COMMISSIONING
45
7.2.4
RELAY CONTACT HEADER SETTINGS
The fire and fault relays can be used as either normally closed or normally open contacts. The
contacts are selected by fitting links to CON3 and CON4 on the terminal board, see Fig. 29. The
links must be fitted for the output to operate.
TB2
CON3
CON4
F
A
UL
T
CONT
A
CTS
ALARM
CONT
A
CTS
14 & 15 CONNECTED IF DETECT
OR IN F
A
UL
T (N/C)
14 & 15 CONNECTED IF DETECT
OR OK (N/O)
17 & 18 CONNECTED IF DETECT
OR NO
T IN ALARM (N/C)
17 & 18 CONNECTED IF DETECT
OR IN ALARM (N/O)
POSITIONS
NORMALL
Y
USED
TB1
TB2
S300 RELA
Y / 4 - 20mA
FIELDB
US TERMINAL
PCB
24V
4 - 20
0v
0v
FB+
FB-
EXC+
EXC-
VID+
VID-
24V
WT
0V
FL
T
FL
TC
ALED
ALM
ALMC
SCRI
SCR
O
10
20
THE LINKS MUST BE FITTED FOR
THE OUTPUT
T
O OPERA
TE
Fig. 29
Header Settings on Terminal Board