SECTION XV: TROUBLESHOOTING (continued)
E ,IWKH%RLOHU&RQWUROGHWHFWVDQHUURULWZLOOÀDVK
(UU
ERLOHUFRQWUROHUURUIROORZHGE\DQXPEHU8VHWKLVWH[WDQG
QXPEHUWRLGHQWLI\WKHERLOHUSUREOHPDQGFRUUHFWLYHDFWLRQLQ7DEOHEHORZ
Display
Status
Recommended Corrective Actions
(UU
Temperature Sensor Fault
Temperature sensor failure, wire harness loose or shorted connection or control
hardware failure:
- Check sensor is securely attached to boiler control
- Check that sensor wire is not damaged
- If secure and in good condition, replace sensor
- If problem persists, replace control
(UU
Communication Fault
Enviracom terminal is shorted to ground or line voltage.
- Check wiring to EnviraCOM terminals 1,2 and 3. Wiring to external EnviraCom
device is incorrect.
(UU
Internal Hardware Fault
Error detected with AC power supply frequency or boiler control failure. Cycle power to
the control. Replace control if problem persists.
(UU
Burner Output (B1) Fault
B1 output sensed powered during safety output relay check sequence or un-powered
during running, or powered in idle in combination with water temperature above 264°F
limit. Cycle power to the control. Replace control if problem persists.
(UU
Line Voltage Fault (< 80 Vac)
$&YROWDJHRXWRIVSHFL¿FDWLRQKLJKRUORZFKHFN//9$&
(UU
Fuse missing
Internal fuse is blown or missing. The fuse protects the Aquastat from miswiring the L1
and L2 on Oil Primary. When the Oil Primary is correctly wired the fuse is useless and
not detected. If Primary is wired incorrectly the fuse is blown out and Aquastat report
HUURU(QYLUD&20PHVVDJHLVVHQWZKHQWKHZLULQJLV¿[HGDQGWKHHUURUGLVDSSHDUV
to indicate the end of the error state. Check wiring and replace fuse.
(UU
User settings lost, (reset to
factory defaults)
Warning: Generated if user adjustments are lost and the device uses factory default
values. Error is cleared by entering and exiting the Adjustment mode. Replace control
if problem persists.
(UU
Manual Reset Lockout
(resettable)
Set if
(UU
was invoked four times in a row. Check wiring and clear Lockout by
pressing all three user keys for 30 seconds.
TABLE 11: BOILER CONTROL ERROR NUMBERS
Содержание V8H3
Страница 76: ...76 Bare Boiler Assembly Continued SECTION XVI REPAIR PARTS continued...
Страница 78: ...78 Jacket Assembly SECTION XVI REPAIR PARTS continued...
Страница 80: ...80 V8H3 Thru V8H9 Steam Boilers Trim and Controls SECTION XVI REPAIR PARTS continued...
Страница 82: ...82 V8H3 Thru V8H9 Water Boilers Trim and Controls SECTION XVI REPAIR PARTS continued...
Страница 84: ...84 Beckett AFG Burner SECTION XVI REPAIR PARTS continued...
Страница 94: ...94 SERVICE RECORD DATE SERVICE PERFORMED...
Страница 95: ...95 SERVICE RECORD DATE SERVICE PERFORMED...
Страница 96: ...96 U S Boiler Company Inc P O Box 3020 Lancaster PA 17604 1 888 432 8887 www usboiler net...