Cellular Receiver 2 Options

2G Alarm Communicator Installlation Manual

20

[203] Cellular Receiver 1 Address

Default (000.000.000.000)

Enter the Cellular Receiver 1 IP address. This information will be provided by your central station system administrator. Each 3 digit
segment of the address must be within a valid range of 000-255.

NOTE: 

When a valid IP address has been entered, the Cellular is enabled and will communicate events over the Cellular channel.

[204] Cellular Receiver 1 Port

Default (0BF5/3061)

This Section determines the port used by Cellular Receiver 1. Change the default value of this port when your installation is located
behind a firewall, and must be assigned a particular port number as determined by your central station system administrator. Valid
range: 0000 - FFFF.

NOTE: 

Programming this Section with 0000 will disable the receiver.

[205] Cellular Receiver 1 APN

Default (  )

The Access Point Name (APN) determines the Cellular network that the Communicator will connect to. This information is available
from your network carrier. Program this Section as 32 ASCII characters.

NOTE: 

When a SIM card with a custom APN is used, the unit will not have access to the Internet. DLS and remote flash can still be

done if Section [221] is programmed with a valid Public APN.

[206] Cellular Receiver 1 Domain Name

Default (  )

Programming this Section is 

not

  permitted on a UL/ULC  listed system.

Enter the Domain Name as 32 ASCII characters. This information will be provided by your central station system administrator.

C

ELLULAR

 R

ECEIVER

 2 O

PTIONS

[211] Cellular Receiver 2 Account Code

Default (0000000000)

The account code is used by the central station to distinguish between different transmitters. This account code is used when transmit-
ting signals to the central station receiver. Signals received on the panel will use the panel account number. Valid range: 000000000

1

 -

FFFFFFFFF

E

NOTE: 

Programming this Section as all 0 or F will cause a Module Configuration Trouble (yellow LED = 12 flashes).

[212] Cellular Receiver 2 DNIS

Default (000000)

The DNIS is used in addition to the Account Code to identify the Communicator module at the central station. Valid range: 000000 -

0

99999. Values are entered as a 0 followed by the 5 digit DNIS value. Format is BCD.

NOTE: 

Each Ethernet/Cellular receiver must be programmed with a unique DNIS.

[213] Cellular Receiver 2 Address

Default (000.000.000.000)

Enter the Cellular Receiver 2 IP address. This IP address will be provided by your central station. Format is 4 fields, each field is 3 digit
decimal. Valid range: 000 - 255.

NOTE: 

When a valid address has been entered, Cellular Receiver 2 is enabled and will communicate events over the Cellular path. 

[214] Cellular Receiver 2 Port

Default (0BF5/3061)

This Section defines the port of Cellular Receiver 2. Change the value of this port when your installation is located behind a firewall,
and must be assigned a particular port number, as determined by your central station system administrator. Valid range: 0000 - FFFF.

NOTE: 

Do not program Cellular Receiver 1 and Cellular Receiver 2 to communicate to the same receiver.

[215] Cellular Receiver 2 APN

Default (  )

The APN determines the Cellular network that the Communicator will connect to. This information is available from your network car-
rier. Program this Section with up to 32 ASCII characters.

NOTE: 

When a SIM card with a custom APN is used, the unit will not have access to the internet. DLS and remote flash can still be

done if Section [221] is programmed with a valid Public APN.

[216] Cellular Receiver 2 Domain Name

Default (  )

Programming this Section is 

not

 permitted on a UL/ULC listed system.

Enter the Cellular Receiver 2 Domain Name with up to 32 ASCII characters.

C

ELLULAR

 O

PTIONS

[221] Cellular Public Access Point Name

Default (  )

When the Communicator is operating on a private APN, use this Section to select a public APN for DLS and Remote Firmware Update.
This information is available from your network carrier. The APN identifies the public Cellular network that the Communicator will
connect to.

firealarmresources.com

Содержание DSC GS2055

Страница 1: ...Installation Manual v2 5 Warning This manual contains information on limitations regarding product use and function and information on the limitations as to liability of the manufacturer NOTE This man...

Страница 2: ...firealarmresources com...

Страница 3: ...g Options Sections Ethernet Cellular Programming Options 11 System Options 11 Programming Options 13 Communications Reporting Codes 16 Ethernet Receiver 1 Options 18 Ethernet Receiver 2 Options 18 Eth...

Страница 4: ...y not occur in time to protect the occupants or their belongings Motion Detectors Motion detectors can only detect motion within the designated areas as shown in their respective installation instruct...

Страница 5: ...rn to normal entry NOTE Authorized access to Connect24 GS2055 TL255GS or DLS IV is required to modify any Ethernet Cellular Programming Section Specific panel Sections must be configured for proper op...

Страница 6: ...TION REQUIREMENTS For ULC Residential fire and burglary applications the GS2055 TL255GS can be used as primary communication channel via either Cellular or Ethernet as applicable or as a back up in co...

Страница 7: ...monitoring station to determine if it is a master re seller or visit http www Connect24 com to become an authorized dealer In either instance you will require a Profile Number Installer ID Number and...

Страница 8: ...sons only Service Person is defined as a person having appropriate technical training and expe rience necessary to be aware of hazards to which that person may be exposed in performing a task and of m...

Страница 9: ...d any values that are modified from their default in the appropriate Programming Worksheets NOTE When programming Toggle Options the toggle is ON when the number is displayed and OFF when the number i...

Страница 10: ...ramming and scrolling down to Cellular phone No LABEL PROGRAMMING for SMS MESSAGE Programmable Labels can not be modified in Connect24 use DLS IV for label programming only if labels need to be modifi...

Страница 11: ...to Ethernet Receiver 1 or Cel lular Receiver 1 to test the communications path Use this Section to set the interval time in seconds when heartbeats will be sent to the receivers Valid range 000A FFFF...

Страница 12: ...the programmed receivers based on the settings of the periodic test transmission reporting codes 8 Cellular Low Signal Trouble Default OFF This option masks the Low Signal trouble from the Cellular tr...

Страница 13: ...13 DLS Outgoing Port Default 0BFA 3066 The DLS Outgoing Port is used for outgoing session to DLS IV after an SMS request has been sent to the Communicator Use this Sec tion to set the value of the loc...

Страница 14: ...Brazil Western Standard Time PST Philippine Standard Time SLT San Luis Time PIT Pratas Islands PYT Paraguay Time PIT Parcel Island Time JFST Juan Fernandez Island Standard Time MYT Malaysia Time GYT...

Страница 15: ...Time PONT Phonpei Standard Time IST Israel Standard Time MAGT Magadan Island Time 3D 3 MSK Moscow Standard Time 5F 11 5 NFT Norfolk Island Time EAT Eastern Africa Time 61 12 NZST New Zealand Standard...

Страница 16: ...cur when communications with the panel have been lost for more than 60 seconds 024 Panel Absent Trouble Restore Default FF Program 00 to disable this event or FF to enable This event will occur when c...

Страница 17: ...n settings NOTE The time interval in minutes between periodic tests is programmed in Section 125 Ethernet and Section 225 Cellular 030 FTC Restore Default FF Program 00 to disable this event transmiss...

Страница 18: ...igure the device to operate using this Common Receiver Mode functionality program Ethernet Receiver 1 and Cellular Receiver 1 IP address and port number with identical values NOTE When operating in Co...

Страница 19: ...ocated behind a firewall and must be assigned a particular port number as determined by your network administrator Valid range 0000 FFFF NOTE Do not program Ethernet Receiver 1 and Ethernet Receiver 2...

Страница 20: ...F will cause a Module Configuration Trouble yellow LED 12 flashes 212 Cellular Receiver 2 DNIS Default 000000 The DNIS is used in addition to the Account Code to identify the Communicator module at th...

Страница 21: ...lay Valid entries are 00 FF e g for a 10 min ute Cellular Trouble Delay enter 0A There is no reporting delay if value is programmed as 00 227 Voice Call Timeout Default 00 This option sets the Voice C...

Страница 22: ...2 1234 unsuccessful The partition label or partition number may be excluded from the SMS request in a single partition system e g disarm 9123 NOTE The communicator cellular phone number can be viewed...

Страница 23: ...ul Default Unsuccessful When an SMS Command and Control function is not successfully performed by the panel the command sent to the unit will be included in the response sent to the user followed by t...

Страница 24: ...t Boot Loader version of the Communicator 991 Firmware Version This Section will display the current firmware version of the device Update worksheets with new version after a flash update is com plete...

Страница 25: ...Body Identifier 2 digits Allocation Number 4 digits Final Assembly Code 2 digits Serial Number 6 digits and a check digit 998 MAC Address This Section will display the unique12 digit hexadecimal numb...

Страница 26: ...tus codes will indicate the signal levels with digit 1 and 2 a network status with digit 3 and the trouble status with digit 4 and 5 as indicated in table above For example status code 11000F would di...

Страница 27: ...rouble Check with your ISP to confirm Internet service is active in your area Ensure your Ethernet cable is securely inserted into the RJ45 jack of the Communicator and the Hub Router Switch Check the...

Страница 28: ...d No Signal 0 0 0 108 8 bad Check all antenna connections Confirm 2G service is active in area Relocate Panel or install external antenna 1 Bar 1 4 0 2 108 103 weak Relocate Panel or install external...

Страница 29: ...FFFF ____ ____ ____ ____ 011 Installer Code Default CAFE Valid range 0000 FFFF ____ ____ ____ ____ 012 DLS Incoming Port Default 0BF6 3062 Valid range 0000 FFFF ____ ____ ____ ____ 013 DLS Outgoing P...

Страница 30: ...ULAR RECEIVER 1 OPTIONS 201 Cellular Receiver 1 Account Code Default 0000000000 Valid range 0000000001 FFFFFFFFFE ____ ____ ____ ____ ____ ____ ____ ____ ____ ____ 202 Cellular Receiver 1 DNIS Default...

Страница 31: ...this command to the system to night disarm ____________________________________ 605 608 Activate Command Output 1 4 Default Activate Command Output n Send this command to the system to activate a comm...

Страница 32: ...arm Memory Included in the response to the Alarm Memory command if there are no alarms on the system ____________________________________ 634 Error Code Default Error Code Included in the response to...

Страница 33: ...s any upgrades and this EULA and provided the recipient agrees to the terms of this EULA If the SOFTWARE PRODUCT is an upgrade any transfer must also include all prior versions of the SOFTWARE PRODUCT...

Страница 34: ...red in such a manner as to adversely affect performance or prevent adequate inspection or testing to verify any warranty claim Access cards or tags returned for replacement under warranty will be cred...

Страница 35: ...firealarmresources com...

Страница 36: ...evision Interference Problems This booklet is available from the U S Government Printing Office Washington D C 20402 Stock 004 000 00345 4 WARNING TO SATISFY FCC RF EXPOSURE REQUIREMENTS FOR MOBILE TR...

Отзывы: