3. PROVIDE COMBUSTION AIR
INSUFFICIENT COMBUSTION AIR
SUPPLY may result in the production and
release of deadly carbon monoxide (CO) into the
home which can cause severe personal injury or
death.
4. CONNECT VENTING
DAMPER MUST BE OPEN when the main burner is firing.
Like all fuel-burning appliances, boilers need air to
operate reliably and safely.
Provide combustion air using the instructions in
Appendix A—Combustion Air.
4-a
IMPROPER VENTING may result in property
damage and the release of flue gases which
contain deadly carbon monoxide (CO) into the home,
which can cause severe personal injury, death or
substantial property damage.
INSPECT EXISTING CHIMNEY before
installing boiler. Failure to clean or replace
perforated pipe or tile lining will cause severe injury
or death.
The vent system shall be designed and constructed
in accordance with NFPA 54 and applicable local
codes to develop a positive flow adequate to convey
flue or vent gases to the outdoors, while ensuring
that flue gases do not cool prematurely.
Observe all general venting guidelines provided in
Appendix B—Venting. Additionally:
1.
This appliance shall be vented into a listed
gas vent, masonry, metal, or factory-built
chimney as required by NFPA 54 and
applicable local codes for Category I
appliances. If venting this appliance into
a masonry chimney, the chimney must be
lined with approved clay flue lining, a listed
chimney lining system, or other approved
material as required by NFPA 54 and
applicable local codes.
2.
Attach the vent damper with three sheetmetal
screws around the perimeter of the flue collar
(Figure 4-a), oriented so that the position
indicator is visible. The vent damper may
also be mounted anywhere between the flue
outlet and the chimney within reach of the
electrical harness.
3.
Vent connector shall meet the requirements
of NFPA 54 and applicable local codes.
Using sheetmetal screws, attach the vent
connector between the vent damper and the
vertical chimney (Figure 4-b).
4-b
Содержание SERIES 3
Страница 5: ...5 Figure S 1 Minimum Clearances to Combustibles and Alcove Dimensions SPECIFICATIONS continued...
Страница 31: ...31 INTERNAL WIRING Figure IW 1 Wiring Diagram...
Страница 32: ...32 INTERNAL WIRING continued Figure IW 2 Wiring Schematic...
Страница 43: ...43 APPENDIX D System Piping continued Figure D W2 Recommended Water Piping for Zone Valve Zoned heating Systems...
Страница 44: ...44 APPENDIX D System Piping continued Figure D W3 Recommended Water Piping for Circulator Zoned heating Systems...
Страница 53: ...53 SERVICE RECORD DATE SERVICE PERFORMED...
Страница 54: ...54 SERVICE RECORD DATE SERVICE PERFORMED...
Страница 55: ...55 SERVICE RECORD DATE SERVICE PERFORMED...
Страница 56: ...56 U S Boiler Company Inc P O Box 3020 Lancaster PA 17604 1 888 432 8887 www usboiler net...