Jan9
th
2018
RD06 user manual V 1.4
- 8 -
X=1 Enable GPRS Function
(default)
018
Set the time intervals of GPRS
Data
*
$$$$$$
,018,X#
X=0 stop send time interval
GPRS
=[10,6000] Time interval
(Unit: sec)
(default:300)
019
Set the GPRS mode
*
$$$$$$
,019,X#
X=0, Use the UDP mode
X=1, Use the TCP mode
(default)
020
Local digital OUTPUT alarm
function
*
$$$$$$
,020,X#
X=0, disable
X=1, enable,(default)
030
Set SMS alarm function
*
$$$$$$
,030, ABCDEFG#
A=1,Enable SMS alarm for
temperature and humidity alert,
(default)
;
B=1,Enable SMS alarm for
power off (default)
;
C=1,Enable SMS alarm for low
voltage alert, (default)
;
D=0;
E=0;
F=0;
G=0;
040
RS485 setting
*
$$$$$$
,040, A,B,C,D #
A:Baud rate [1200,115200],
9600(default);
B:Data bit,
0-8bit(default),
1-9bit
;
C:Stop bit,
0-0.5bit,
1-1bit(default),
2-1.5bit,
3-2bit
D:Parity bit,
0-null(default),
1-Even parity,
2-Odd parity
041
RS485 working mode
*
$$$$$$
,041, X#
X:0-Report automatically
;
X:1-modbus, Should add TAG
to channels(command
144) ,default
;
042
RS485 address
*
$$$$$$
,042, AB#
AB:[0-F],
Can’t be 00,
default:01