background image

CARE AND MAINTENANCE

The Model TFP1 must be maintained and serviced in ac-
cordance with the following instructions:

NOTES

It is the responsibility of the installing contractor to
provide a copy of this document to the owner or his
representative, and in turn, it is the obligation of the
owner to provide a copy of this document to a suc-
ceeding owner.

Wet pipe sprinkler systems must be maintained at a
minimum temperature of 40°F/4°C to prevent freezing
and bursting of the pipe and/or sprinklers.

Automatic sprinklers are not to be tested with a heat
source. Operation of the heat responsive element can
result.

Absence of an Escutcheon Plate may delay the time
to sprinkler operation in a fire situation.

Before closing a fire protection system main control
valve for maintenance work on the fire protection sys-
tem which it controls, permission to shut down the af-
fected fire protection system must be obtained from
the proper authorities and all personnel who may be
affected by this action must be notified.

Do NOT enclose sprinklers within drapes, curtains, or
valances.

Do NOT hang anything from the sprinklers.

Do NOT cleanse the sprinklers with soap and water,
detergents, ammonia, cleaning fluids, or other chemi-
cals. Remove dust, lint, cobwebs, cocoons, insects,
and larvae by gently brushing with a feather duster or
gently vacuuming with a soft bristle (i.e., dusting)
brush attachment.

Exercise suitable safety precautions in the use and
storage of highly flammable materials. The rapid rate
of fire development and spread of which can be
caused by such materials can reduce the ability of
the sprinkler system to aid in the control of a fire in
which they are involved.

Sprinklers which are found to be leaking or exhibiting vis-
ible signs of corrosion must be replaced.

Automatic sprinklers must never be shipped or stored
where its temperature will exceed 100°F/38°C and they
must never be painted, plated, coated, or otherwise al-
tered after leaving the factory. Modified or over heated
sprinklers must be replaced.

Care must be exercised to avoid damage - before, dur-
ing, and after installation. Sprinklers damaged by drop-
ping, striking, wrench twist/slippage, or the like, must be
replaced.

The Model TFP1 must only be replaced with pendent
sprinklers which are listed for residential fire protection
service and which have the same nominal K-factor, the
same coverage area, and the same or lower flow ratings
(as indicated under “Hydraulic Design Criteria”).

When remodeling, such as by adding false beams or light
fixtures or changing the location of compartment walls,
first verify that the new construction will not violate the in-
stallation requirements stated under WARNINGS. Alter
the new construction and/or the sprinkler system to suit
the requirements of this document.

The owner is responsible for the inspection, testing, and

maintainance of their fire protection system and devices
in compliance with this document, as well as with the ap-
plicable standards of the National Fire Protection Associa-
tion (e.g., NFPA 25), in addition to the standards of any
other authorities having jurisdiction. The installing contrac-
tor or sprinkler manufacturer should be contacted relative
to any questions.

It is recommended that automatic sprinkler systems be in-
spected, tested, and maintained by a qualified Inspection
Service.

STAR SPRINKLER

Page 6

1-3.2.50

OBSOLETE

Содержание Star TFP1

Страница 1: ...annot be fully sprinklered in accordance with the recommendations of NFPA 13 13D or 13R In the event of this condi tion consult the authorities having jurisdiction for guidance and approval It is the...

Страница 2: ...nimum required single and multiple sprinkler flow rates for systems designed to NFPA 13D or NFPA 13R are given in Table A as a func tion of temperature rating and the maximum allowable coverage areas...

Страница 3: ...For proper operational sensitivity the Model TFP1 must be installed beneath a solid ceiling having a smooth or textured surface The Model TFP1 must NOT be used above or below open gridded type suspen...

Страница 4: ...e ceiling ridge is horizontal b the compartment openings to adjoining spaces have minimum lintel depths of 8 inches below the lowest sprinkler c any adjacent sprinklers in the direction of the ceiling...

Страница 5: ...he Sprinkler into the sprinkler fit ting Step 4 Wrench tighten the Sprinkler using only the 4947 Sprinkler Socket or 4948 Wrench Socket Com bination Ref Figure 4 The wrench recess of the 4947 is to be...

Страница 6: ...ability of the sprinkler system to aid in the control of a fire in which they are involved Sprinklers which are found to be leaking or exhibiting vis ible signs of corrosion must be replaced Automatic...

Страница 7: ...Buyer s representatives IN NO EVENT SHALL TYCO FIRE PRODUCTS BE LI ABLE IN CONTRACT TORT STRICT LIABILITY OR UN DER ANY OTHER LEGAL THEORY FOR INCIDENTAL INDIRECT SPECIAL OR CONSEQUENTIAL DAMAGES INCL...

Страница 8: ...UP TO A MAXIMUM OF ONE HALF THE LENGTH OF THE COVERAGE AREA BEING HYDRAULICALLY CALCULATED 2 THE MOUNTING SURFACE MUST BE LOCATED WITHIN 4 TO 6 INCHES OF THE PEAK IF IT IS NOT CONTINUOUS OVER THE FUL...

Отзывы: