STAR SPRINKLER

Page 8

1-3.2.50

GRAPH D

MAXIMUM WATER SPRAY DISTRIBUTION WHEN A SPRINKLER IS LOCATED ON A PITCHED CEILING

OPPOSITE FROM AN INTERSECTING PITCHED CEILING

NOTES:

1.

UP TO A MAXIMUM OF ONE-HALF THE LENGTH OF THE
COVERAGE AREA BEING HYDRAULICALLY
CALCULATED.

2.

3 FEET IS THE MAXIMUM PERMITTED AND 1 FOOT IS
THE MINIMUM REQUIRED.

GRAPH C

MAXIMUM WATER SPRAY DISTRIBUTION WHEN A SPRINKLER IS LOCATED AT A PEAK

NOTES:

1.

UP TO A MAXIMUM OF ONE-HALF THE LENGTH OF THE
COVERAGE AREA BEING HYDRAULICALLY
CALCULATED.

2.

THE MOUNTING SURFACE MUST BE LOCATED
WITHIN 4 TO 6 INCHES OF THE PEAK, IF IT IS NOT
CONTINUOUS OVER THE FULL LENGTH OF THE
CEILING RIDGE.

GRAPH E

MINIMUM REQUIRED SLANT DISTANCE BETWEEN A RIDGE AND A SPRINKLER

WITHOUT UNDULY OBSTRUCTING THE WATER DISTRIBUTION

NOTE:

UP TO A MAXIMUM OF ONE-HALF THE LENGTH OF THE COVERAGE

AREA BEING HYDRAULICALLY CALCULATED.

COVERAGE AREAS:

(a)

20’ x 20’

(b)

18’ x 18’

(c)

16’ x 16’

(d)

14’ x 14’

(e)

12’ x 12’

7071 S. 13th Street • Suite 103

Oak Creek, WI 53154

www.starsprinkler.com

PRINTED IN U.S.A. 3-01

OBSOLETE

Содержание Star TFP1

Страница 1: ...annot be fully sprinklered in accordance with the recommendations of NFPA 13 13D or 13R In the event of this condi tion consult the authorities having jurisdiction for guidance and approval It is the...

Страница 2: ...nimum required single and multiple sprinkler flow rates for systems designed to NFPA 13D or NFPA 13R are given in Table A as a func tion of temperature rating and the maximum allowable coverage areas...

Страница 3: ...For proper operational sensitivity the Model TFP1 must be installed beneath a solid ceiling having a smooth or textured surface The Model TFP1 must NOT be used above or below open gridded type suspen...

Страница 4: ...e ceiling ridge is horizontal b the compartment openings to adjoining spaces have minimum lintel depths of 8 inches below the lowest sprinkler c any adjacent sprinklers in the direction of the ceiling...

Страница 5: ...he Sprinkler into the sprinkler fit ting Step 4 Wrench tighten the Sprinkler using only the 4947 Sprinkler Socket or 4948 Wrench Socket Com bination Ref Figure 4 The wrench recess of the 4947 is to be...

Страница 6: ...ability of the sprinkler system to aid in the control of a fire in which they are involved Sprinklers which are found to be leaking or exhibiting vis ible signs of corrosion must be replaced Automatic...

Страница 7: ...Buyer s representatives IN NO EVENT SHALL TYCO FIRE PRODUCTS BE LI ABLE IN CONTRACT TORT STRICT LIABILITY OR UN DER ANY OTHER LEGAL THEORY FOR INCIDENTAL INDIRECT SPECIAL OR CONSEQUENTIAL DAMAGES INCL...

Страница 8: ...UP TO A MAXIMUM OF ONE HALF THE LENGTH OF THE COVERAGE AREA BEING HYDRAULICALLY CALCULATED 2 THE MOUNTING SURFACE MUST BE LOCATED WITHIN 4 TO 6 INCHES OF THE PEAK IF IT IS NOT CONTINUOUS OVER THE FUL...