Series LFII Residential Sprinklers 

4.2K Horizontal and Recessed Horizontal Sidewall 

Wet Pipe and Dry Pipe Systems

Page 1 of 10  

SEPTEMBER  2010 

TFP410

Technical Services 

  800-381-9312 | +1-401-781-8220 

www.tyco-fire.com

General 

Description

The TYCO RAPID RESPONSE Series 

LFII  Residential  Horizontal  Sidewall 

Sprinklers  (TY1334)  are  decorative, 

fast  response,  frangible  bulb  sprin-

klers  designed  for  use  in  residential 

occupancies  such  as  homes,  apart-

ments, dormitories, and hotels. When 

aesthetics and optimized flow charac-

teristics  are  the  major  consideration, 

the  Series  LFII  Residential  Sidewall 

Sprinklers should be the first choice.
The Series LFII Residential Sprinklers  

are  intended  for  use  in  the  following 

scenarios: 
•  wet and dry pipe residential sprinkler 

systems  for  one-  and  two-family 

dwellings  and  mobile  homes  per 

NFPA 13D

•  wet and dry pipe residential sprinkler 

systems for residential occupancies 

up  to  and  including  four  stories  in 

height per NFPA 13R

•  wet and dry pipe sprinkler systems 

for  the  residential  portions  of  any 

occupancy per NFPA 13

Historically  residential  sprinklers, 

based  on  their  Listing,  have  been 

limited to wet pipe sprinkler systems 

to assure speed of water delivery for a 

given prescribed design area (number 

of design sprinklers).

The  Listing  for  the  Series  LFII 

Residential Horizontal and Recessed 

Horizontal  Sidewall  Sprinklers  now 

offers the laboratory approved option 

of  designing  dry  pipe  residential 

sprinkler systems.

Through extensive testing, it has been 

determined that the number of design 

sprinklers (hydraulic design area) for the 

Series LFII Residential Sprinklers need 

not be increased over the number of 

design  sprinklers  (hydraulic  design 

area) as specified for wet pipe sprinkler 

systems, as is accustomed for density/ 

area  sprinkler  systems  designed  per 

NFPA 13.
Consequently, 

the 

Series 

LFII 

Residential Sprinklers offer the features 

of non-water filled pipe in addition to 

not having to increase the number of 

design  sprinklers  (hydraulic  design 

area)  for  systems  designed  to  NFPA 

13, 13D, or 13R. Non-water filled pipe 

will permit options for areas sensitive 

to freezing

The Series LFII Residential Sprinklers 

has a 4.2 (60,5) K-Factor that provides 

the  required  residential  flow  rates 

at  reduced  pressures,  enabling 

smaller  pipe  sizes  and  water  supply 

requirements.
The  recessed  version  of  the  Series 

LFII Residential Sprinklers is intended 

for  use  in  areas  with  finished  walls. 

It  employs  a  two-piece  Style  20 

Recessed Escutcheon. The Recessed 

Escutcheon  provides  1/4  inch  (6,4 

mm)  of  recessed  adjustment  or  up 

to 1/2 inch (12,7 mm) of total adjust-

ment from the flush mounting surface 

position. The adjustment provided by 

the Recessed Escutcheon reduces the 

accuracy to which the pipe nipples to 

the sprinklers must be cut.

The Series LFII Residential Sprinklers 

has been designed with heat sensitivity 

and water distribution characteristics 

proven to help in the control of residen-

tial fires and to improve the chance for 

occupants to escape or be evacuated. 

IMPORTANT

Always  refer  to  Technical  Data 

Sheet  TFP700  for  the  “INSTALLER 

WARNING”  that  provides  cautions  

with respect to handling and instal-

lation  of  sprinkler  systems  and 

components. Improper handling and 

installation can permanently damage 

a sprinkler system or its components 

and  cause  the  sprinkler  to  fail  to  

operate in a fire situation or cause it  

to operate prematurely

.

NOTICE

The Series LFII Residential Horizontal 

Sidewall  Sprinklers  described  herein 

must  be  installed  and  maintained  in 

compliance  with  this  document  and 

the applicable standards of the National 

Fire Protection Association, in addition 

to  the  standards  of  any  authorities 

having  jurisdiction.  Failure  to  do  so 

may impair the performance of these 

devices.
Owners are responsible for maintaining 

their fire protection system and devices 

in  proper  operating  condition.  The 

installing contractor or sprinkler manu-

facturer should be contacted with any 

questions. 

Model/Sprinkler 

Identification 

Number (SIN)

TY1334

Содержание TY1334

Страница 1: ...filled pipe in addition to not having to increase the number of design sprinklers hydraulic design area for systems designed to NFPA 13 13D or 13R Non water filled pipe will permit options for areas sensitive to freezing The Series LFII Residential Sprinklers has a 4 2 60 5 K Factor that provides the required residential flow rates at reduced pressures enabling smaller pipe sizes and water supply ...

Страница 2: ...ating Bulb Deflector 1 Components 2 Button Assembly Frame TOP 57 2 mm 2 1 4 41 3 mm 1 5 8 6 4 5 3 2 1 2 7 8 DIA 73 0 mm RECESSED ESCUTCHEON STYLE 20 FLATS WRENCH CENTERLINE OF WATERWAY 1 2 NPT BOSS END OF DEFLECTOR TOP OF DEFLECTOR 7 16 11 1 mm FIGURE 1 RAPID RESPONSE SERIES LFII RESIDENTIAL HORIZONTAL SIDEWALL AND RECESSED HORIZONTAL SIDEWALL SPRINKLERS TY1334 FIGURE 2 STYLE 20 RECESSED ESCUTCHEO...

Страница 3: ...sprinkler systems the requirements for Dry System Water Delivery per the Section 8 3 4 3 of the 2010 edition of NFPA 13D apply For a residential hazard in no case shall the time of water delivery exceed 15 seconds for the most remote operating sprinkler Hydraulic Design NFPA 13D and 13R The minimum re quired sprinkler flow rate for systems designed to NFPA 13D or NFPA 13R are given in Tables A B C...

Страница 4: ...M 18 4 psi 1 27 bar 16 x 18 4 9 x 5 5 16 4 9 19 GPM 71 9 LPM 20 5 psi 1 41 bar 19 GPM 71 9 LPM 20 5 psi 1 41 bar 21 GPM 79 5 LPM 25 0 psi 1 72 bar 21 GPM 79 5 LPM 25 0 psi 1 72 bar 16 x 20 4 9 x 6 1 16 4 9 23 GPM 87 1 LPM 30 0 psi 2 07 bar 23 GPM 87 1 LPM 30 0 psi 2 07 bar 26 GPM 98 4 LPM 38 3 psi 2 64 bar 26 GPM 98 4 LPM 38 3 psi 2 64 bar Sidewall sprinklers where installed under a ceiling with a...

Страница 5: ... 4 9 23 GPM 87 1 LPM 30 0 psi 2 07 bar Not Applicable Not Applicable Not Applicable Sidewall sprinklers where installed under a ceiling with a slope greater than a 0 inch rise for a 12 inch run to a slope up to a 2 inch rise for a 12 inch run must be located per one of the following At the high positioned to discharge down the slope Along the slope and positioned to discharge across the slope a Fo...

Страница 6: ...7 bar I 14 GPM 53 0 LPM 11 1 psi 0 77 bar I 17 GPM 64 3 LPM 16 4 psi 1 13 bar I 17 GPM 64 3 LPM 16 4 psi 1 13 bar 16 x 16 4 9 x 4 9 16 4 9 I 16 GPM 60 6 LPM 14 5 psi 1 00 bar I 16 GPM 60 6 LPM 14 5 psi 1 00 bar I 18 GPM 68 1 LPM 18 4 psi 1 27 bar I 18 GPM 68 1 LPM 18 4 psi 1 27 bar 16 x 18 4 9 x 5 5 16 4 9 I 19 GPM 71 9 LPM 20 5 psi 1 41 bar I 19 GPM 71 9 LPM 20 5 psi 1 41 bar I 21 GPM 79 5 LPM 25...

Страница 7: ...LPM 18 4 psi 1 27 bar 14 x 14 4 3 x 4 3 14 4 3 II 16 GPM 60 6 LPM 14 5 psi 1 00 bar II 16 GPM 60 6 LPM 14 5 psi 1 00 bar II 18 GPM 68 1 LPM 18 4 psi 1 27 bar II 18 GPM 68 1 LPM 18 4 psi 1 27 bar 16 x 16 4 9 x 4 9 16 4 9 II 16 GPM 60 6 LPM 14 5 psi 1 00 bar II 16 GPM 60 6 LPM 14 5 psi 1 00 bar II 18 GPM 68 1 LPM 18 4 psi 1 27 bar II 18 GPM 68 1 LPM 18 4 psi 1 27 bar 16 x 18 4 9 x 5 5 16 4 9 II 22 G...

Страница 8: ... C 12 x 12 3 7 x 3 7 12 3 7 III 16 GPM 60 6 LPM 14 5 psi 1 00 bar III 16 GPM 60 6 LPM 14 5 psi 1 00 bar 14 x 14 4 3 x 4 3 14 4 3 III 16 GPM 60 6 LPM 14 5 psi 1 00 bar III 16 GPM 60 6 LPM 14 5 psi 1 00 bar 16 x 16 4 9 x 4 9 16 4 9 III 16 GPM 60 6 LPM 14 5 psi 1 00 bar III 16 GPM 60 6 LPM 14 5 psi 1 00 bar 16 x 18 4 9 x 5 5 16 4 9 N A N A 16 x 20 4 9 x 6 1 16 4 9 N A N A a For coverage area dimensio...

Страница 9: ...e Series LFII Residential Sprinkler and push the Closure over the Mounting Plate until its flange comes in contact with the ceiling Care and Maintenance The RAPID RESPONSE Series LFII Residential Horizontal and Recessed Horizontal Sidewall Sprinklers TY1334 must be maintained and serviced in accordance with the following instructions NOTICE Before closing a fire protection system main control valv...

Страница 10: ...ncluding but not limited to labor charges regardless of whether TFSBP was informed about the possi bility of such damages and in no event shall TFSBP s liability exceed an amount equal to the sales price The foregoing warranty is made in lieu of any and all other warranties express or implied including warran ties of merchantability and fitness for a particular purpose This limited warranty sets f...

Отзывы: