2G Alarm Communicator Installlation Manual

System Options

11

The Programming Sections described in this document can be viewed at the SCW9055/SCW9057 LCD. To start programming enter:

[*][8][installer  code]  [851][# # # ]

,  Where  # # #   is  the  3  digit  Section  number  referenced  in  this  section.  The  Programming  Worksheets

at the end of this document can be used to record the new values when programming changes have been made from the default values.
Programming Sections are accessed through Connect24. Installers may 

review/record

 programming Options at the panel.

NOTE: 

Ethernet/Cellular Programming Sections accessed through the panel are for 

display purposes only

. Configuration changes 

must be done using Connect24.

S

YSTEM

 O

PTIONS

[001] Ethernet IP Address

Default (000.000.000.000)

Enter the IP address of the Communicator. Ensure that the IP address is unique to your Communicator on the local network. Format is
4 fields, each field is a 3 digit decimal number. Valid range: 000-255. If an IP address is programmed in this Section, the unit will oper-
ate with Static IP (DHCP disabled). Sections [002] and [003] must also be programmed when using Static IP addresses.

NOTE: 

 Default for this Section is Dynamic Host Configuration Protocol (DHCP) enabled. When enabled, the DHCP Server will set

values for: IP Address [001], Subnet Mask [002], and Gateway [003]. Programming an IP address in this Section will disable
DHCP (Static IP).

[002] Ethernet IP Subnet Mask

Default (255.255.255.000)

Enter the Ethernet IP Subnet Mask of the Communicator. Format is 4 fields, each field is 3 digits. Valid range: 000-255.

NOTE: 

If DHCP is enabled, the DHCP Server will assign the subnet mask for this Section and the programmed value will be ignored.

[003] Ethernet Gateway IP Address

Default (000.000.000.000)

Enter the Ethernet Gateway IP address of the Communicator. The gateway IP address is required when a router is used on the local net-
work to reach the destination IP address specified in Section [001]. Format is 4 fields, each field is a 3 digit decimal number. Valid
range: 000-255.

NOTE: 

If DHCP is enabled, the DHCP Server will assign the Gateway IP address for this Section and the programmed value will be

ignored.

[004] Receiver Supervision Interval

Default (0087/135)

When receiver supervision is enabled (ON) in Section [005] Toggle Option [3], the unit sends heartbeats to Ethernet Receiver 1 or Cel-
lular Receiver 1 to test the communications path. Use this Section to set the interval time (in seconds) when heartbeats will be sent to
the receivers. Valid range 000A-FFFF seconds. If the programmed value is less than (000A/10) seconds, supervision is disabled.

Receiver Window: 

This is the supervision timeout that must be configured at the central station receiver.

Recommended Values:

 This is the recommended heartbeat interval that should be programmed into the Communicator.

• For ULC installations, the Daily test transmission must be enabled over each available communication channel Sections [125] and

[225]. When programming with Connect24, the recommended intervals will be programmed automatically when the required win-
dow is selected.

[005] System Toggle Options
[1] Ethernet Receiver 1 Supervised

Default (OFF)

(

TL255GS

 only).

ON

: Ethernet Receiver 1 will be supervised and heartbeats will be sent to Ethernet Receiver 1 based on the supervision interval pro-

grammed in Section [004].

OFF

: Ethernet Receiver 1 will not be supervised. When disabled, heartbeat 1 is sent to the Ethernet receiver once every hour, regard-

less of supervision type (heartbeat 1 or 2). The heartbeat is resent every 5 seconds until ACK. If no event or heartbeat ACK is received
after (Receiver Supervision In 75 seconds), Supervisory trouble is indicated.

NOTE: 

Ethernet Receiver 2 can not be supervised.

[2] Cellular Receiver 1 Supervised

Default (OFF)

ON

: Cellular Receiver 1 will be supervised and heartbeats will be sent to Cellular Receiver 1 based on the supervision interval pro-

grammed in Section [004]. If ACK to heartbeat is not received, it is retransmitted every 5 seconds. Failure to ACK 2 consecutive heart-
beats will reset the radio.

OFF

: Cellular Receiver 1 will not be supervised. When disabled, heartbeat is not sent to the receiver. Supervisory trouble is indicated.

NOTE: 

 Cellular Receiver 2 can not be supervised.

[3] Supervision Type

Default (OFF)

ON

: Heartbeat 1 (Commercial Supervision). This supervision type is suitable for applications where swap detection is required on the

supervisory packet.

OFF

: Heartbeat 2 (Residential Supervision). This supervision type is suitable for applications where supervision of the communication

path to the receiver is required. (no swap detection).

NOTE: 

Commercial supervision is more data intensive than residential supervision and should only be used when required to meet the 

approval for the installation.

E

THERNET

/C

ELLULAR

 P

ROGRAMMING

 O

PTIONS

firealarmresources.com

Содержание DSC GS2055

Страница 1: ...Installation Manual v2 5 Warning This manual contains information on limitations regarding product use and function and information on the limitations as to liability of the manufacturer NOTE This man...

Страница 2: ...firealarmresources com...

Страница 3: ...g Options Sections Ethernet Cellular Programming Options 11 System Options 11 Programming Options 13 Communications Reporting Codes 16 Ethernet Receiver 1 Options 18 Ethernet Receiver 2 Options 18 Eth...

Страница 4: ...y not occur in time to protect the occupants or their belongings Motion Detectors Motion detectors can only detect motion within the designated areas as shown in their respective installation instruct...

Страница 5: ...rn to normal entry NOTE Authorized access to Connect24 GS2055 TL255GS or DLS IV is required to modify any Ethernet Cellular Programming Section Specific panel Sections must be configured for proper op...

Страница 6: ...TION REQUIREMENTS For ULC Residential fire and burglary applications the GS2055 TL255GS can be used as primary communication channel via either Cellular or Ethernet as applicable or as a back up in co...

Страница 7: ...monitoring station to determine if it is a master re seller or visit http www Connect24 com to become an authorized dealer In either instance you will require a Profile Number Installer ID Number and...

Страница 8: ...sons only Service Person is defined as a person having appropriate technical training and expe rience necessary to be aware of hazards to which that person may be exposed in performing a task and of m...

Страница 9: ...d any values that are modified from their default in the appropriate Programming Worksheets NOTE When programming Toggle Options the toggle is ON when the number is displayed and OFF when the number i...

Страница 10: ...ramming and scrolling down to Cellular phone No LABEL PROGRAMMING for SMS MESSAGE Programmable Labels can not be modified in Connect24 use DLS IV for label programming only if labels need to be modifi...

Страница 11: ...to Ethernet Receiver 1 or Cel lular Receiver 1 to test the communications path Use this Section to set the interval time in seconds when heartbeats will be sent to the receivers Valid range 000A FFFF...

Страница 12: ...the programmed receivers based on the settings of the periodic test transmission reporting codes 8 Cellular Low Signal Trouble Default OFF This option masks the Low Signal trouble from the Cellular tr...

Страница 13: ...13 DLS Outgoing Port Default 0BFA 3066 The DLS Outgoing Port is used for outgoing session to DLS IV after an SMS request has been sent to the Communicator Use this Sec tion to set the value of the loc...

Страница 14: ...Brazil Western Standard Time PST Philippine Standard Time SLT San Luis Time PIT Pratas Islands PYT Paraguay Time PIT Parcel Island Time JFST Juan Fernandez Island Standard Time MYT Malaysia Time GYT...

Страница 15: ...Time PONT Phonpei Standard Time IST Israel Standard Time MAGT Magadan Island Time 3D 3 MSK Moscow Standard Time 5F 11 5 NFT Norfolk Island Time EAT Eastern Africa Time 61 12 NZST New Zealand Standard...

Страница 16: ...cur when communications with the panel have been lost for more than 60 seconds 024 Panel Absent Trouble Restore Default FF Program 00 to disable this event or FF to enable This event will occur when c...

Страница 17: ...n settings NOTE The time interval in minutes between periodic tests is programmed in Section 125 Ethernet and Section 225 Cellular 030 FTC Restore Default FF Program 00 to disable this event transmiss...

Страница 18: ...igure the device to operate using this Common Receiver Mode functionality program Ethernet Receiver 1 and Cellular Receiver 1 IP address and port number with identical values NOTE When operating in Co...

Страница 19: ...ocated behind a firewall and must be assigned a particular port number as determined by your network administrator Valid range 0000 FFFF NOTE Do not program Ethernet Receiver 1 and Ethernet Receiver 2...

Страница 20: ...F will cause a Module Configuration Trouble yellow LED 12 flashes 212 Cellular Receiver 2 DNIS Default 000000 The DNIS is used in addition to the Account Code to identify the Communicator module at th...

Страница 21: ...lay Valid entries are 00 FF e g for a 10 min ute Cellular Trouble Delay enter 0A There is no reporting delay if value is programmed as 00 227 Voice Call Timeout Default 00 This option sets the Voice C...

Страница 22: ...2 1234 unsuccessful The partition label or partition number may be excluded from the SMS request in a single partition system e g disarm 9123 NOTE The communicator cellular phone number can be viewed...

Страница 23: ...ul Default Unsuccessful When an SMS Command and Control function is not successfully performed by the panel the command sent to the unit will be included in the response sent to the user followed by t...

Страница 24: ...t Boot Loader version of the Communicator 991 Firmware Version This Section will display the current firmware version of the device Update worksheets with new version after a flash update is com plete...

Страница 25: ...Body Identifier 2 digits Allocation Number 4 digits Final Assembly Code 2 digits Serial Number 6 digits and a check digit 998 MAC Address This Section will display the unique12 digit hexadecimal numb...

Страница 26: ...tus codes will indicate the signal levels with digit 1 and 2 a network status with digit 3 and the trouble status with digit 4 and 5 as indicated in table above For example status code 11000F would di...

Страница 27: ...rouble Check with your ISP to confirm Internet service is active in your area Ensure your Ethernet cable is securely inserted into the RJ45 jack of the Communicator and the Hub Router Switch Check the...

Страница 28: ...d No Signal 0 0 0 108 8 bad Check all antenna connections Confirm 2G service is active in area Relocate Panel or install external antenna 1 Bar 1 4 0 2 108 103 weak Relocate Panel or install external...

Страница 29: ...FFFF ____ ____ ____ ____ 011 Installer Code Default CAFE Valid range 0000 FFFF ____ ____ ____ ____ 012 DLS Incoming Port Default 0BF6 3062 Valid range 0000 FFFF ____ ____ ____ ____ 013 DLS Outgoing P...

Страница 30: ...ULAR RECEIVER 1 OPTIONS 201 Cellular Receiver 1 Account Code Default 0000000000 Valid range 0000000001 FFFFFFFFFE ____ ____ ____ ____ ____ ____ ____ ____ ____ ____ 202 Cellular Receiver 1 DNIS Default...

Страница 31: ...this command to the system to night disarm ____________________________________ 605 608 Activate Command Output 1 4 Default Activate Command Output n Send this command to the system to activate a comm...

Страница 32: ...arm Memory Included in the response to the Alarm Memory command if there are no alarms on the system ____________________________________ 634 Error Code Default Error Code Included in the response to...

Страница 33: ...s any upgrades and this EULA and provided the recipient agrees to the terms of this EULA If the SOFTWARE PRODUCT is an upgrade any transfer must also include all prior versions of the SOFTWARE PRODUCT...

Страница 34: ...red in such a manner as to adversely affect performance or prevent adequate inspection or testing to verify any warranty claim Access cards or tags returned for replacement under warranty will be cred...

Страница 35: ...firealarmresources com...

Страница 36: ...evision Interference Problems This booklet is available from the U S Government Printing Office Washington D C 20402 Stock 004 000 00345 4 WARNING TO SATISFY FCC RF EXPOSURE REQUIREMENTS FOR MOBILE TR...

Отзывы: