Страница 254: ... Not connected Port Name Data source Port Name Not connected Point ID Data source Point ID Not connected Point Name Data source Point Name Not connected Offset 1 With those parameters you have possibility to change value which you will take from the data source NewValue OldValue Offset1 Scale1 Offset2 S cale2 0 Offset 2 0 Scale 1 1 Scale 2 1 ITag ID Interlocking Tag ID Interlocking TAG Tag used fo...

Страница 255: ...nds in seconds Range of values 1 3600 30 Execute Timeout Execute command timeout in seconds Range of values 1 3600 10 Cancel Timeout Cancel command timeout in seconds Range of values 1 3600 10 Select Accept Select command will be confirmed with positive result Values Yes No Yes Cancel Accept Cancel command will be confirmed with positive result Values Yes No Yes Select needed Execute command will ...

Страница 256: ...unication ports RTU hardware points or PLC If you have connected Tag to the Data source and connected it also to Slave protocol all the information regarding linkage you can see in the tag configuration of window Also you can see here real time value state timestamp quality and cause of transmission of selected tag Signal monitoring 4 12 1 Tag states Tag states configuration tool allows you to con...

Страница 257: ... picture shows initial Tag States window Initial Tag states window When you start to configure state for status signal it s needed to add with the priority 0 type irrelevant and quality Not topical with the value Yes Then you add normal states like Reset 0 and Set 1 Following picture show this configuration ...

Страница 258: ...e TAG Manager Page 258 of 309 Configured status state Reset Set If the state is configured properly then is possible to assign state to the signal or command in the TAG Manager window like in the following picture Configured Tag with assigned state ...

Страница 259: ...ic To use it it s needed to create Manual Status Integer 64 bits or Manual Status Float 64 bits tags After creation of Manual tag you will see Logic calculation area like in the following figure Manual Status Tag with Logic calculations area To create some logic it is needed to add Logic calculations with the help of right mouse button on the Logic calculation window like in the following figure L...

Страница 260: ... next calculation else if Result is FALSE it will output value 0 to the next calculation With the parameters Result TRUE and Result FALSE it is possible to change result values to the next logic calculation Operation can be one of assign equal not equal less less or equal more more or equal OR OR bits AND AND bits XOR XOR bits addition subtraction multiplication division Integer type Logic operati...

Страница 261: ...onal user comments Empty State ID Tag state ID State Name Assigned Tag State name Not assigned State Actual state Value Actual value 0 Time Date Time of last change Quality Actual quality 0x00000000 Not init Cause Actual cause Not defined Offset 1 With those parameters you have possibility to change value which you will take from the data source NewValue OldValue Offset1 Scale1 Offset2 Scale2 0 Of...

Страница 262: ... IsaGRAF PLC Programming window Popup menu window Field name Description Active Create new Branch Creates new branch Branches Create new Resource Creates new resource Branches Open Isagraf workbench Open the integrated programmable logic environment IsaGRAF by selecting this menu item Everywhere Enable Isagraf Enables IsaGRAF runtime Everywhere IsaGRAF is an IEC 61131 open control software for aut...

Страница 263: ...E_Create_Command_Ack_LINT Creates integer command acknowledgement Field name Description Variable Input of command Data type ENILIT_OUT_COACK_LINT ID Commands identification number Data type UDINT Result Command acknowledgement type positive negative termination Data type BYTE Create Enable or disable acknowledgement Data type BOOL E_Create_Command_Ack_LREAL Creates float command acknowledgement F...

Страница 264: ... negative termination Data type BYTE Create Enable or disable acknowledgement Data type BOOL E_Create_Command_LINT Creates integer command Field name Description Variable Output of command to RTU Data type ENILIT_IN_COACK_LINT ID Commands identification number Data type UDINT Value Value of command Data type LINT TimeOut Wait for command acknowledgement Data type TIME Type Type of command single d...

Страница 265: ...ID Identification number of command acknowledgement Data type UDINT Ret_Result Result of command acknowledgement Data type BYTE Ret_TimeStamp Timestamp of command acknowledgement Data type LINT Ret_Ack Acknowledgement positive or negative Data type BOOL E_Create_Command_LREAL Creates float command Field name Description Variable Output of command to RTU Data type ENILIT_IN_COACK_LREAL ID Commands ...

Страница 266: ... Data type BOOL Create Enable or disable acknowledgement Data type BOOL Ret_ID Identification number of command acknowledgement Data type UDINT Ret_Result Result of command acknowledgement Data type BYTE Ret_TimeStamp Timestamp of command acknowledgement Data type LINT Ret_Ack Acknowledgement positive or negative Data type BOOL E_Create_Event_LINT Creates integer event Field name Description Varia...

Страница 267: ...ata type BOOL E_Create_Event_LREAL Creates float event Field name Description Variable Output of Event to RTU Data type ENILIT_OUT_EV_LREAL Value Value of event Data type LREAL Quality Quality of event Data type UINT Create Enable or disable event creation Data type BOOL E_Get_TimeStamp Gets timestamp of RTU Field name Description TimeStamp TimeStamp of RTU Data type LINT ...

Страница 268: ...ommand from RTU Data type ENILIT_OUT_COACK_LINT ID Commands identification number Data type UDINT Value Value of command Data type LINT TimeStamp TimeStamp of command Data type LINT Type Type of command Data type BYTE SubType Type of command activation deactivation Data type BYTE Test Command with test flag Data type BOOL IsCommand If Yes then Command is active Data type BOOL ...

Страница 269: ...mmand from RTU Data type ENILIT_OUT_COACK_LREAL ID Commands identification number Data type UDINT Value Value of command Data type LREAL TimeStamp TimeStamp of command Data type LINT Type Type of command Data type BYTE SubType Type of command activation deactivation Data type BYTE Test Command with test flag Data type BOOL IsCommand If Yes then Command is active Data type BOOL ...

Страница 270: ...nput of event from RTU Data type ENILIT_IN_EV_LINT Value Value of event Data type LINT TimeStamp TimeStamp of event Data type LINT Quality Quality of event Data type UDINT IsEvent If Yes then Event is active Data type BOOL E_Wait_Event_LREAL Waits float event Field name Description Variable Input of event from RTU Data type ENILIT_IN_EV_LREAL Value Value of event ...

Страница 271: ...Bad configuration E_COACK_BAD_VALUE Bad value E_COACK_CANCEL_DONE Deactivation confirmation E_COACK_CANCEL_REJECTED Deactivation rejected E_COACK_COMMAND_ALREADY_IN_PROGRESS Command already in progress E_COACK_COMMAND_IN_PROGRESS Command in progress E_COACK_COMMAND_QUEUE_FULL Command queue full E_COACK_EXECUTE_DONE Activation confirmation E_COACK_EXECUTE_REJECTED Activation rejected E_COACK_INTELO...

Страница 272: ...nd execution undefined result Command quality E_COSUB_LONG_PULSE Long pulse E_COSUB_NOT_DEFINED Not defined E_COSUB_PERSISTENT Persistent E_COSUB_SHORT_PULSE Short pulse Quality of event E_QUAL_BLOCKED Blocked E_QUAL_GOOD Good E_QUAL_INVALID Invalid E_QUAL_INVALIDTIME Invalid time E_QUAL_NOTINIT Not initialized E_QUAL_NOTTOPICAL Not topical E_QUAL_OVERFLOW Overflow E_QUAL_SUBSTITUTED Substituted ...

Страница 273: ...rtup Values No Yes Yes Clock precision Clock will be synchronized only if time offset is larger than requested precision Range of value 1 60000 miliseconds 10 Clock not synchronized If there was no clock synchronization for particular time it will be considered that clock is not synchronized Range of values 1 86400 seconds 86400 Synchronization from slaves After what time allow synchronization fro...

Страница 274: ...own use only for protocol testing or commissioning No Log Log clock synchronizations from slave communication protocol Values No Yes Yes Show On startup show this window Values No Yes No Expand On startup expand all tree nodes Values No Yes No Create new SNTP client If you have created new SNTP client you will see following window with default parameters Other opportunity is to run Show monitor wi...

Страница 275: ...r disable SNTP client Values No Yes No SNTP Version Version of SNTP Values 3 4 3 Priority If you will configure more than one SNTP server you can rank servers in your order Range of values 1 255 1 Server SNTP server IP address Values xxx zzz yyy nnn 127 0 0 1 UDP Port UDP port to connect with server Range of values 1 65535 123 Ethernet port Here the information address can be specified Range of va...

Страница 276: ...e timeout after request has been sent Range of values 1 86400 seconds 5 Synchronization period The time period to make synchronization Range of values 1 86400 seconds 15 Log IP Enables to view IP log Values No Yes Yes Log Raw Enables to view raw log Values No Yes Yes Log Data Enables to view data log Values No Yes Yes SNTP client popup window With the Show monitor you can open diagnostic tool for ...

Страница 277: ...Enilit RTU User Manual 16 09 Enilit RTU software Time management Page 277 of 309 Time management monitor window ...

Страница 278: ...ues to view and keep saved system and events log 4 16 1 Hardware monitoring With the popup menu in Enilit RTU Hardware configuration window you can run Enilit RTU Hardware state monitoring Hardware popup menu When you click Show Hardware state you will see following figure With this window you can check if the hardware is well configured and working In this hardware monitoring window you can see c...

Страница 279: ... status can be monitored via communication protocols You can connect hardware status signals to tags with TAG Manager you can control also hardware with commands from SCADA Following figure shows Hardware status signals commands and measurements window Hardware status signals commands and measurements Field name Description Card types Connected Central processor communicates with card The card wor...

Страница 280: ...cts wrongs card type Type Status item 0 Ok 1 Fault AI31 DI31 DO31 CPU Temperature Central processor Temperature measurement Type Status item CPU Watchdog state Watchdog state 0 Ok 1 Fault CPU Led2 State Central processor Led2 state Type Status item 0 Led2 off 1 Led2 on CPU Led2 Control Control of central processor Led2 state Type Command item 0 Off 1 On CPU 4 16 2 Protocol monitoring and supervisi...

Страница 281: ...it for all serial or TCP protocols even for SNTP Standard master protocol monitor window Field name Description Default value Enabled Enables to view communication data Values Checked Unchecked Unchecked Follow Enables to follow last communication data Values Checked Unchecked Unchecked Log to file Enables to log all data to log file Values Checked Unchecked Unchecked Next figure shows that you ca...

Страница 282: ... Values Checked Unchecked Checked Follow Enables to follow last communication data Values Checked Unchecked Checked Log to file Enables to log all data to log file Values Checked Unchecked Checked This communication port monitoring tool is very useful at substation commissioning stage Commissioning engineer doesn t need any additional testing software even worse hardware for port monitoring and so...

Страница 283: ...d Reset process manually It is very useful in commissioning stage 4 16 2 3 Status signals commands and measurements From every protocol in controlling direction status signals and measurements of protocols can be used for monitoring in SCADA or HMI Commands of protocols can be used as well for protocol supervision Standard protocol status items for master protocols Field name Description Protocols...

Страница 284: ...s Type Float All RX Packets Count of protocol received packets Type Float All RX Err Answer Timeout Type Float All serial protocols RX Err First Char Type Float All serial protocols RX Err Last Char Type Float All serial protocols RX Err Check Sum Type Float All serial protocols RX Err Length Type Float All serial protocols RX Err Mirrored Type Float All serial protocols PRP 1 device is visible on...

Страница 285: ...of 309 Standard protocol control items for IEC master protocols 4 16 3 System log When you start Enilit RTU CMS the first window is System log window The information in this window is also written to a file The location of logs is described in the RTU description file System log window ...

Страница 286: ...s window is also written to the file By default Events log files are stored in the RTU configuration directory Logs The location of logs is described in the RTU description file To quickly open Events log you can use TAG Manager menu File and Open Tag history file TAG Manager menu File Configuration parameters for Logs you can find in TAG Manager main branch Device ...

Страница 287: ...scription Free user description Comments Free user comments Log RTU Time Additional column will be added to history files which shows event received time in TAG Manager Values No Yes No Days for history How many days to keep events in Events list Range of values 10 1000 days 365 Max file size Maximum size of all Events list files Range of values 10 1000 Mb 100 Record count Record count in one Even...

Страница 288: ...asurements tags Log measurements changes to Events list files Values No Yes Yes Log command tags Log commands changes to Events list files Values No Yes Yes Log incoming changes Log incoming changes to Events list files Values No Yes Yes Log outgoing changes Log outgoing changes to Events list files Values No Yes Yes Show On startup show this window No Expand On startup expand all tree nodes No Sh...

Страница 289: ...plications or in cases where data is changed infrequently 4 17 2 2 Warm Standby A method of redundancy in which the secondary RTU system runs in the background of the primary system Data is mirrored to the secondary RTU at regular intervals which means that there are times when both servers do not contain the exact same data 4 17 2 3 Hot Standby A method of redundancy in which the primary RTU and ...

Страница 290: ...two RTU s One of it is called Main and another Standby At any time there can be only one Main RTU The Main RTU is responsible data acquisition from slave and server devices command transmission to slave and server devices PLC logic process information transmission to upper communication levels process information transmission to Standby RTU The Standby RTU is responsible data acquisition from Main...

Страница 291: ...iption about 4 13 Self control and diagnosis Monitored information Communication paths between Main and Standby RTU s this is done by default and is not user selectable RS 485 RS 232 port hardware errors and state Ethernet port hardware errors and state Cards hardware errors and state Inner voltages and temperatures Main CPU state Power supply state Main Watchdog relay on CPU card Digital Input ty...

Страница 292: ...r disables Redundancy on start Values No Yes No Enabled Shows if redundancy is enabled To change this parameter use Enilit Project Manager No Main Device Shows if this device is Main device No Device Main Main Device Name To change this parameter use Enilit Project Manager Device Main IP Main Device IP address To change this parameter use Enilit Project Manager Device Standby Standby Device Name T...

Страница 293: ...rtup Device waits for connections from redundant Device if there are no connections for specified time this Device will be set to Main mode Range of Values 100 60000 ms 5000 Port Monitor Show port monitor on system startup Values No Yes No Show On startup show this window No Expand On startup expand all Tree Nodes No 4 17 7 Communication channel configuration 4 17 7 1 Redundancy Connection LAN1 pa...

Страница 294: ...ge of values 0 2147483647 milliseconds 0 disabled 500 TCP No delay TCP No delay disables the Nagle Algorithm Values No Yes No Connect Time Out Communication timeout In case if this is last connection between RTU s and it is timed out then switchover from Standby RTU to Active happens 500 Reconnect How often try to connect to communication port if there was error Range of Values 50 60000 ms 500 Por...

Страница 295: ...TH1 ETH2 ETH3 ETH4 Not assigned TCP Port TCP IP communication port 5404 TCP Keep Alive TCP Keep Alive Do not set low values because it will add overhead to communication Range of values 0 2147483647 milliseconds 0 disabled 500 TCP No delay TCP No delay disables the Nagle Algorithm Values No Yes No Connect Time Out Communication timeout In case if this is last connection between RTU s and it is tim...

Страница 296: ...meters Redundancy connection RS 232 RS 485 No 3 parameters Field name Description Default value ID For internal use Port Name Port Name RS 232 RS 485 No 3 Enabled on start Enables or disables connection on start Values No Yes No Com port Communication port number Not assigned Baud rate Serial port baud rate Range of values 110 921600 9600 Data bits Serial port data bits Values 7 8 bits 8 Stop bits...

Страница 297: ...Port Monitor Show port monitor on system startup Values No Yes No Log raw data Log raw communication data Values No Yes Yes 4 17 7 4 Redundancy Connection RS 232 RS 485 No 4 parameters Redundancy connection RS 232 RS 485 No 4 parameters Field name Description Default value ID For internal use Port Name Port Name RS 232 RS 485 No 4 Enabled on start Enables or disables connection on start Values No ...

Страница 298: ...res Two wires Four wire Reconnect How often try to reconnect to communication port if there was error Range of values 1 600 seconds 10 Port Monitor Show port monitor on system startup Values No Yes No Log raw data Log raw communication data Values No Yes Yes 4 17 8 Status signals commands and measurements Every system status signal for Redundancy you can connect to upper communication link and sen...

Страница 299: ...n port enabled Field name Description Device is primary Device is primary The name of the Device in your project shows that this device is primary Device is in MAIN mode Current Device is now in MAIN mode Device is in STANDBY mode Current Device is now in STANDBY mode Events in internal buffer Total events in internal buffer Events in buffer from system Total events in system buffer Events in buff...

Страница 300: ...ts Protocol transmitted packets RX Bytes Protocol received bytes RX Packets Protocol received packets RX Err Answer Time Out Error Answer Time out RX Err First Char Error Wrong first character RX Err Last Char Error Wrong last character RX Err Check Sum Error Wrong Check sum RX Err Length Error Wrong Packet Length RX Err Mirrored Error Got Mirrored data Connected Redundancy communication link is w...

Страница 301: ...items for redundant connection Field name Description TX Bytes Protocol transmitted bytes TX Requests Protocol transmitted packets RX Bytes Protocol received bytes RX Packets Protocol received packets Connected Connected to the redundant RTU Values 1 Normal 0 Communication error Enabled Enabled or disabled redundant connection Values 1 Enabled 0 Disabled ...

Страница 302: ...tacks in Enilit RTU is made data cyber security capabilities according standard IEEE 1686 2007 IEEE Standard for Substation Intelligent Electronic Devices IEDs Cyber Security Capabilities February 2008 IEEE 1686 2007 is a security standard for IEDs It establishes requirements for IED security in accordance with NERC CIP This standard defines the functions and features to be provided in substation ...

Страница 303: ...ee paragraph 4 5 3 of this document 4 18 2 4 Authorization levels by password The Enilit RTU supports the ability to assign authorization to utilize Enilit RTU functions and features based on individual user created passwords At a minimum the following functions and features shall have this assign ability available View Data the ability to view operational data voltage current power energy status ...

Страница 304: ...ntenance port 4 18 3 1 Storage capability The audit trail facility has the capability to store more than 10 000 events before the circular buffer begins to overwrite the oldest event with the newest event There is no capability to erase or modify the audit trail It is not possible to remove the storage media of the audit trail without permanently damaging the Enilit RTU beyond the capability of fi...

Страница 305: ...on file or keystroke entry of new configuration parameter Password Creation Creation of new password or modification of password level of authorization Password Revocation Revocation of a password Audit Log Access User access of audit log for viewing or file download Time Date Change User request to change time and date Audit Trial log Settings of Audit Trial ...

Страница 306: ...18 4 1 Events Events are defined as authorized activities which can be expected to occur in the routine use and maintenance of the Enilit RTU All events can be monitored and transmitted to the supervisory system Event points have momentary change detect capability so that the occurrence of an event will be reported on the next scan of the Enilit RTU by the supervisory system The Enilit RTU reports...

Страница 307: ...l Access in this mode all functions including password changes and user assignment levels can be made The configuration software is password controlled so that the software cannot be accessed without the proper password All communications ports other on the Enilit RTU have the capability to be enabled or disabled through configuration of the Enilit RTU When disabled through configuration no commun...

Страница 308: ...oint command DPS Double point signal GI General interrogation ICD IED Capability Description IED Intelligent Electronic Device MV Measurement value PLC Programmable logic controller PRP Parallel Redundancy Protocol RTU Remote terminal unit SCADA Supervisory control and data acquisition SCL Substation Configuration Language SNTP Simple Network Time Protocol SPC Single point command SPS Single point...

Страница 309: ... Contacts Cyber security capabilities Page 309 of 309 Contacts UAB Enilit Tel 370 655 53155 Veiverių str 134 221 Tel Fax 370 37 291708 LT 46352 Kaunas E mail info enilit lt Lithuania www enilit eu Support e mail support enilit lt ...