ANNEX A - MODBUS OVERVIEW
55
The Modbus parameters are configured on the Network tab of the PC300 configuration tool.
Note:
When Modbus is enabled or disabled or if the network parameters are changed
then the detector needs to be powered down and up or restarted from the
configuration tool to activate the new settings.
A1.4 SUPPORTED MODBUS FUNCTION CODES
The FV300 supports the following MODBUS Function Codes:
A1.4.1
FV300 REGISTERS
The FV300 has one block of 16 bit registers used for MODBUS access organised as
follows:
Code
Function
03
Read Holding Registers
04
Read Input Registers
06
Write Single Register
16
Write Multiple Registers
Offset
Register
Data
Read/Write (R/W)
00
Commands
See 1.4.2
R/W
01
Reserved
02
Reserved
03
Reserved
04
Reserved
05
Reserved
06
Reserved
07
Reserved
08
Overall Status
See 1.4.3
R
09
4-20mA level
4-20mA level x 1000
e.g. Alarm=17mA,Value=17000
R
10
1
st
Cluster state
0
CS
R
11
1
st
Cluster centre
X (0-255)
Y (0-255)
R
12
1
st
Cluster size
SX (0-255)
SY (0-255)
R
13
2
nd
Cluster state
0
CS
R
14
2
nd
Cluster centre
X (0-255)
Y (0-255)
R
15
2
nd
Cluster size
SX (0-255)
SY (0-255)
R
16
3
rd
Cluster state
0
CS
R
17
3
rd
Cluster centre
X (0-255)
Y (0-255)
R
18
3
rd
Cluster size
SX (0-255)
SY (0-255)
R
19
4
th
Cluster state
0
CS
R
20
4
th
Cluster centre
X (0-255)
Y (0-255)
R
21
4
th
Cluster size
SX (0-255)
SY (0-255)
R
Table. 6
www.acornfiresecurity.com