Installation

The  RAPID  RESPONSE  Series  LFII 

Residential Horizontal and Recessed 

Horizontal Sidewall Sprinklers (TY1334) 

must be installed in accordance with 

the following instructions.

NOTICE

Do not install any bulb type sprinkler if 

the bulb is cracked or there is a loss of 

liquid from the bulb. With the sprinkler 

held  horizontally,  a  small  air  bubble 

should be present. The diameter of the 

air bubble is approximately 1/16 inch 

(1,6 mm).
Obtain  a  leak-tight  1/2  inch  NPT 

sprinkler joint by applying a minimum 

to maximum torque of 7 to 14 ft. lbs. 

(9,5 to 19,0 Nm). Higher levels of torque 

can  distort  the  sprinkler  Inlet  with 

consequent leakage or impairment of 

the sprinkler.
Do  not  attempt  to  compensate 

for  insufficient  adjustment  in  an 

Escutcheon Plate by under- or over-

tightening the Sprinkler. Re-adjust the 

position of the sprinkler fitting to suit.

Series LFII Residential Horizontal 

Sidewall Sprinklers 

The Series LFII Residential Horizontal 

Sidewall Sprinklers must be installed 

in  accordance  with  the  following 

instructions.
1.  Install horizontal sidewall sprinklers 

in the horizontal position with their 

center-line  of  waterway  perpen-

dicular to the backwall and parallel 

to the ceiling. The word “TOP” on 

the Deflector is to face towards the 

ceiling  with  the  front  edge  of  the 

Deflector parallel to the ceiling.

2.  With pipe-thread sealant applied to 

the pipe threads, hand-tighten the 

sprinkler into the sprinkler fitting. 

3.  Tighten the sprinkler into the 

sprin-

kler fitting using only the W-Type 6 

Sprinkler Wrench. (Figure 3). With 

reference  to  Figure  1,  apply  the 

W-Type 6 Sprinkler Wrench to the 

wrench flats. 

Series LFII Residential Recessed 

Horizontal Sidewall Sprinklers 

The Series LFII Residential Recessed 

Horizontal  Sidewall  Sprinklers  must 

be  installed  in  accordance  with  the 

following instructions.
1.  Install recessed horizontal sidewall 

sprinklers in the horizontal position 

with their center-line of waterway 

perpendicular to the backwall and 

parallel  to  the  ceiling.  The  word 

“TOP” on the Deflector is to face 

towards the ceiling. 

2.  After  installing  the  Style  20 

Mounting  Plate  over  the  sprin-

kler threads and with pipe-thread 

sealant applied to the pipe threads, 

hand-tighten the sprinkler into the 

sprinkler fitting.

3.  Tighten the sprinkler into the sprin-

kler fitting using only the W-Type 7 

Recessed Sprinkler Wrench (Figure 

4). With reference to Figure 1, apply 

the W-Type 7 Recessed Sprinkler 

Wrench  to  the  sprinkler  wrench 

flats.

4.  After the ceiling has been installed 

or the finish coat has been applied, 

slide on the Style 20 Closure over 

the Series LFII Residential Sprinkler 

and  push  the  Closure  over  the 

Mounting  Plate  until  its  flange 

comes in contact with the ceiling.

Care and   

Maintenance

The  RAPID  RESPONSE  Series  LFII 

Residential Horizontal and Recessed 

Horizontal Sidewall Sprinklers (TY1334) 

must  be  maintained  and  serviced 

in  accordance  with  the  following 

instructions.

NOTICE

Before closing a fire protection system 

main  control  valve  for  maintenance 

work  on  the  fire  protection  system 

that it controls, obtain permission to 

shut down the affected fire protection 

systems  from  the  proper  authorities 

and notify all personnel who may be 

affected by this action. 
Absence  of  the  outer  piece  of  an 

escutcheon,  which  is  used  to  cover 

a clearance hole, can delay sprinkler 

operation in a fire situation.
Owners  must  assure  that  the  sprin-

klers are not used for hanging of any 

objects and that the sprinklers are only 

cleaned  by  means  of  gently  dusting 

with a feather duster; otherwise, non-

operation in the event of a fire or inad-

vertent operation may result.

Exercise  care  to  avoid  damage  to 

sprinklers  before,  during,  and  after 

installation.  Never  paint,  plate,  coat, 

or otherwise alter automatic sprinklers 

after they leave the factory. 
Replace sprinklers that:
•  were modified or over-heated.
•  were damaged by dropping, striking, 

wrench twisting, wrench slippage, or 

the like.

•  are leaking or exhibiting visible signs 

of corrosion.

•  were exposed to corrosive products 

of combustion but have not operated, 

if you cannot easily remove combus-

tion by-products with a cloth. 

•  have  a  cracked  bulb  or  have  lost 

liquid  from  the  bulb.  Refer  to  the 

Installation section in this data sheet.

Initial and frequent visual inspections of 

random samples are recommended for 

corrosion-resistant sprinklers to verify 

the integrity of the corrosion-resistant 

material 

of  construction.  Thereafter, 

annual inspections per NFPA 25 should 

suffice. 
Inspections  of  corrosion-resistant 

sprinklers are recommended at close 

range,  instead  of  from  the  floor  level 

per  NFPA.  Inspection  at  close  range 

can better determine the exact sprinkler 

condition and the long-term integrity of 

the corrosion-resistant material, which 

can be affected by the corrosive condi-

tions present.
Responsibility lies with the owner for 

the  inspection,  testing,  and  mainte-

nance of their fire protection system 

and  devices  in  compliance  with  this 

document, as well as with the appli-

cable  standards  of  the  National  Fire 

Protection Association (that is, NFPA 

25), in addition to the standards of any 

authorities having jurisdiction. Contact 

the  installing  contractor  or  sprinkler 

manufacturer regarding any questions.
Automatic sprinkler systems are recom-

mended to be inspected, tested, and 

maintained  by  a  qualified  Inspection 

Service  in  accordance  with  local 

requirements and/or national codes.

Содержание TY1334

Страница 1: ...filled pipe in addition to not having to increase the number of design sprinklers hydraulic design area for systems designed to NFPA 13 13D or 13R Non water filled pipe will permit options for areas sensitive to freezing The Series LFII Residential Sprinklers has a 4 2 60 5 K Factor that provides the required residential flow rates at reduced pressures enabling smaller pipe sizes and water supply ...

Страница 2: ...ating Bulb Deflector 1 Components 2 Button Assembly Frame TOP 57 2 mm 2 1 4 41 3 mm 1 5 8 6 4 5 3 2 1 2 7 8 DIA 73 0 mm RECESSED ESCUTCHEON STYLE 20 FLATS WRENCH CENTERLINE OF WATERWAY 1 2 NPT BOSS END OF DEFLECTOR TOP OF DEFLECTOR 7 16 11 1 mm FIGURE 1 RAPID RESPONSE SERIES LFII RESIDENTIAL HORIZONTAL SIDEWALL AND RECESSED HORIZONTAL SIDEWALL SPRINKLERS TY1334 FIGURE 2 STYLE 20 RECESSED ESCUTCHEO...

Страница 3: ...sprinkler systems the requirements for Dry System Water Delivery per the Section 8 3 4 3 of the 2010 edition of NFPA 13D apply For a residential hazard in no case shall the time of water delivery exceed 15 seconds for the most remote operating sprinkler Hydraulic Design NFPA 13D and 13R The minimum re quired sprinkler flow rate for systems designed to NFPA 13D or NFPA 13R are given in Tables A B C...

Страница 4: ...M 18 4 psi 1 27 bar 16 x 18 4 9 x 5 5 16 4 9 19 GPM 71 9 LPM 20 5 psi 1 41 bar 19 GPM 71 9 LPM 20 5 psi 1 41 bar 21 GPM 79 5 LPM 25 0 psi 1 72 bar 21 GPM 79 5 LPM 25 0 psi 1 72 bar 16 x 20 4 9 x 6 1 16 4 9 23 GPM 87 1 LPM 30 0 psi 2 07 bar 23 GPM 87 1 LPM 30 0 psi 2 07 bar 26 GPM 98 4 LPM 38 3 psi 2 64 bar 26 GPM 98 4 LPM 38 3 psi 2 64 bar Sidewall sprinklers where installed under a ceiling with a...

Страница 5: ... 4 9 23 GPM 87 1 LPM 30 0 psi 2 07 bar Not Applicable Not Applicable Not Applicable Sidewall sprinklers where installed under a ceiling with a slope greater than a 0 inch rise for a 12 inch run to a slope up to a 2 inch rise for a 12 inch run must be located per one of the following At the high positioned to discharge down the slope Along the slope and positioned to discharge across the slope a Fo...

Страница 6: ...7 bar I 14 GPM 53 0 LPM 11 1 psi 0 77 bar I 17 GPM 64 3 LPM 16 4 psi 1 13 bar I 17 GPM 64 3 LPM 16 4 psi 1 13 bar 16 x 16 4 9 x 4 9 16 4 9 I 16 GPM 60 6 LPM 14 5 psi 1 00 bar I 16 GPM 60 6 LPM 14 5 psi 1 00 bar I 18 GPM 68 1 LPM 18 4 psi 1 27 bar I 18 GPM 68 1 LPM 18 4 psi 1 27 bar 16 x 18 4 9 x 5 5 16 4 9 I 19 GPM 71 9 LPM 20 5 psi 1 41 bar I 19 GPM 71 9 LPM 20 5 psi 1 41 bar I 21 GPM 79 5 LPM 25...

Страница 7: ...LPM 18 4 psi 1 27 bar 14 x 14 4 3 x 4 3 14 4 3 II 16 GPM 60 6 LPM 14 5 psi 1 00 bar II 16 GPM 60 6 LPM 14 5 psi 1 00 bar II 18 GPM 68 1 LPM 18 4 psi 1 27 bar II 18 GPM 68 1 LPM 18 4 psi 1 27 bar 16 x 16 4 9 x 4 9 16 4 9 II 16 GPM 60 6 LPM 14 5 psi 1 00 bar II 16 GPM 60 6 LPM 14 5 psi 1 00 bar II 18 GPM 68 1 LPM 18 4 psi 1 27 bar II 18 GPM 68 1 LPM 18 4 psi 1 27 bar 16 x 18 4 9 x 5 5 16 4 9 II 22 G...

Страница 8: ... C 12 x 12 3 7 x 3 7 12 3 7 III 16 GPM 60 6 LPM 14 5 psi 1 00 bar III 16 GPM 60 6 LPM 14 5 psi 1 00 bar 14 x 14 4 3 x 4 3 14 4 3 III 16 GPM 60 6 LPM 14 5 psi 1 00 bar III 16 GPM 60 6 LPM 14 5 psi 1 00 bar 16 x 16 4 9 x 4 9 16 4 9 III 16 GPM 60 6 LPM 14 5 psi 1 00 bar III 16 GPM 60 6 LPM 14 5 psi 1 00 bar 16 x 18 4 9 x 5 5 16 4 9 N A N A 16 x 20 4 9 x 6 1 16 4 9 N A N A a For coverage area dimensio...

Страница 9: ...e Series LFII Residential Sprinkler and push the Closure over the Mounting Plate until its flange comes in contact with the ceiling Care and Maintenance The RAPID RESPONSE Series LFII Residential Horizontal and Recessed Horizontal Sidewall Sprinklers TY1334 must be maintained and serviced in accordance with the following instructions NOTICE Before closing a fire protection system main control valv...

Страница 10: ...ncluding but not limited to labor charges regardless of whether TFSBP was informed about the possi bility of such damages and in no event shall TFSBP s liability exceed an amount equal to the sales price The foregoing warranty is made in lieu of any and all other warranties express or implied including warran ties of merchantability and fitness for a particular purpose This limited warranty sets f...

Отзывы: