TFP1253

Page 3 of 8

sprinkler systems. The air compressors 

work in conjunction with the NG-1 1150, 

NG-1 1500, NG-1 2000, and NG-1 3000 

Nitrogen Generators in a typical dry or 

preaction fire sprinkler system. It is also 

a plant nitrogen source for wet pipe fire 

sprinkler systems used with the NG-1 

1500, NG-1 2000, and NG-1 3000 

Nitrogen Generators.
The NG1 Air Compressors consists of 

the following features:

TNGC-1150

•  5 hp
•  Used with Model NG-1 1150
•  Air receiver tank:

 

Americas: 60 gal (227 L); vertical

 

EMEA, APAC: 71 gal (270 L); 

horizontal

TNGC-1500/2000

•  7.5 hp 
•  Used with Model NG-1 1500 or NG-1 

2000

•  Air Receiver Tank:

 

Americas: 80 gal (303 L); with 

after cooler; vertical

 

EMEA, APAC: 71 gal (270 L); 

horizontal

TNGC-3000

•   10 hp
•  Used with Model NG-1 3000
•  Air Receiver Tank

 

Americas: 120 gal (488 L); with 

after cooler; vertical

 

EMEA, APAC: 71 gal (270 L); 

horizontal

NOTICE

The TYCO Model NG-1 1150, NG-1 

1500, NG-1 2000, and NG-1 3000 

Stand-Alone Nitrogen Generator 

described herein must be installed 

and maintained in compliance with this 

document, as well as with the applica-

ble standards of the  NATIONAL FIRE 

PROTECTION ASSOCIATION, in addi-

tion to the standards of any authorities 

having jurisdiction, such as FM Global. 

Failure to do so may impair the perfor-

mance of these devices.
The owner is responsible for main-

taining their fire protection system 

and devices in proper operating con-

dition. Contact the installing contrac-

tor or product manufacturer with any 

questions.
In all cases, the appropriate NFPA or 

FM Global installation standard, or 

other applicable standard, must be 

referenced to ensure applicability and 

to obtain complete installation guide-

lines. The general guidelines in this 

data sheet are not intended to provide 

complete installation criteria.

Technical 

Data

NG-1 Nitrogen Generators

Approvals

FM Approved 

Compliance with CE Pressure Equipment 

UL508A Listed Industrial Control Panel

Cabinet Dimensions

See Table A

Weight

See Table A

Operating Performance

See Table B

Temperature Range

40

°

F (5

°

C) to 105

°

F (40

°

C)

Power Supply

120 VAC/Single 1 phase/60Hz (dedicated 

circuit) 

230 VAC/Single phase/50Hz (dedicated 

circuit)

Power Consumption

2 amps

Gas Connection

Air Inlet - 1/2 in. NPT Female 

Nitrogen Outlet - 1/2 in. NPT Female

Drain Connection

1/4 in. NPT Connection

Nitrogen Quality

N

2

 Purity at Discharge: 98% or greater 

(maximum of 2.0% oxygen)
N

Pressure at Discharge: Minimum of 

15 psig (1 bar); Max of feed air pressure 

minus 15 psig (1 bar)
N

Water Dew Point: Typically less than 

-70

°

F (-57

°

C)

Note

: When connecting a TYCO Stand-

Alone Nitrogen Generator to an existing 

dry pipe/preaction fire sprinkler system, 

the existing fire sprinkler system(s) must be 

limited to a maximum leak rate of less than 

6 psig (0.4 bar) within a 24 hour period, per 

system.

NG1 Compressors

Air Compressor Dimensions

See Table C

Weight

See Table C

Operating Performance

See Table B

Temperature Range

40

°

F (5

°

C) to 105

°

F (40

°

C)

Power Supply

Americas:

•  460 VAC/Three phase/60 Hz (Standard)
•  208 VAC/Three phase/60 Hz (Optional)

EMEA and APAC:

•  400 VAC/Single phase/50Hz (Standard)

Note: 

Other configurations are available. 

Contact Johnson Controls Technical Ser-

vices for more information.

Auto Drain

•  120 VAC/Single phase/60Hz
•  220 VAC/1 phase/50Hz

Note:

 The auto drain can be connected 

to the Nitrogen Generator cabinet power 

supply.

Power Consumption

Americas:

TNGC-1150 

7.6 Amps @ 460 VAC

 

 

17.5 Amps @ 208 VAC

TNGC-1500/2000 

11 Amps @ 460 VAC

 

 

25.3 Amps @ 208 VAC

TNGC-3000 

14 Amps @ 460 VAC

 

32.2 Amps @ 208 VAC

Model 

Number

Width 

Inches (mm)

Length 

Inches (mm)

Height 

Inches (mm)

Weight 

Lbs (kg)

Americas

RoW

Americas

RoW

Americas

RoW

Americas

RoW

TNGC-1150

20 (508)

23.9 (606)

32 (813)

62.4 (1584)

70 (1778)

43.7 (1111)

435 (197)

295.4 (134)

TNGC-1500/2000

23.6 (599)

23.3 (592)

38.1 (968)

60.6 (1540)

70.1 (1781)

47.2 (1200)

573 (260)

416.7 (189)

TNGC-3000

43.2(1097)

23.9 (606)

30 (762)

60.6 (1540)

76.6 (1946)

47.2 (1200)

800 (362)

443.2 (201)

NOTES

•  RoW = Rest of World - the EMEA and APAC regions.

TABLE C 

MODEL NG1 COMPRESSOR DIMENSIONS AND WEIGHT -  

AMERICAS AND REST OF WORLD REGIONS

Содержание NG-1 1150

Страница 1: ...to TFP1262 for more information on TYCO Dry Air Vent TAV D and to TFP1263 for more information on TYCO SMART Air Vent TSV D System Assembly The TYCO Nitrogen Generator unit includes the following comp...

Страница 2: ...605 1150 4353 2300 8706 NG 1 1500 24 3 688 11000 41640 1440 5451 2880 10902 NG 1 2000 24 688 18500 70030 2025 7666 4050 15331 NG 1 3000 35 992 22500 85172 2900 10978 5800 21955 Notes a Capacity based...

Страница 3: ...l Cabinet Dimensions See Table A Weight See Table A Operating Performance See Table B Temperature Range 40 F 5 C to 105 F 40 C Power Supply 120 VAC Single 1 phase 60Hz dedicated circuit 230 VAC Single...

Страница 4: ...panel for wall mount ing using standard anchors Step 2 Power Supply The Nitrogen Generator requires a ded icated power supply that connects to the terminal blocks in the nitrogen gen erator cabinet Se...

Страница 5: ...ENERATOR RUNNING OUTPUT BYPASS MODE ALARM OUTPUT LEAK MONITORING OUTPUT POWER ON OFF OUTPUT NITROGEN SUPPLY LINE PRESSURE OUTPUT L1 N G PRESSURE SWITCH INCOMING POWER FUSE BOX BUILDING MANAGEMENT SYST...

Страница 6: ...compressors in EMEA and APAC the air discharge plumb ing should first be connected to the WSD 25 water separator which then is to be connected to the inlet of the nitro gen generator Step 4 Plumb the...

Страница 7: ...gen separation membrane will provide up to 20 years of service life Filter Replacement Procedure With reference to Figure 4 perform the following steps when replacing the cartridge filters located in...

Страница 8: ...10 Close the depressurization ball valve The Nitrogen Generator can now be placed back into service Step 11 Turn the power supply to the unit ON Step 12 Close the Bypass Ball Valve Step 13 Open the In...

Отзывы: