ANNEX B - CCTV DETAILS
60
The top left hand corner of the overlay gives status information about configurable options and the
delay settings as follows:
B 1.2
ALARM STATE
If the detector enters the alarm state then the overlay will change to report the event and highlight
the location of the fire within the field of view. The alarm will be identified by a box shown on the
overlay which encloses the fire with “ALARM” flashing at the top. The box will adjust in size
according to the size of the fire. The log counter will be displayed to show where the event is
recorded in the detectors internal log.
Fig. B-2 Shows the alarm location box and information fields on the text overlay.
The identity fields are now displayed next to the box on the text overlay. If the location and identity
field is empty then, the serial number will be displayed instead. These fields will move according
to the size and position of the alarm box so that the information can be seen on the overlay. Their
position will depend on where the alarm is within the field of view and how big it is. The fields
showing the status of options are not displayed.
Overlay Field
Description
D
This field shows the selected alarm delay setting:
S – Short delay
M – Medium delay (default)
L – Long delay
X – Extra long delay
O
Shows the mode of the OPM test:
<D> for manual (on Demand) or <A> for automatic. (Timed)
W
Shows the window heater status:
<-> window heater disabled, <W> window heater enabled
M
Shows the alarm mask status:
<->mask is disabled, <M> mask is enabled.
Fig. B-2
Alarm State Overlay
www.acornfiresecurity.com