7
Wire Length
Tables
Table 2 and Table 3 show the maximum wire lengths possible for the power wiring. Table 4 and
Table 5 show the maximum wire lengths for the communication wiring.
•
When using multiple annunciators and runs, the total of all runs must not exceed 10,000 feet
(304.8 m, including T-Taps).
•
Four 2081-9044 Overvoltage Protectors are the maximum number permitted on any single
communication loop.
Power Wiring
Length Tables
Table 2. Wire Length with 2081-9044 Overvoltage Protectors
Table 3. Without Transient Suppression
Total Current
(Amps)
12 AWG
(3.309 mm²)
14 AWG
(2.801 mm²)
16 AWG
(1.309 mm²)
18 AWG
(0.823 mm²)
0.100 2,500
ft.
(762 m)
2,500 ft.
(762 m)
2,371 ft.
(722.68 m)
1,409 ft.
(429.46 m)
0.200
2,500 ft.
(762 m)
1,782 ft.
(543.15 m)
889 ft.
(270.96 m)
705 ft.
(214.88 m)
Total Current
(Amps)
12 AWG
(3.309 mm²)
14 AWG
(2.801 mm²)
16 AWG
(1.309 mm²)
18 AWG
(0.823 mm²)
0.100
2,500 ft.
(762 m)
2,500 ft.
(762 m)
2,500 ft.
(762 m)
2,349 ft.
(715.97 m)
0.200
2,500 ft.
(762 m)
2,500 ft.
(762 m)
1,482 ft.
(451.71 m)
1,175 ft.
(358.14 m)
0.300
2,500 ft.
(762 m)
1,980 ft.
(603.5 m)
988 ft.
(301.14 m)
783 ft.
(238.65 m)
0.400
2,361 ft.
(719.63 m)
1,485 ft.
(452.62 m)
741 ft.
(225.85 m)
587 ft.
(178.91 m)
0.500
1,889 ft.
(575.76 m)
1,188 ft.
(362.1 m)
593 ft.
(180.74 m)
470 ft.
(143.25 m)
0.600
1,574 ft.
(479,75 m)
990 ft.
(301.75 m)
494 ft.
(150.57 m)
392 ft.
(119.48 m)
0.700
1,349 ft.
(411.17 m)
849 ft.
(258.77 m)
423 ft.
(128.93 m)
336 ft.
(102.41 m)
0.800
1,181 ft.
(359.96 m)
743 ft.
(226.46 m)
371 ft.
(113.08 m)
294 ft.
(89.61 m)
0.900
1,049 ft.
(319.73 m)
660 ft.
(201.16 m)
329 ft.
(100.27 m)
261 ft.
(79.55 m)
1.000
944 ft.
(287.73 m)
594 ft.
(181 m)
296 ft.
(90.22 m)
235 ft.
(71.62 m)
1.100
859 ft.
(261.82 m)
540 ft.
(164.59 m)
269 ft.
(81.99 m)
214 ft.
(65.22 m)
1.200
787 ft.
(239.87 m)
495 ft.
(150.87 m)
247 ft.
(75.28 m)
196 ft.
(59.74 m)
Color Touchscreen LCD Annunciator Installation Instructions,
Continued
Содержание AutoPulse Z-20
Страница 12: ...579 1172AR Rev A...