Overview,
Continued
The first programming step is to select the application mode (i.e., Agent Release, Single Hazard,
Cross Zoned, Combined Release, etc.). The AutoPulse Z-10 can be programmed with any one of
13 agent release or Preaction/Deluge application modes.
Note:
Refer to Table 1-2 in Chapter 1 for a summary of each application mode.
Method Description
Text-Based
Programming
The first prompt, shown below, queries you to select the application mode.
[01] APPLICATION MODE:
d*1 = Agent Release, Single Hazard, Cross Zoned, Combined Release
2 = Agent Release, Single Hazard, Non-Cross Zoned, Combined Release
3 = Agent Release, Dual Hazard, Cross Zoned
4 = Agent Release, Dual Hazard, Non-Cross Zoned
5 = Preaction/Deluge, Single Hazard, Cross Zoned, Combined Release
6 = Preaction/Deluge, Single Hazard, Non-Cross Zoned, Combined Release
7 = Preaction/Deluge, Dual Hazard, Cross Zoned
8 = Preaction/Deluge, Dual Hazard, Non-Cross Zoned
9 = Agent Release, Single Hazard, Cross-Zoned, NYC abort
10 = Agent Release and Preaction/Deluge, Single Hazard, Cross-Zoned, Combined
Release
11 = Agent Release and Preaction/Deluge, Single Hazard, Combined Release
12 = Agent Release, Single Hazard, Cross-Zoned, Bell/Horn/Strobe
13 = Agent Release, Single Hazard, Bell/Horn/Strobe
(d=default, *=current setting)
Select Number(X=exit):
Enter the number corresponding to the application mode you want to select and press the carriage return. Refer
to “Programming the Relay Option” in the next section for a description of the next programming step.
Front Panel
Programming
The top LED (red) on the left side of the display is lit to indicate the application mode is being programmed. The
top LED on the right side of the display is lit to indicate the default application (Agent Release, 1 Hazard, Cross
Zoned, Combined RAC) that is currently selected.
Press ACK to use the default. To choose a different application, do the following:
1.
Press the RESET key to move down through the list of available applications. Each time you press this
key, the illuminated LED on the right side of the panel changes to the next one down. If none of the first
nine applications are selected, the second application mode menu will appear. It is shown on the next
page. (Refer to the figure below for the relationship between the LEDs and applications.)
2.
When the LED corresponding to the desired application is illuminated, press the ACK key. This saves the
selection in memory and moves you to the next programming step.
Programming the Application Mode
Overview
When top LED (red) on left
side of display is lit, it
indicates that the
application mode is being
programmed.
These LEDs represent the
available application
selections. Use the
RESET key to move
through the choices.
Press ACK when the
illuminated LED
corresponds to the
desired choice.
Yellow Trouble LED lit to
indicate panel is in
programming mode.
Green LED is AC Power.