Tyco TY1334 Скачать руководство пользователя страница 3

TFP410

Page 3 of 10 

Technical  

Data 

Approvals

•  UL Listed for use with wet pipe and 

dry pipe systems

•  C-UL  Listed  for  use  only  with  wet 

pipe systems

•  NYC Approved under MEA 44-03-E
For details on these approvals, refer to 

the Design Criteria section.

Maximum Working Pressure

175 psi (12,1 bar) 

Discharge Coefficient

K=4.2 GPM/psi

1/2

 (60,5 LPM/bar

1/2

Temperature Rating

155°F (68°C) or 175°F (79°C) 

Finishes

•  White Polyester 
•  Chrome Plated
•  Natural Brass 

Physical Characteristics

Frame  . . . . . . . . . . . . . . . . . . . . Brass
Button . . . . . . . . . . . . . . . . . . . Bronze 
Sealing Assembly . . . . . . . . Beryllium 

Nickel w/Teflon* 

Bulb (3 mm) . . . . . . . . . . . . . . . . Glass 
Compression Screw . . . . . . . . Bronze  
Deflector . . . . . . . . . . . . . . . . .Copper

Operation

The  glass  Bulb  contains  a  fluid  that 

expands when exposed to heat. When 

the rated temperature is reached, the 

fluid expands sufficiently to shatter the 

glass  Bulb,  allowing  the  sprinkler  to 

activate and flow water.

Design  

Criteria 

The  RAPID  RESPONSE  Series  LFII 

Residential Horizontal and Recessed 

Horizontal Sidewall Sprinklers (TY1334) 

are  UL  and  C-UL  Listed  for  installa-

tion in accordance with the following 

criteria.

Note: 

When conditions exist that are 

outside  the  scope  of  the  provided 

criteria,  refer  to  the  Residential 

Sprinkler  Design  Guide  TFP490  for 

the manufacturer’s recommendations 

that  may  be  acceptable  to  the  local 

authority having jurisdiction. 

*Registered trademark of Dupont

System Types

Per the UL Listing, wet pipe and dry 

pipe systems may be utilized. Per the 

C-UL Listing, only wet pipe systems 

may be utilized.

•  For dry systems corrosion-resistant 

or  internally  galvanized  pipe  shall 

be  utilized  with  the  sprinklers  de-

scribed in this data sheet.

•  For  dry  systems  not  using  CPVC, 

pendent sprinklers shall be installed 

on  return  bends,  where  the  sprin-

klers,  return  bends,  and  branch 

line  piping  (that  is,  potential  areas 

for trapped water) are in areas at or 

above 40°F (4°C).

Refer to technical data sheet TFP485 

about the use of Residential Sprinklers 

in residential dry pipe systems.

NOTICE

When  corrosion-resistant  or  inter-

nally galvanized pipe and fittings with 

a  potable  water  supply  is  utilized, 

return  bends  need  not  be  installed. 

However, any portion of the piping that 

has  the  potential  to  trap  water  must 

be maintained at or above 40°F (4°C) 

unless provision to drain such areas is 

provided and maintained dry.

Water Delivery

When using the Series LFII Residential 

Horizontal Sidewall Sprinklers (TY1334) 

in  dry  pipe  sprinkler  systems,  the 

requirements  for  “Dry  System  Water 

Delivery” per the Section 8.3.4.3 of the 

2010 edition of NFPA 13D apply. For 

a residential hazard, in no case shall 

the  time  of  water  delivery  exceed  15 

seconds for the most remote operating 

sprinkler.

Hydraulic Design  

(NFPA 13D and 13R)

The minimum re quired sprinkler flow 

rate for systems designed to NFPA 13D 

or NFPA 13R are given in Tables A, B, 

C, D and E as a function of tempera-

ture rating and the maximum allowable 

coverage areas. The sprinkler flow rate 

is  the  minimum  required  discharge 

from  each  of  the  total  number  of 

“design  sprinklers”  as  specified  in 

NFPA 13D or NFPA 13R.

NOTICE

The  number  of  “design  sprinklers” 

specified in NFPA 13D and 13R for wet 

pipe  systems  is  to  be  applied  when 

designing dry pipe systems. There is 

no need to increase the design area, as 

is the case for density/area systems, in 

accordance with U.S. Patent 7,712,543. 

Hydraulic Design  

(NFPA 13)

For  systems  designed  to  NFPA  13, 

the  number  of  design  sprinklers  is 

to  be  the  four  most  hydraulically 

demanding  sprinklers.  The  minimum 

required  discharge  from  each  of  the 

four sprinklers is to be the greater of 

the following: 
•  The flow rates given in Tables A or B 

for NFPA 13D and 13R as a function 

of temperature rating and the maxi-

mum allowable coverage area. 

•  A  minimum  discharge  of  0.1  GPM/

sq.  ft.  over  the  “design  area”  com-

prised of the four most hydraulical-

ly  demanding  sprinklers  for  actu-

al  coverage  areas  protected  by  the 

four sprinklers. 

NOTICE

The  number  of  “design  sprin-

klers”  specified  in  NFPA  13  for  wet 

pipe  systems  is  to  be  applied  when 

designing dry pipe systems. There is 

no need to increase the design area, as 

is the case for density/area systems, in 

accordance with U.S. Patent 7,712,543. 

Obstruction to Water Distribution

Sprinklers are to be located in accor-

dance  with  the  obstruction  rules 

defined  by  NFPA  13  for  residential 

sprinklers. 

Operational Sensitivity

The sprinklers are to be installed with 

an  end-of-  deflector-boss  to  wall 

distance of 1-3/8 to 6 inches or in the 

recessed position using only the Style 

20 Recessed Escutcheon as shown in 

Figure 2.
In  addition  the  top-of-deflector-to-

ceiling distance is to be within the range 

(Tables A, B, C, D or E) being hydrauli-

cally calculated.

Sprinkler Spacing

The minimum spacing between sprin-

klers is 8 feet (2,4 m). The maximum 

spacing  between  sprinklers  cannot 

exceed the width of the coverage area 

(Tables  A  and  B)  being  hydraulically 

calculated; (maximum 12 feet for a 12 

ft. x 12 ft. coverage area, or 16 feet for 

a 16 ft. x 20 ft. coverage area. 

Содержание TY1334

Страница 1: ...filled pipe in addition to not having to increase the number of design sprinklers hydraulic design area for systems designed to NFPA 13 13D or 13R Non water filled pipe will permit options for areas sensitive to freezing The Series LFII Residential Sprinklers has a 4 2 60 5 K Factor that provides the required residential flow rates at reduced pressures enabling smaller pipe sizes and water supply ...

Страница 2: ...ating Bulb Deflector 1 Components 2 Button Assembly Frame TOP 57 2 mm 2 1 4 41 3 mm 1 5 8 6 4 5 3 2 1 2 7 8 DIA 73 0 mm RECESSED ESCUTCHEON STYLE 20 FLATS WRENCH CENTERLINE OF WATERWAY 1 2 NPT BOSS END OF DEFLECTOR TOP OF DEFLECTOR 7 16 11 1 mm FIGURE 1 RAPID RESPONSE SERIES LFII RESIDENTIAL HORIZONTAL SIDEWALL AND RECESSED HORIZONTAL SIDEWALL SPRINKLERS TY1334 FIGURE 2 STYLE 20 RECESSED ESCUTCHEO...

Страница 3: ...sprinkler systems the requirements for Dry System Water Delivery per the Section 8 3 4 3 of the 2010 edition of NFPA 13D apply For a residential hazard in no case shall the time of water delivery exceed 15 seconds for the most remote operating sprinkler Hydraulic Design NFPA 13D and 13R The minimum re quired sprinkler flow rate for systems designed to NFPA 13D or NFPA 13R are given in Tables A B C...

Страница 4: ...M 18 4 psi 1 27 bar 16 x 18 4 9 x 5 5 16 4 9 19 GPM 71 9 LPM 20 5 psi 1 41 bar 19 GPM 71 9 LPM 20 5 psi 1 41 bar 21 GPM 79 5 LPM 25 0 psi 1 72 bar 21 GPM 79 5 LPM 25 0 psi 1 72 bar 16 x 20 4 9 x 6 1 16 4 9 23 GPM 87 1 LPM 30 0 psi 2 07 bar 23 GPM 87 1 LPM 30 0 psi 2 07 bar 26 GPM 98 4 LPM 38 3 psi 2 64 bar 26 GPM 98 4 LPM 38 3 psi 2 64 bar Sidewall sprinklers where installed under a ceiling with a...

Страница 5: ... 4 9 23 GPM 87 1 LPM 30 0 psi 2 07 bar Not Applicable Not Applicable Not Applicable Sidewall sprinklers where installed under a ceiling with a slope greater than a 0 inch rise for a 12 inch run to a slope up to a 2 inch rise for a 12 inch run must be located per one of the following At the high positioned to discharge down the slope Along the slope and positioned to discharge across the slope a Fo...

Страница 6: ...7 bar I 14 GPM 53 0 LPM 11 1 psi 0 77 bar I 17 GPM 64 3 LPM 16 4 psi 1 13 bar I 17 GPM 64 3 LPM 16 4 psi 1 13 bar 16 x 16 4 9 x 4 9 16 4 9 I 16 GPM 60 6 LPM 14 5 psi 1 00 bar I 16 GPM 60 6 LPM 14 5 psi 1 00 bar I 18 GPM 68 1 LPM 18 4 psi 1 27 bar I 18 GPM 68 1 LPM 18 4 psi 1 27 bar 16 x 18 4 9 x 5 5 16 4 9 I 19 GPM 71 9 LPM 20 5 psi 1 41 bar I 19 GPM 71 9 LPM 20 5 psi 1 41 bar I 21 GPM 79 5 LPM 25...

Страница 7: ...LPM 18 4 psi 1 27 bar 14 x 14 4 3 x 4 3 14 4 3 II 16 GPM 60 6 LPM 14 5 psi 1 00 bar II 16 GPM 60 6 LPM 14 5 psi 1 00 bar II 18 GPM 68 1 LPM 18 4 psi 1 27 bar II 18 GPM 68 1 LPM 18 4 psi 1 27 bar 16 x 16 4 9 x 4 9 16 4 9 II 16 GPM 60 6 LPM 14 5 psi 1 00 bar II 16 GPM 60 6 LPM 14 5 psi 1 00 bar II 18 GPM 68 1 LPM 18 4 psi 1 27 bar II 18 GPM 68 1 LPM 18 4 psi 1 27 bar 16 x 18 4 9 x 5 5 16 4 9 II 22 G...

Страница 8: ... C 12 x 12 3 7 x 3 7 12 3 7 III 16 GPM 60 6 LPM 14 5 psi 1 00 bar III 16 GPM 60 6 LPM 14 5 psi 1 00 bar 14 x 14 4 3 x 4 3 14 4 3 III 16 GPM 60 6 LPM 14 5 psi 1 00 bar III 16 GPM 60 6 LPM 14 5 psi 1 00 bar 16 x 16 4 9 x 4 9 16 4 9 III 16 GPM 60 6 LPM 14 5 psi 1 00 bar III 16 GPM 60 6 LPM 14 5 psi 1 00 bar 16 x 18 4 9 x 5 5 16 4 9 N A N A 16 x 20 4 9 x 6 1 16 4 9 N A N A a For coverage area dimensio...

Страница 9: ...e Series LFII Residential Sprinkler and push the Closure over the Mounting Plate until its flange comes in contact with the ceiling Care and Maintenance The RAPID RESPONSE Series LFII Residential Horizontal and Recessed Horizontal Sidewall Sprinklers TY1334 must be maintained and serviced in accordance with the following instructions NOTICE Before closing a fire protection system main control valv...

Страница 10: ...ncluding but not limited to labor charges regardless of whether TFSBP was informed about the possi bility of such damages and in no event shall TFSBP s liability exceed an amount equal to the sales price The foregoing warranty is made in lieu of any and all other warranties express or implied including warran ties of merchantability and fitness for a particular purpose This limited warranty sets f...

Отзывы: