background image

ing ridges must be installed with their frame arms per-
pendicular to the ceiling ridges.

Failure to properly orientate the sprinkler frame arms
may result in impaired fire protection due to cold sol-
dering and/or inadequate spray coverage.

Do not attempt to compensate for insufficient adjust-
ment in an Escutcheon Plate by under- or over-tight-
ening the Sprinkler. Readjust the position of the sprin-
kler fitting to suit.

1. The sprinkler must only be installed in the pendent position

and with the deflector parallel to the mounting surface.

2. After installing the #2084 or #2085 mounting plate (or other

acceptable escutcheon, as applicable) over the sprinkler
pipe threads and with pipe thread sealant applied to the
pipe threads, hand tighten the sprinkler into the sprinkler
fitting.

3. Wrench tighten the sprinkler using only a W-Type 7 Sprin-

kler Wrench (Ref. Figure 5). The wrench recess of the
W-Type 7 is to be applied to the sprinkler wrench flats (Ref.
Figure 1).

FIGURE 1

MIZAR S210 RESIDENTIAL

PENDENT SPRINKLER

FIGURE 2A

155°F, MIZAR S210 RESIDENTIAL SPRINKLER

WITH #2085 RECESSED ESCUTCHEON

2-1/4" DIA.

(57.2 mm)

SPRINKLER

FACE OF

FITTING

SURFACE

MOUNTING

1/8"

(3.2 mm)

3/4" (19.1 mm)

1-1/4" (31.8 mm)

1/4" (6.4 mm)

3/4" (19.1 mm)

5/8±1/4"

(15.9±6.4 mm)

CLOSURE

PLATE

MOUNTING

S210

2-7/8" DIA.

(73.0 mm)

2-3/16"

(55.6 mm)

1-1/2"

(38.1 mm)

ESCUTCHEON

PLATE SEATING

SURFACE

FLATS

WRENCH

1/2" NPT

(BOTH SIDES)

7/16" (11.1 mm)

NOMINAL MAKE-IN

STAR SPRINKLER

1-3.2.30

Page 3

(a) For coverage area dimensions less than or between those

indicated, it is necessary to use the minimum required flow for
the next highest coverage area for which hydraulic design
criteria are stated.

(b) Requirement is based on minimum flow in GPM from each

sprinkler. The associated residual pressures are calculated
using the nominal K-factor. Refer to Hydraulic Design Criteria
Section for details.

TABLE A

NFPA 13D AND NFPA 13R

HYDRAULIC DESIGN CRITERIA

12 x 12

MAXIMUM

COVERAGE

AREA

(a)

FT. x FT.

175°F

SINGLE

SPRINKLER

Minimum Flow

(b)

(Residual Pressure)

14 x 14

16 x 16

18 x 18

20 x 20

10 GPM

(11.1 PSI)

8 GPM

(7.1 PSI)

11 GPM

(13.4 PSI)

11 GPM

(13.4 PSI)

13 GPM

(18.8 PSI)

13 GPM

(18.8 PSI)

16 GPM

(28.4 PSI)

16 GPM

(28.4 PSI)

9 GPM

(9.0 PSI)

8 GPM

(7.1 PSI)

155°F

MULTIPLE

SPRINKLERS

Minimum Flow

(b)

(Residual Pressure)

155°F

175°F

9 GPM

(9.0 PSI)

11 GPM

(13.4 PSI)

11 GPM

(13.4 PSI)

13 GPM

(18.8 PSI)

16 GPM

(28.4 PSI)

9 GPM

(9.0 PSI)

9 GPM

(9.0 PSI)

11 GPM

(13.4 PSI)

13 GPM

(18.8 PSI)

16 GPM

(28.4 PSI)

2-7/8" DIA.

(73.0 mm)

2-1/4" DIA.

(57.2 mm)

SPRINKLER

FACE OF

FITTING

SURFACE

MOUNTING

1/8"

(3.2 mm)

1" (25.4 mm)

1-1/4" (31.8 mm)

1/4" (6.4 mm)

1/2" (12.7 mm)

1/2±1/8"

(12.7±3.2 mm)

CLOSURE

PLATE

MOUNTING

S210

FIGURE 2B

175°F, MIZAR S210 RESIDENTIAL SPRINKLER

WITH #2084 RECESSED ESCUTCHEON

OBSOLETE

Содержание Star Mizar S210

Страница 1: ...tion Failure to do so may impair the integrity of these devices Because of the above cited stipulations and the var ied nature of residential type architecture there will be some compartment designs...

Страница 2: ...fective date of May 22 2000 states that the minimum required discharge from each of the design sprinklers for sys tems designed to NFPA 13 must be calculated based on delivering a minimum design densi...

Страница 3: ...PLATE MOUNTING S210 2 7 8 DIA 73 0 mm 2 3 16 55 6 mm 1 1 2 38 1 mm ESCUTCHEON PLATE SEATING SURFACE FLATS WRENCH 1 2 NPT BOTH SIDES 7 16 11 1 mm NOMINAL MAKE IN STAR SPRINKLER 1 3 2 30 Page 3 a For c...

Страница 4: ...s stor age racks stock piles etc and the sprinkler deflector is NOT to be less than the clearance given in Table B Sprinklers which are found to be leaking or exhibiting vis ible signs of corrosion mu...

Страница 5: ...have minimum lintel depths of 8 inches below the lowest sprinkler c any adjacent sprinklers in the direction of the ceiling ridge are to be in a row which runs parallel to the ridge and the sprinklers...

Страница 6: ...R OTHER CONTINUOUS OBSTRUCTIONS ARE NOT TO EXCEED A VERTICAL DEPTH V OF MORE THAN 3 INCHES WITHIN THE SPRINKLER COVERAGE AREA STAR SPRINKLER Page 6 1 3 2 30 Horizontal Vertical Distance from Clearance...

Страница 7: ...ssumes nor authorizes any person to assume for it any other obligation in connec tion with the sale of products or parts of products Tyco Fire Products shall not be responsible for sprinkler sys tem d...

Страница 8: ...M REQUIRED SLANT DISTANCE BETWEEN A RIDGE AND A SPRINKLER WITHOUT UNDULY OBSTRUCTING THE WATER DISTRIBUTION NOTES 1 UP TO A MAXIMUM OF ONE HALF THE LENGTH OF THE COVERAGE AREA BEING HYDRAULICALLY CALC...

Отзывы: