background image

Model ESFR-17 

16.8 K-factor Pendent Sprinkler 

Early Suppression, Fast Response

Page 1 of 4 

APRIL 2015 

TFP317

IMPORTANT

Always refer to Technical Data 

Sheet TFP700 for the “INSTALLER  

WARNING” that provides cautions 

with respect to handling and instal-

lation of sprinkler systems and com-

ponents. Improper handling and 

installation can permanently damage 

a sprinkler system or its compo-

nents and cause the sprinkler to fail  

to operate in a fire situation or cause  

it to operate prematurely.

Technical 

Data

Approvals

UL Listed 

C-UL Listed 

FM Approved

Maximum Working Pressure

175 psi (12,1 bar)

Pipe Thread Connections

3/4 Inch NPT or

 

ISO 7-R 3/4

Discharge Coefficient

K=16.8 gpm/psi

1/2

 (241,9 lpm/bar

1/2

)

Temperature Ratings

165°F (74°C) and 212°F (100°C)

Finish

Natural Brass

Physical Characteristics

Frame  . . . . . . . . . . . . . . . . . . . . . . . . . . . . .Brass 

Deflector . . . . . . . . . . . . . . . . . . . . . . . . . .Bronze 

Compression Screw . . . . . . . . . .  Stainless Steel 

Hook . . . . . . . . . . . . . . . . . . . . . . . . . . . . MONEL 

Strut. . . . . . . . . . . . . . . . . . . . . . . . . . . . . MONEL 

Link Assembly . . . . . . . . . . . . . . . . Solder, Nickel 

Button  . . . . . . . . . . . . . . . . . . . Phosphor Bronze 

Sealing Assembly  . . Beryllium Nickel w/TEFLON 

General 

Description

TYCO Model ESFR-17 Pendent Sprin-

klers are Early Suppression, Fast 

Response (ESFR) sprinklers having a 

nominal K-factor of 16.8 (Ref. Figures 

1 and 2). They are suppression mode 

sprinklers that are especially advanta-

geous as a means of eliminating in-rack 

sprinklers when protecting high-piled 

storage.
Model ESFR-17 Pendent Sprinklers are 

primarily used for ceiling-only sprinkler 

protection of (but not limited to) the fol-

lowing storage applications:
•  most encapsulated or non-encap-

sulated common materials including 

cartoned, unexpanded plastics

•  cartoned, expanded plastics
•  uncartoned, unexpanded plastics
•  uncartoned, expanded plastics
•  some storage arrangements of 

rubber tires, roll paper, and aerosols

For more specific criteria, refer to Table 

1 in this technical data sheet as well as 

the applicable design standard.
The Model ESFR-17 Pendent Sprin-

klers provide the system designer 

with hydraulic and sprinkler place-

ment options not presently available 

to traditional ESFR Sprinklers having 

a nominal K-factor of 14.0. In particu-

lar, Model ESFR-17 Pendent Sprinklers 

are designed to operate at substan-

tially lower-end head pressures, as 

compared to ESFR Sprinklers having 

a nominal K-factor of 14.0. This feature 

offers flexibility when sizing system 

piping, as well as possibly reducing or 

eliminating the need for a system fire 

pump.
Applications for the ESFR-17 Pendent 

Sprinklers are expanding beyond cur-

rently recognized installation stan-

dards. For information on research fire 

tests (with flammable liquids and aero-

sols, for example) that may be accept-

able to an authority having jurisdiction, 

contact Tyco Fire Protection Products 

(TFPP) Technical Services.

NOTICE

The Model ESFR-17 Pendent Sprinklers 

described herein must be installed and 

maintained in compliance with this doc-

ument, as well as with the applicable 

standards of the National Fire Protec-

tion Association (NFPA), in addition to 

the standards of any authorities having 

jurisdiction (e.g., FM Global). Failure to 

do so may impair the performance of 

these devices.
The owner is responsible for main-

taining their fire protection system 

and devices in proper operating con-

dition. Contact the installing contrac-

tor or product manufacturer with any 

questions.
In all cases, the appropriate NFPA or 

FM Global installation standard, or 

other applicable standard, must be ref-

erenced to ensure applicability and to 

obtain complete installation guidelines. 

The general guidelines in this technical 

data sheet are not intended to provide 

complete installation criteria.

Sprinkler 

Identification 

Number (SIN)

TY7223