1-4
Table 1-1. AutoPulse Z-10 Original 9 Applications With Original Relay Operation
Releasing Application
IDC 1
IDC 2
IDC 3
IDC 4
SPM1
SPM2
NAC1
NAC2
RAC1
RAC2
Timers
Panel Aux Relays
Relay Exp Board 1 (Hazard 1)
Relay Exp Board 2 (Hazard 2)
Notes 1, 2, & 3
Note 4
Notes 4
& 5
Abort
Rel.
Aux1
Aux2
Aux3
Relay 1
Relay 2
Relay 3
Relay 4
Relay 1
Relay 2
Relay 3
Relay 4
1. Agent Release, Single Hazard, Cross-Zoned, Combined Release
Stage 1 - 1st Alarm
IDC 1 or 2 Alarm
Abort
MS
Steady Optional
Opt
TBL Alarm
Supv or
Start
Release
Timer
(select.)
Trouble Alarm
2nd
Cross-
Zone
Alarm
Discharge Trouble Alarm
2nd
Cross-
Zone
Alarm
Discharge
Stage 2 - Alarm Confirmed
IDC 1 & 2 Alarm
Steady
120bpm
Opt
Start
Stage 3 - Release
Alarm
Steady Steady ON
ON
Expired
Pressure Switch Alarm
Pressure
Steady
Steady
Tamper Switch (Supervisory)
Supv.
Optional
2. Agent Release, Single Hazard, Combined Release
Stage 1 - Alarm
IDC 1 or 2 Alarm
Abort
MS
Steady 120bpm
Opt
Start
TBL Alarm
Supv Or
Pressure
(select.)
Trouble Alarm
Pressure
Switch
Alarm
Discharge Trouble Alarm
Pressure
Switch
Alarm
Discharge
Stage 2 - Release
Alarm
Steady Steady ON
ON
Expired
Pressure Switch Alarm
Pressure
Steady
Steady
Tamper Switch (Supervisory)
Supv.
Optional
3. Agent Release, Dual Hazard, Cross-Zoned
Hazard 1, Stage 1 - 1st Alarm
IDC 1 or 2 Alarm
Abort
MS
Optional
Opt
TBL
Hazard
1 Auto
or
Manual
Alarm
Hazard 2
Auto or
Manual
Alarm
System
or
Hazard
1 TBL
Hazard
1 Alarm
2nd
Cross-
Zone
Alarm
Hazard 1
Discharge
Hazard 1
System
or
Hazard
2 TBL
Hazard
2 Alarm
2nd
Cross-
Zone
Alarm
Hazard 2
Discharge
Hazard 2
Hazard 1, Stage 2 - Alarm Confirmed
IDC 1 & 2 Alarm
120bpm
Opt
Start
Hazard 1, Stage 3 - Release
Alarm
Steady
ON
Expired
Hazard 2, Stage 1 - 1st Alarm
IDC 3 or 4 Alarm
Abort
MS
Optional
Opt
Hazard 2, Stage 2 - Alarm Confirmed
IDC 3 & 4 Alarm
120bpm
Opt
Start
Hazard 2, Stage 3 - Release
Alarm
Steady
ON
Expired
4. Agent Release, Dual Hazard
Hazard 1, Stage 1 - Alarm
IDC 1 or 2 Alarm
Abort
MS
120bpm
Opt
Start
TBL
Hazard
1 Auto
or
Manual
Alarm
Hazard 2
Auto or
Manual
Alarm
System
or
Hazard
1 TBL
Hazard
1 Alarm
Start
Release
Timer
Hazard 1
Discharge
Hazard 1
System
or
Hazard
2 TBL
Hazard
2 Alarm
Start
Release
Timer
Hazard 2
Discharge
Hazard 2
Hazard 1, Stage 2 - Release
Alarm
Steady
ON
Expired
Hazard 2, Stage 1 - Alarm
IDC 3 or 4 Alarm
Abort
MS
120bpm
Opt
Start
Hazard 2, Stage 2 - Release
Alarm
Steady
ON
Expired
Releasing Application
IDC 1
IDC 2
IDC 3
IDC 4
SPM1 SPM2
NAC1
NAC2
RAC1
RAC2
Time-Limit
Cutout
Panel Aux Relays
Relay Exp Board 1 (Hazard 1)
Relay Exp Board 2 (Hazard 2)
Note 6
Aux1 Aux2
Aux3 Relay 1
Relay 2
Relay 3
Relay 4
Relay 1
Relay 2
Relay 3
Relay 4
5. Preaction/Deluge, Single Hazard, Cross-Zoned
Stage 1 - 1st Alarm
1st IDC in Alarm
Steady
Optional
Opt
TBL Alarm
Supv. or
Waterflow
(select.)
Trouble Alarm
2nd
Cross-
Zone
Alarm
Discharge Trouble Alarm
2nd
Cross-
Zone
Alarm
Discharge
Stage 2 - Alarm Confirmed / Release
2nd IDC in Alarm
Steady
Steady
ON
ON
Opt
Waterflow Alarm
WF
Steady
Steady
Note 7
Note 7
Supervisory Alert
Supv
Optional
6. Preaction/Deluge, Single Hazard, Combined Release
Releasing Alarm
Any 1 or more IDC's in Alarm
Steady
ON
ON
Opt
TBL Alarm
Supv. or
Waterflow
(select.)
Trouble Alarm Waterflow Discharge Trouble Alarm Waterflow Discharge
Waterflow Alarm
WF
Steady
Note 7
Note 7
Supervisory Alert
Supv
Optional
7. Preaction/Deluge, Dual Hazard, Cross-Zoned
Hazard 1, Stage 1 - Alarm
IDC 1 or 2 Alarm
Optional
Opt
TBL
Hazard
1
Alarm
Hazard 2
Alarm
System
or
Hazard
1 TBL
Hazard
1 Alarm
2nd
Cross-
Zone
Alarm
Hazard 1
Discharge
Hazard 1
System
or
Hazard
2 TBL
Hazard
2 Alarm
2nd
Cross-
Zone
Alarm
Hazard 2
Discharge
Hazard 2
Hazard 1, Stage 2 - Release
IDC 1 & 2 Alarm
Steady
ON
Opt
Hazard 2, Stage 1 - Alarm
IDC 3 or 4 Alarm
Optional
Opt
Hazard 2, Stage 2 - Release
IDC 3 & 4 Alarm
Steady
ON
Opt
Waterflow Alarm (both hazards)
WF
Steady
Steady
Note 7
Note 7
Supervisory Alert (both hazards, no NAC)
Supv
8. Preaction/Deluge, Dual Hazard
Hazard 1 - Releasing Alarm
IDC 1 or 2 Alarm
Steady
ON
Opt
TBL
Hazard
1
Alarm
Hazard 2
Alarm
System
or
Hazard
1 TBL
Hazard
1 Alarm
Waterflow
Hazard 1
or Hazard
2
Discharge
Hazard 1
System
or
Hazard
2 TBL
Hazard
2 Alarm
Waterflow
Hazard 1
or Hazard
2
Discharge
Hazard 2
Hazard 2 - Releasing Alarm
IDC 3 or 4 Alarm
Steady
ON
Opt
Waterflow Alarm (both hazards)
WF
Steady
Steady
Note 7
Note 7
Supervisory Alert (both hazards, no NAC)
Supv
Releasing Application
IDC 1
IDC 2
IDC 3
IDC 4
SPM1
SPM2
NAC1
NAC2
RAC1
NAC3
Timers
Panel Aux Relays
Relay Exp Board 1 (Hazard 1)
Relay Exp Board 2 (Hazard 2)
Note 8
Abort Rel. Aux1
Aux2 Aux3 Relay 1
Relay 2
Relay 3
Relay 4
Relay 1
Relay 2
Relay 3
Relay 4
9. Agent Release, Single Hazard, Cross-Zoned, NYC abort
Stage 1 - 1st Alarm
IDC 1 or 2 Alarm
Abort
MS
Steady
Opt
TBL Alarm
Supv. or
Start
Release
Timer
(select.)
Trouble Alarm
2nd
Cross-
Zone
Alarm
Discharge Trouble Alarm
2nd
Cross-
Zone
Alarm
Discharge
Stage 2 - Alarm Confirmed
IDC 1 & 2 Alarm
OFF
120bpm
Steady
Opt
Start
Abort switch pressed
Alarm
Steady
OFF
OFF
Opt
Suspend
Abort switch released
Alarm
Steady
OFF
OFF
Start
Investigate (Abort) Timer expired
Alarm
OFF
120bpm
Steady
Expired
Reload
Stage 3 - Release
Alarm
OFF Steady ON Steady Expired
Pressure Switch Alarm
Pressure
Steady
Steady
Tamper Switch (Supervisory)
Supv.
Optional
Style C Option
Releasing Application
IDC1 IDC2 IDC3 IDC4 SPM1
SPM2 NAC1 NAC2
RAC1
RAC2
Timers
Panel AUX Relays
Style C Option Agent Release
Style C Operation: Current limited equals an
alarm; short/open equals a trouble
Same as Agent Release applications above
except all IDCs operate Style C.
Abort
(Style C)
MS
(Style C)
Same as Agent Release applications above except SPM1 and SPM2 are associated with both hazards.
Style C Option Preaction Deluge
Style C Operation: Current limited equals an
alarm; short/open equals a trouble
Same as Preaction/Deluge applications above except all IDCs and SPMs
operate Style C.
Same as Preaction/Deluge applications above except SPM1 and SPM2 are associated with both hazards.
NOTES
:
1. SPM1 and SPM2 are combination Manual Release / Abort zones in Agent Release Dual Hazard applications only. A s
a Manual Release and a current limit is an Abort condition.
5. Where Temporal Code pattern is only allowed for evacuation signaling and the Audible NAC ope
Cross-Zoned Alarm is changed from the default Temporal Code to 20bpm, NAC 2 should not be
Supervisory signaling.
2. A Manual Release will start the Releasing Timer and operate the NAC cadence pattern associated with the start of the
Release Timer in the I/O matrix for the application selected.
6. In Preaction/Deluge applications configured for Class A/B (i.e. non-Style C), a short on any IDC
immediate manual release.
3. A Manual Release will override an Abort. In an abort condition the NACs will operate in accordance with the active Sta
2, and 3 operation in the I/O matrix for application selected and the specific Abort operation selected.
7. In Preaction/Deluge applications configured for Style C operation, SPM2 activates a manual rele
hazards.
4. Optional operation is selectable for 20bpm or Temporal Code. When Temporal Code is selected for the Alarm NAC
operation, the Supervisory NAC signal will be 20BPM. When 20BPM is selected for the Alarm NAC operation, the
Supervisory NAC signal will be temporal code.
8. For application mode 9 only, RAC2 is not used as a releasing circuit; instead it becomes a third N