GRAPH A

MAXIMUM PERMITTED VERTICAL DISTANCE BETWEEN THE SPRINKLER MOUNTING SURFACE AND

THE BOTTOM OF CEILING MOUNTED OBSTRUCTIONS SUCH AS BEAMS, OVERHANGS, AND LIGHT FIXTURES

WITHOUT UNDULY OBSTRUCTING THE WATER SPRAY DISTRIBUTION

NOTES:

1.

CEILING OBSTRUCTIONS MUST BE SPACED ON THE BASIS OF USING THE MAXIMUM RESIDUAL PRESSURE WHICH WOULD BE
PRESENT FOR A SINGLE SPRINKLER OPERATION.

2.

BEAMS AND/OR OTHER CONTINUOUS OBSTRUCTIONS ARE NOT TO EXCEED A VERTICAL DEPTH ‘V’ OF MORE THAN 3 INCHES
WITHIN THE SPRINKLER COVERAGE AREA.

STAR SPRINKLER

Page 6

1-3.2.30

Horizontal

Vertical

Distance from

Clearance

Sprinkler to

Below

Obstruction

Sprinkler

Below Sprinkler

Deflector, in.

Deflector, ft.

More than 6

24

From 3 to 6

19

Between 2 and 3

16

From 1 to 2

13

Less than 1

10

TABLE B

MINIMUM VERTICAL

CLEARANCE BETWEEN

TOP OF FREE STANDING

OBSTRUCTION AND

SPRINKLER DEFLECTOR

FIGURE 5

W-TYPE 7 SPRINKLER

WRENCH

RECESS

WRENCH

WITH SPRINKLER

ENGAGEMENT

IN TO ENSURE

WRENCHING AREA

PUSH WRENCH

OBSOLETE

Содержание Star Mizar S210

Страница 1: ...tion Failure to do so may impair the integrity of these devices Because of the above cited stipulations and the var ied nature of residential type architecture there will be some compartment designs...

Страница 2: ...fective date of May 22 2000 states that the minimum required discharge from each of the design sprinklers for sys tems designed to NFPA 13 must be calculated based on delivering a minimum design densi...

Страница 3: ...PLATE MOUNTING S210 2 7 8 DIA 73 0 mm 2 3 16 55 6 mm 1 1 2 38 1 mm ESCUTCHEON PLATE SEATING SURFACE FLATS WRENCH 1 2 NPT BOTH SIDES 7 16 11 1 mm NOMINAL MAKE IN STAR SPRINKLER 1 3 2 30 Page 3 a For c...

Страница 4: ...s stor age racks stock piles etc and the sprinkler deflector is NOT to be less than the clearance given in Table B Sprinklers which are found to be leaking or exhibiting vis ible signs of corrosion mu...

Страница 5: ...have minimum lintel depths of 8 inches below the lowest sprinkler c any adjacent sprinklers in the direction of the ceiling ridge are to be in a row which runs parallel to the ridge and the sprinklers...

Страница 6: ...R OTHER CONTINUOUS OBSTRUCTIONS ARE NOT TO EXCEED A VERTICAL DEPTH V OF MORE THAN 3 INCHES WITHIN THE SPRINKLER COVERAGE AREA STAR SPRINKLER Page 6 1 3 2 30 Horizontal Vertical Distance from Clearance...

Страница 7: ...ssumes nor authorizes any person to assume for it any other obligation in connec tion with the sale of products or parts of products Tyco Fire Products shall not be responsible for sprinkler sys tem d...

Страница 8: ...M REQUIRED SLANT DISTANCE BETWEEN A RIDGE AND A SPRINKLER WITHOUT UNDULY OBSTRUCTING THE WATER DISTRIBUTION NOTES 1 UP TO A MAXIMUM OF ONE HALF THE LENGTH OF THE COVERAGE AREA BEING HYDRAULICALLY CALC...

Отзывы: